19
Wiring Instructions
Make sure the power supply switch is OFF before carrying out work on
the wiring or inspections involving disassembly.
If such work is carried out with the power on, there is a danger that
equipment may malfunction or electric shock may occur, leading to
injury or other accidents.
CAUTION
Make sure that wiring work requiring a special license is carried out by
qualified personnel.If carried out by unqualified personnel, overheating
or short circuits leading to injury, fires, damage or other accidents may
occur.
CAUTION
Drive Section Terminal Box
Drive Section Terminal Block
MC-COSR
Terminal
Box
Controller Terminal Block
Shield
Shield Cable
Power Supply
100 – 240 V AC
When making a connection to the terminal block, use crimp-style jacks (for M4) with
insulation sleeves.
(0.35 in)
(0.24 in)
6.3 mm
(0.24 in)
4.3 mm
(0.17 in)
6.6 mm
(0.26 in)
MAX
MIN
9.0 mm
(0.35 in)
Recommended Cable Specifications
Cable Specifications
Actuator
Terminal No.
Minimum
Cross Section
mm
2
(in
2
)
Maximum Wire
Gauge No.
(AWG)*
Cable Type
Power Source
1, 2
1.25 (0.002)
16
GND
2.00 (0.003)
14
Cabtyre cable
Valve Operation
Signals
3 (shield),
4 (
), 5 (
)
0.75 (0.001)
18
2 conductor
shielded cable
* (American Wire Gauge)
172-65185A-08 (MC-COSR Multi-control Valve) 20 Nov 2014