IOM - FFDE

Redefine your comfort zone. ™ | www.titus-hvac.com

Service: Removal and Replacement of FFDER & FFDERA Filters

WARNING

DISCONNECT THE UNIT FROM THE ELECTRICAL POWER 

SOURCE BEFORE ATTEMPTING ANY SERVICE

WARNING

THE STANDARD FILTER IS PROTECTED WITH AN 

EXTENDED METAL FACE SCEEN. THIS IS NEVER TO 

BE USED TO HANDLE THE FILTER. IT IS ONLY FOR 

PROTECTION AGAINST AN ACCIDENTAL TOUCH OF THE 

FILTER. ONLY HANDLE THE FILTER BY THE FRAME

Note:

 All filters should be visually inspected for freight damage before 

installation. It is necessary to use two workers when removing the filter 
and for installation to avoid twisting or separation of the media seals. 
Handle the filter only by the frame and never place anything on the 
upstream filter side of the filter. Additionally, it is important to keep the 
filter level to prevent any shearing force on the media itself.
 

 

       

FOR FFDER & FFDERA FILTERS:

Tools Required: 

Phillips Head Driver, Battery Operated Drill, 3/16” hex 

head ball driver (2ea)

Step 1.

 With the power off, remove the diffuser screen by removing the 6 

each 10-32x1/2 screws, then carefully place in a safe location.

Step 2.

 Loosen the six 1/4x12 socket head screws far enough to rotate 

the eight filter clips 90°. The filter may be loose enough to drop during 
this operation. If not, slowly pull the filter away from the knife-edge seal, 
taking care not to touch the filter face during this operation. It is important 
to pull the filter slowly away from the seal, so that the gel remains in the 
filter gel track.

Step 3.

 Carefully clean plenum assembly knife edge surface of residual 

gel material.

Step 4.

 Inspect filter for visible damage, if damaged set aside for 

replacement or repair.

Step 5.

 Inspect the gel seal, if reinstalling the removed filter. Determine 

if the gel has lost its ability to seal (i.e. the gel should reform to cover the 
track without voids or openings), if so repair the gel material or consider 
replacement of filter.

Step 6.

 Place the filter evenly against the filter-sealing surface of the unit. 

Reposition filter clips and screws. The clips should be rotated and angled 
into place. It is recommended that four workers work on each corner of the 
filter simultaneously, holding the filter seated into the track. Hand tighten 
clips from opposite corners evenly until all clamps are tightened.

Step 7.

 Reinstall diffuser screen by hand-tightening the screws.

Step 8.

 Determine if recertification or testing of replacement is required.

Step 9. 

 Restore power to FFU and verify proper operation of FFU.

FFDR & FFDRA Filter Change

Fan Filter Unit

Filter 

2-Piece Welded
Plenum Housing

Filter Clip and
Screw (typ 6)

Diffuser Screen
Screws (typ 6)

FFDR & FFDRA Filter Replacement

Filter 

Filter Clip

Gel Track

Knife- Edge

Seal

Diffuser
Screen

10-32
PHP
Screws

¼ -20
Cap
Screw

Содержание FFDE

Страница 1: ...Redefine your comfort zone www titus hvac com INSTALLATION OPERATION MANUAL Fan Filter Unit FFDE FFDER FFDERA...

Страница 2: ...filter Cleaning foam 14 Service Removal and Replacement of FFDE Filters 15 Service Removal and Replacement of Roomside Replaceable Filters 16 Service FFDE and FFDER Motor Removal and Installation 17 S...

Страница 3: ...he information for reference WARNING TO REDUCE THE RISK OF FIRE ELECTRICAL SHOCK OR INJURY TO PERSONS OBSERVE THE FOLLOWING A Installation work and electrical wiring must be done by qualified person s...

Страница 4: ...units are completely assembled at the factory with the exception of the optional 20 eyebolts that are used when hanging the unit from an engineered design support system and installation of the HEPA...

Страница 5: ...e front of the control enclosure Counterclockwise rotation will increase the set point differential for switching clockwise rotation will reduce the set point The process to adjust this for a specific...

Страница 6: ...tional details of the controls modes are provided on page 7 FEATURES Networkable Via MODBUS RTU 0 10 VDC Analog Control Manual Control Via Onboard Potentiometer Simple Connections RJ45 For Networking...

