background image

 

User Manual-MA2T 

 

 

 

Version A August 2021 

9  of  25 

 

 

Outer tube reed sensor adjustment 

 

The external limit switches are mounted in the two slots at the side of the cover tube. 

 

Use the 2.5mm Allen key inner hexagon to position and lock the reed sensor.   

 

Ensure the reed sensor doesn’t meet other magnetic parts, as this may cause incorrect measurements. 

 

The torque required to secure the screw to fix the reed sensor is within 1.5 Nm 

 

The signal is potential free and independent from the motor power circuit. 

 

Connect the reed sensor with max 32V, <1A. 

 

The reed sensors are N.C.. 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

2.5mm 

 

Содержание MA2T

Страница 1: ...User Manual MA2T Version A August 2021 1 of 25 A User Manual MA2T...

Страница 2: ...pment power off 6 Duty cycle 6 Temperature 6 2 Installation 7 Mechanical installation 7 Mounting notice 7 Manual drive operation 8 Outer tube reed sensor adjustment 9 Electrical installation 10 Import...

Страница 3: ...g terms and acronyms are being used in this manual VDC The positive pole of power input VDC The negative pole of power input RPM Number of turns per minute AWG American wiring gauge Hall POT Hall Effe...

Страница 4: ...on Target Personnel Please allow qualified mechanical and electrical professionals to perform all installation maintenance and replacement of the TiMOTION products Please keep the products away from p...

Страница 5: ...rmation contained in this user manual and on the product label Never exceed the performance limits stated herein Be sure the actuator is not in operation Ensure the actuator is free from loads that co...

Страница 6: ...e actuator within the specified working limits Refrain from having any contact with the actuator Equipment power off Switch off the main supply to prevent any unintentional operation Regularly check f...

Страница 7: ...d at both ends of the attachments Do not mount the actuator with the pins in different rotated angles this could cause stress on the nut during operation The load should act along the stroke axis of t...

Страница 8: ...g the actuator ensure there is enough space between the rear adapter and any objects This will allow the user override to be operated Use the 5mm Allen key for both the IP protection screw and the man...

Страница 9: ...llen key inner hexagon to position and lock the reed sensor Ensure the reed sensor doesn t meet other magnetic parts as this may cause incorrect measurements The torque required to secure the screw to...

Страница 10: ...e ensure it is able to withstand the peak of high voltage To reduce the chance of interference refrain from placing signal cables along power cables Use a two wire system to prevent ground loop Please...

Страница 11: ...source with the proper size is important to avoid a significant voltage drop The further away the DC source is the larger the extension cable may need to be Please refer to the following table for th...

Страница 12: ...ring the inrush current Please be sure all contacts switches and relays are sized appropriately to handle the inrush current It is not recommended to configure the hard start setting to the soft start...

Страница 13: ...or is ordered with customized wiring please contact TiMOTION s sales representatives for more detailed information In general the MA2T T Smart version cable exit can have a maximum of 3 sets with 8 pi...

Страница 14: ...S feedback to PLC Reed switch signal output to PLC or up to 8 actuators having synchronized function when actuators extended or retracted Port No Wire AWG Description Spec P1 Red 14 Connect Red to Vm...

Страница 15: ...uits when the actuator is in the middle of the stroke The signal circuit is connected to the motor power circuit and the value Vm depends on actuator voltage Connect the limit switch signal wire to th...

Страница 16: ...representative to determine the compatibility of T Smart capable products with your desired communication protocol e g CAN BUS or J1939 2 Wire definition of two actuators in synchronized mode Output...

Страница 17: ...to ship separately all cables will be fixed onto the actuator under the default installation procedure For PGMA settings it is required to change the short circuit plug or the Reed sensor cable on P2...

Страница 18: ...tested according to TiMOTION s factory assembly standard procedure before shipping Ensure to protect the plugs and pins during the process Ensure the plug is in the right location and fully pressed in...

Страница 19: ...eplace the default installed P2 short circuit plug with the extension cables for the PGMA setting Step 1 Unscrew the cover Step 2 Remove the cover Step 3 Unplug the short circuit plug Step 4 Replaced...

Страница 20: ...nd close the program after completing installation 2 Once the TAD1 extension cable is replaced connect the TAD1 to the computer the LED on the TAD1 will constantly shine indicating a successful connec...

Страница 21: ...User Manual MA2T Version A August 2021 21 of 25 4 Product specifications 2D drawings...

Страница 22: ...User Manual MA2T Version A August 2021 22 of 25 Ordering key Please contact your TiMOTION sales engineer for the latest revision ordering key...

Страница 23: ...he application Align or reduce the load Try running the actuator without load The actuator cannot lift the full load or the motor runs too slowly Insufficient power supply Verify the power supply is p...

Страница 24: ...ystem matches the sync setting in PGMA Communication wires are not properly connected Check the parallel communication wires for all actuators Control signals extend retract are not correctly connecte...

Страница 25: ...is connected supply power to all actuators at the same time Then wait 10 seconds before the Run In Run Out signals are activated Signal cable damaged or removed under operation Under parallel configu...