9
IOM - FFDE
Redefine your comfort zone. ™ | www.titus-hvac.com
Electrical Specifications
Control and Interface Signals:
1. External Speed 0-10V Input
• Input impedance 20k Ohms.
• MIN ON-to-OFF threshold: 190mV*
• MAX OFF-to-ON threshold: 240mV*
• ON (~215mV) to 9.89V linearly scales 1 to 99% speed.
• 9.89V or more deadbands to 100% speed.
Test
Probe
JacksPoints:
The test probe jacks may be used to measure the motor rpm or the PWM
signal that is being output to the motor.
• In Manual or Analog Control Mode with an Address setting of 1 or
greater, the test probe jacks output 0-2000 mVDC representing motor
RPM. By changing the address DIP switches to 0, the test probe jacks
will output 0-1000 mVDC representing 0-100% demand signal to the
motor. The address may be changed without interrupting power to
the control card.
• In Network Control Mode, 0-2000 mVDC always represents RPM.
2. External LED Output
• 10mA regulated
• LED forward voltages up to 5V
3. RPM Signal
• Signal Value: mVDC = RPM
• Ex: 900mV = 900RPM
• RPM Output Range: ~ 0, 5 to 2000 RPM (0, 5mV to 2000 mV DC)
• RPM Output Resolution: 5RPM (Zero, 400 steps from 5 to 2000
RPM
inclusive)
LED Indicators:
• Onboard Status LED:
The Onboard Status LED is software controlled by the unit
microcontroller. The Status LED is solid ON when RPM reported by
the motor is greater than zero and OFF when RPM reported by the
motor is zero.
• External Status LED:
Support for an external Status LED (10mA current-controlled driver),
via a 2-pin MTA connector, for remote system status notification. The
external Status LED operates in the same manner as the Onboard
Status
LED.
• Onboard Net LED:
The Onboard Net LED is driven directly by the receive data signal.
The NET LED shows all network traffic on a 2-wire network. The NET
LED is intended to confirm low-level network connectivity,
independent of microcontroller or firmware functionality. If A/B
network wires are swapped, the NET LED will be normally on,
providing quick diagnostics of this common condition.
RJ45 Network Cable Connections:
Bus Power
Pass Through
0V (GND)
RS-485
0V (GND)
Bus Power
Pass Through
Power Lost or No Communications
Network Data Traffic In Progress
A/B network wires are swapped
Net LED Status Definition
LED OFF
LED ON
LED Flickering
Specification
Min
Max
Units
Typical
22
50
na
0
24
na
25
50/60
60
50
42
0.5
C
VA
Hz
VAC
Input Voltage
Supply Frequency
Input Power Consumption
Ambient Operating Temperature
Electrical and Environmental Specifications
Содержание FFDE
Страница 19: ...19 IOM FFDE Redefine your comfort zone www titus hvac com Motor Cable Configurations...
Страница 25: ...25 IOM FFDE Redefine your comfort zone www titus hvac com FFDE Filter Drawing...
Страница 26: ...26 IOM FFDE Redefine your comfort zone www titus hvac com IOM FFDE FFDER FFDERA FFDER and FFDERA Filter Drawing...
Страница 28: ...605 Shiloh Rd Plano TX 75074 ofc 972 212 4800 fax 972 212 4884 Redefine your comfort zone www titus hvac com...