172-65185A-08 (MC-COSR Multi-control Valve) 20 Nov 2014
Malfunctions and Countermeasures
○
:OFF
●
:ON
LE 4, 3, 2, 1
Malfunction Details
Performance of the
actuator when
abnormality occurs
Remedy
○○○○
No malfunction is
detected (All LEDs
are normally OFF)
Continuous operation
○○○●
Operation signal
input error
Continuous operation
Operation input signal is
abnormal.
Make sure that there is no
abnormality with the
controller and the cable for
the operation input signal.
●○○○
Temperature in the
actuator is
abnormal
Continuous operation
Make sure that the
temperature around the
drive section is within the
specification range (0 to
50 °C (32 – 122 F°).
○○●●
Motor is
overloaded
Motor shuts down,
then keep rebooting
after a few seconds.
Motor is abnormally
overloaded. Contact
TLV.
○●○●
Low motor load
(reducer gear wear,
motor slippage)
Continuous operation
Possibility of abnormal wear
of the gear in the reducer.
Contact TLV.
●○○●
Potentiometer
signal error
Stops when
malfunction occurs
Potentiometer is
abnormal. Contact TLV.
●○●○
Initialization error
Stops when
malfunction occurs
●●○○
E
2
PROM Store
Error
Stops when
malfunction occurs
If the same phenomenon
occurs after switching the
power OFF and ON, contact
TLV.
○●●●
Motor drive power
voltage is
abnormal
Continuous
operation
Possible abnormality of
the power supply circuit is
considered. Contact TLV.
●○●●
CPU Error
Stops when
malfunction occurs
If the same phenomenon
occurs after switching the
power OFF and ON, contact
TLV.
●●●○
External clock
stops
Continuous operation
using internal clock
●●●●
Mode Setting Error Stops
Possible abnormality of
the internal circuit.
Contact TLV.
○○●○
(spare)
Continuous operation
○●○○
(spare)
Continuous operation
○●●○
(spare)
Continuous operation
●●○●
(spare)
Continuous operation