Страница 7: ...0 VDC NETWORK control MODBUS RTU Note Network mode can be configured using either DIP switch setting shown above DIP switch pictorials are for reference and may be labeled differently by the manufactu...

Страница 8: ...he eight DIP switches of switch bank S2 A maximum of 200 ENV1028 devices is recommended per local area network LAN If an Titus ACC Control Console is the MODBUS master then addresses should be assigne...

Страница 9: ...tors Onboard Status LED The Onboard Status LED is software controlled by the unit microcontroller The Status LED is solid ON when RPM reported by the motor is greater than zero and OFF when RPM report...

Страница 10: ...ters to factory default values write 170 AA hex to Register 14 and then cycle power Note Register 24 may be read in network mode to determine the value of 0 10VDC signal that may be connected For exam...

Страница 11: ...on Note The 4 pin connector is on the 1 8 white cable from motor Low Air Velocity Step 1 Check to be sure that the manual speed potentiometer is set correctly Step 2 Check incoming power supply for pr...

Страница 12: ...x of 24 flashes two longs then 4 short A flow index of 89 flashes 8 longs then 9 short A flow index of 30 flashes 3 longs then an extra long A flow index of 04 flashes an extra long then 4 short A flo...

Страница 13: ...if applicable Step 2 Switch the ON OFF switch to the off position Step 3 Remove the 16 x23 prefilter from the snap in frame See figure below Step 4 Clean the prefilter by hand washing in water with a...

Страница 14: ...ivet Hand Tool 5 32 aluminum rivet grip range 126 187 Step 1 Remove unit from ceiling Step 2 Remove the 10 screws holding the HEPA ULPA filter to the lid assembly Step 3 Lift the lid assembly off the...

Страница 15: ...owly pull the filter away from the knife edge seal taking care not to touch the filter face during this operation It is important to pull the filter slowly away from the seal so that the gel remains i...

Страница 16: ...t to a low torque setting to avoid stripping the sheet metal screws Carefully remove housing assembly paying attention to wire routing Step 7 Using an adjustable wrench loosen the two set screws that...

Страница 17: ...an adjustable wrench loosen the two set screws that attach the blower wheel to the motor shaft Disconnect the two brown wires from the capacitor using a pair of pliers Disconnect 5 pin and 16 pin wir...

Страница 18: ...the cable that connects to the control board and the motor The new Nidec motor will require you to replace the cable The old cable was a sixteen pin connector while the new motor cable will have a fo...

Страница 19: ...19 IOM FFDE Redefine your comfort zone www titus hvac com Motor Cable Configurations...

Страница 20: ...ith air causing the motor to stall which can damage the fan motor This also can be minimized by notifying Titus beforehand for assistance The ECM motors used in the FFDE FFDER and FFDERA designs are a...

Страница 21: ...21 IOM FFDE Redefine your comfort zone www titus hvac com Wiring Diagrams Universal Card Wiring Diagram 4 pin Control Cable 5 pin Power Cable 4 Pin MTA Motor Connector Remote Run Indicator LED...

Страница 22: ...iring Diagram w Continous Filter Monitoring 4 pin Control Cable 5 pin Power Cable 4 Pin MTA Motor Connector Remote Run Indicator LED Note Register 24 may be read in network mode to determine the value...

Страница 23: ...23 IOM FFDE Redefine your comfort zone www titus hvac com Wiring Diagrams continued Infrared Speed Control Remote Mounted Visual Control Unit...

Страница 24: ...A Universal Control Card FFDE FFDER FFDERA 265888 N A Visual Speed Control Card FFDE FFDER FFDERA 63951 002 N A IR Sensor Harness 63759 001 N A IR Sensor without Harness 63758 2x2 120V S266587 005 2x...

Страница 25: ...25 IOM FFDE Redefine your comfort zone www titus hvac com FFDE Filter Drawing...

Страница 26: ...26 IOM FFDE Redefine your comfort zone www titus hvac com IOM FFDE FFDER FFDERA FFDER and FFDERA Filter Drawing...

Страница 27: ...sted using a Shortridge Airdata Multimeter 870 with a Velgrid head The recommended method of reading is to place one corner of the Velgrid head 1 1 4 from the corner of the filter face and then take f...

Страница 28: ...605 Shiloh Rd Plano TX 75074 ofc 972 212 4800 fax 972 212 4884 Redefine your comfort zone www titus hvac com...