Non-video signal lines must use appropriate shielded Cat 5 cabling (S-FTP), or at least an
equivalent. Ensure that all electrically connected components are carefully earthed and
protected against surges (high voltage transients caused by switching or lightning).
ESD
Electrostatic discharge (ESD) can damage or destroy electronic components. Proper
precautions should be taken against ESD when opening the equipment.
RoHS
Global concerns over the health and environmental risks associated with the
use of certain environmentally-sensitive materials in electronic products have
led the European Union (EU) to enact the Directive on the Restriction of the
use of certain Hazardous Substances (RoHS) (2011/65/EU). TKH Security
offers products that comply with the EU’s RoHS Directive.
Product disposal
The unit contains valuable materials which qualify for recycling. In the
interest of protecting the natural environment, properly recycling the unit at
the end of its service life is imperative.
When processing the printed circuit board, dismantling the lithium battery
calls for special attention. This kind of battery, a button cell type, contains so
little lithium, that it will never be classified as reactive hazardous waste. It is
safe for normal disposal, as required for batteries by your local authority.
2.2
Protection against overvoltage
Note: The following instructions must be observed for outdoor installations.
The installer is responsible for protection of the camera against overvoltage.
These international standards apply (equivalent standards may also be used):
● IEC 60364-4-44 Electrical installations of buildings - Part 4-443:
Protection against overvoltages of atmospheric origin or due to switching.
● IEC 60364-5-53 Electrical installations of buildings - Part 5-534:
Devices for protection against overvoltages
● IEC 62305 Protection against lightning – All parts
The information below can be used to determine the required measures.
Transient overvoltage immunity test level
The equipment installed in this outdoor enclosure, including camera and power supply, is
tested for application in an industrial environment. The transient overvoltage immunity is
tested according IEC 61000-6-2 and IEC 61000-4-5 for industrial levels.
● For AC power ports the test level is 2kV Line to Earth and 1kV Line to Line.
● For signal ports the test level is 1kV Line to Earth. (no Line to Line test required)
Safety and compliance
10