SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED 

WITH A 24 OR 115 VAC STANDING PILOT

115V

24V

DRY

OF FURNACE/BOILER

INTERNAL CONTROLS

24V OR 115V GAS VALVE

HOT

COM

B2

COM
TR

Aquastat

T-stat

TH

HOT

B1

XL

UN
IV

ER
SA
L CO

NT
RO
LL

E

R

XN

J1

J2

RED JUMPER POSITION MUST BE THE SAME

AS APPLIANCE INTERLOCK VOLTAGE.

IMPORTANT:

D/N 9183046-1

24 OR 115 VAC

LEGEND:

CALL
JUMPER

115 VAC
50/60 Hz

SUPPLY

SS2 ELECTRICAL BOX.

CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN 

IMPORTANT:

115 VAC

1. Remove the wire on TH or HOT of gas valve and connect it on #1 on UC1 terminal block. 
2. Connect #2 on UC1 terminal block to TR or Common. 
3. Connect #4 on UC1 terminal block to TH or HOT on gas valve.
4. Connect 115 VAC supply voltage to L & N terminals on UC1.  Installer must supply overload and disconnect protection.
5. Crimp ground wire to grounding spade in SS2 electrical box.
6. Make sure RED voltage jumper on UC1 is on 24V or 115V depending on control voltage.

NOTE:

If burner safety control goes out on lockout, the SideShot will continue to run as long as a call for heat is present.

DRAFT ADJUSTMENT PROCEDURE FOR OIL EQUIPMENT

The SS2 Vent system will properly vent a wide range of BTU/hr. input capacities.  To compensate for different burner capacities, vent connector
lengths, types and sizes, it features a draft adjustment located on the back of the venter assembly.  Turning this draft adjustment knob clockwise will
increase draft and raise the BTU capacity.  Turning the knob counter-clockwise will decrease draft and lower the BTU capacity.  The SS2 is factory set
for the highest draft (BTU capacity). 

IMPORTANT:

Before proceeding, close all windows, doors and fireplace dampers.  Turn on all appliances in the structure that exhaust indoor air such as clothes
dryer, exhaust fans, range hoods, bathroom and whole house exhaust fans.  Failure to perform the draft adjustment procedure may cause a poor vent
system installation possibly resulting in fire, carbon monoxide poisoning, explosion, personal injury or property damage.

1. Insert a stack thermometer into the vent pipe as close as possible to the SS2 inlet. 

NOTE:

plug hole when finished with installation.

2. Adjust barometric draft control to the minimum or least draft setting.

3. Place the heating system into operation.  

NOTE:

There will be a slight pause between the venter operation and the burner operation.   A Venter pre-purge 

of up to 35 seconds may also be selected.  See “Pre / Post-Purge Settings” on page 5.

4. Continuously monitor the over fire draft and adjust the SS2 draft adjustment knob to maintain a  reading of 

-.02 to -.03” W.C.. When the flue gas temperature at the venter inlet has stabilized make any final draft 

adjustment necessary to maintain a reading of  -.02 to -.03” W.C..  

IMPORTANT:

If a minimum of -.02” W.C. 

cannot be obtained with the SS2 draft adjustment  knob turned fully clockwise and adjust barometric damper 
closed “more draft” until a reading of -.02” W.C. is obtained.

5.  Perform a smoke test and make any adjustments to the burner air shutter and venter draft adjustment to arrive at 

a trace of smoke (between 0 and 1) at a minimum over fire draft of -.02” W.C..

6.  Perform a CO2 test at the same location as the smoke test. Reduce the CO2  1% to 2% by opening the burner air 

shutter.  Recheck over fire draft and increase venter draft or adjust barometric damper closed “more draft” if 
necessary to maintain a minimum of -.02” W.C..

Do not allow heating system to run at less than a -.02” W.C. over fire draft or at a CO2 level that is less than a 1% reduction from the value measured at
a trace of smoke and a -.02” W.C. over fire draft. If these parameters are unobtainable, contact Tjernlund at 1-800-255-4208 for Technical Assistance. 

7.  Remove the call for heat from the heating system.  

NOTE:

The SS2 will run in post-purge mode which is factory set at 2 minutes and adjustable 

up to 16 minutes.  Allow the system to cool down to ambient room temperature.

8.  Restart the heating system.

DIAGRAM K

DRAFT ADJUSTMENT
LOCKING KEPS NUT

DRAFT

ADJUSTMENT

KNOB

TIGHTEN KEPS NUT
AGAINST BRACKET ONCE

DRAFT POSITION IS SET

Содержание SIDESHOT SS2

Страница 1: ...eries Because of the low set point of the SS1 Fan Prover as low as 03 w c cross winds may cause the Fan Prover to close prior to a call for heat Activating the Prover Status Check on the SS1 may cause...

