4.3.3.3 Alarm Logic Table
Flow Alarm
Invert
Alarm Action
Below Threshold
Above Threshold
Single
Unticked
OFF
ON
Single
Ticked
ON
OFF
In Range
Outside Range
Dual
Unticked
ON
OFF
Dual
Ticked
OFF
ON
NOTE:
The NPN and PNP have different outputs when used due to their wiring.
•
Using the NPN: OFF =PVDC and ON = Unpowered 0VDC
•
Using the PNP: OFF=Unpowered 0VDC and ON = PVDC
4.3.3.4 Analog Outputs
NOTE:
FOR FULL ANALOG OUTPUT FUNCTION EXTERNAL POWER OF >15VDC IS
REQUIRED
Analog Output: there are four options on the
drop-down menu:
•
Not Used
•
4-20mA (active)
•
0-5 Volt
•
0-10 Volt.
NOTE:
The 4-20mA is ACTIVE (
Not
loop powered).
Incorrect wiring may damage this device
Once the Analog Mode selection has been
made you can enter the low and high flows
for the analog outputs as required. These are
numeric entries in the units and time base
selected in calibration settings.