172-65185A-08 (MC-COSR Multi-control Valve) 20 Nov 2014
12
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Use hoisting equipment for heavy objects (weighing approximately
20 kg (44 lb) or more). Failure to do so may result in back strain or other
injury if the object should fall.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
Installation Environment
Avoid installation in the following types of environments:
Locations with ambient temperatures above 50 °C (122 °F) or below 0 °C (32 °F)
Locations with ambient humidity above 90% RH and below 10% RH
Locations where corrosive gas is generated
Locations with heavy vibration or shock
Locations with high inductive interference or other factors that would have a
harmful effect on electrical circuitry
1. Blowdown
Before installing the MC-COSR, be
sure to blow down all piping
thoroughly. If this is not possible,
perform a blowdown using the
bypass valve.
Blowdown is especially important
for newly installed piping or after
the system has been shut down for
a long period of time.
開
閉
閉
バイパス配管利用のブロー
M C -C O SR
Open
Closed
Closed
Blowdown with the Bypass Valve
2. Removing Seal and Cap
Before installation, be sure to remove all protective seals and caps
covering the product inlet and outlets. (Found in 2 locations.)
①
②
3.
Installation Angle
Install the MC-COSR vertically, so that the arrow mark on
the body points horizontally in the direction of steam flow.
Allowable inclination is 10 degrees in the fore-aft direction
and 15 degrees side to side in the plane perpendicular to
the steam flow line.