Страница 2: ...es exceeding Venter limits excessive vent pipe runs elbows directly on venter discharge high winds plugged kinked Fan Prover sensing tube or a faulty Fan Prover switch In Forcer model s intake screen...

Страница 3: ...G IN FIRE ELECTRICAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE NOTE Oil burner capacities exceeding 1 GPH may require the burner to be adjusted to more efficient 12...

Страница 4: ...ipment to the outdoors By recirculating indoor air with a cooling fan surrounding com bustible materials remain at safe temperatures After each burner cycle the SS2 will continue to operate in post pu...

Страница 5: ...be connected to a natural draft chimney 5 The SS2 shall not be installed where flue gas temperatures exceed 650oF 343oC at its inlet Flue gas temperature verification A On oil fuel verify flue gas te...

Страница 6: ...OF A PREVIOUSLY USED APPLIANCE Perform prior to SS2 installation The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition...

Страница 7: ...LIANCE INTERLOCK RELAY VENTER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR 4 C GND F AUXILIARY DEVICE COMMUNICATION TERMINALS 2 mA 5VDC For Tjernlund MAC1E or MAC4E auxiliary devi...

Страница 8: ...ilure to do so may result in personal injury and or equipment damage LED 6 RED should not be on if 115 VAC supply power is removed from the control Pre purge Used for longer vent runs to get draft ful...

Страница 9: ...code for Oil burning Equipment CSA Std B139 M91 See Diagram A1 A venting system shall not terminate underneath a veranda porch or deck or above a paved sidewalk or a paved driveway that is located bet...

Страница 10: ...ng Saw SS2 VENT SYSTEM CLEARANCES FROM COMBUSTIBLES OBSTRUCTIONS With an inlet flue gas temperature of 650oF 343oC or below the SS2 has been Listed for Zero Clearance from combustibles NOTE You must a...

Страница 11: ...r easy one person installations remove 3 screws from rear and bottom of vent cabinet Slide venter assembly out of SS2 cabinet and set aside being careful not to dam age housing After SS2 cabinet is se...

Страница 12: ...apered reducers and increasers as shown below Determine vent pipe layout which will allow for the least amount of elbows to the appliance Calculate the equivalent vent pipe length from the appli ance...

Страница 13: ...e to wire the SS2 as outlined in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC p...

Страница 14: ...N 9183046 6 115 VAC LEGEND CALL JUMPER Ignitor CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Line Voltage Thermostat or Aquastat Control Low Voltage Jumper 1 Separate t...

Страница 15: ...D CALL JUMPER CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN SS2 ELECTRICAL BOX IMPORTANT Limit or Aquastat Control Low Voltage Jumper 1 Disconnect B1 from L1 of oil burner primary control burner re...

Страница 16: ...sure RED voltage jumper on UC1 is on 115V SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO AN OIL FIRED FURNACE WITH A HONEYWELL T87 OR EQUIVALENT NON POWERED THERMOSTAT XN R UNIVERSAL CONTR...

Страница 17: ...ELECTRICAL BOX CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN IMPORTANT 1 Remove the wire on MV at gas valve and connect it on 1 on UC1 terminal block 2 Connect 2 on UC1 terminal block to MV PV 3 Co...

Страница 18: ...resulting in fire carbon monoxide poisoning explosion personal injury or property damage 1 Insert a stack thermometer into the vent pipe as close as possible to the SS2 inlet NOTE plug hole when fini...

Страница 19: ...he main burner is burning properly i e no floating lifting or flash back C If the heater has a two stage or modulating gas valve verify that burner operates properly at both low and high fire If the d...

Страница 20: ...direct at 1 800 255 4208 for further assistance LED STATUS FAULT INDICATORS LED INDICATOR LIGHTS LED 1 Amber Appliance call for heat LED 2 Blue Safety circuit through P1 P2 SS2 Limit Fan Prover Indica...

Страница 21: ...J2 on UC1 circuit board if using typical wiring where supply voltage from ter minal 1 is routed to terminal 3 through call jumper then to 4 when appliance interlock relay makes With call for heat esta...

Страница 22: ...roubleshooting guide to determine defective component If unable to determine faulty component contact your Tjernlund distributor or Tjernlund Products Technical Customer Service Department at 1 800 25...

Отзывы: