12
Installation Manual – THH
Redefine your comfort zone. ™ | www.titus-hvac.com
THH HIGH PERFORMANCE HORIZONTAL
FAN COIL UNITS
Section 2 – Start-Up
Model/Size
AHRI 440
Certified
Coil
Airflow CFM
(Dry Flow)
Cooling Capacity
Water
Power Input
(Watts)
Rows
FPI
QT (BTUH)
QS (BTUH)
Flow Rate GPM
WPD ft-wg
THHC/THHP
06
*
4
10
700
17800
14000
3.7
1.6
290
THHC/THHP
06
*
4
10
900
23500
18500
4.9
1.9
410
THHC/THHP
10
*
4
10
1100
29400
22900
6.0
2.2
470
THHC/THHP
12
*
4
10
1400
43000
31800
8.7
4.2
560
THHC/THHP
14
4
10
1750
47100
36250
9.6
3.0
715
THHC/THHP
16
4
10
2000
51000
41000
10.5
2.0
830
THHC/THHP
18
4
10
2200
53000
42000
11.0
2.2
850
THHC/THHP
20
4
10
2300
56000
44000
11.4
2.5
870
AHRI STANDARD RATINGS
Notes:
1. Based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F temperature rise, high speed fan. Motor type is PSC and motor voltage is 115/1/60.
Airflow under dry coil connections. All models tested at 0.05" external static pressure.
2. Airflow rate CFM on sizes 14 through 20 exceed maximum ratings in AHRI 440 and are therefore not certified