IM2020 

23 

 

2. The most effective use of the curtain is when it is installed above doorways up to 2.2 m high 
and when it is installed to protect open window openings up to 1.5 m high. 
3. Air curtains can be installed both horizontally with the air outlet grille looking down, and in a 
vertical  position  (except  for  the  WT1  3M  model),  where  the  control  panel  of  the  device  or  the 
control cable must be in the upper part. 
 

NOTE: 

When operating the air curtain in vertical position, its life time can be reduced. 
 
4.  The  curtain  must  be  installed  as  close  to  the  upper  side  of  the  opening  as  possible, 
maintaining  a  distance  of  at  least  50  mm  between  the  upper  side  of  the  device  body  and  the 
ceiling. 
5. To obtain maximum efficiency, the opening width should be  less than or equal to the width of 
the air outflow of the device. 
6. In wide openings, the curtains must be installed one after other so that the entire width of the 
opening overlaps. 
7. There are special mounting holes for mounting the air curtain on the back side of its body. The 
curtain is hung on pre-mounted fasteners in the wall with these openings. 
Screws or bolts with hat diameter of 9-12 mm are recommended as fasteners (not supplied). The 
installation dimensions of the curtain are shown in table 2. 
 

Electrical connection 

1.  Before  connecting  the  curtain  to  the  mains,  make  sure  that  the  parameters  of  the  power 
supply  at  the  connection  point correspond to the  parameters  indicated  on the  rating label  with 
the technical data of the device. 
2.  Connection  the  curtain  to  the  electrical  network  should  be  carried  out  only  by  qualified 
specialists in accordance with "Rules for the installation of electrical devices" and  "Safety Rules 
for the operation of electrical devices operating at voltages up to 1000V ~." 
3.  Before  connecting  the  curtain,  make  sure  that  the  curtain  is  properly  grounded.  Proper 
grounding is important to minimize electric shock and fire danger. 
 

ATTENTION! 

All work on connecting the air curtain should be done only with a complete removal of the supply 
voltage. 
 

THC WT1 3M, THC WT1 5M models 

1. The  air  curtain  is designed to be  connected to  an  alternating current  electric  network  with  a 
single-phase  voltage  of  220V  ~  (allowable  voltage  fluctuations  from  198V~  to  242V~)  and  an 
earth loop. 
2. To connect to the electric network, the air curtain is equipped with a power cord with a plug. 
3.  To connect the  air  curtain  to  the  electrical  network, insert  the  plug  of the  power  cord  into a 
socket with a grounding wire. 
 

ATTENTION! 

1. The electrical outlet must be enough for rated current of at least 16A, and the electrical wire 
supplied  to  the  outlet  from  the  power  board  must  have  a  core  section  of  at  least  1.5  mm

2

  for 

copper wire and at least 2.5 mm

2

 for aluminum wires. 

2.  A  circuit  breaker  designed  for  rated  current  of  16A  must  be  installed  in  the  power  panel  to 
protect the wiring from overloads. 
 

THC WT1 6M, THC WT1 9M models 

1. The curtain is designed to be permanently connected to an alternating current electric network 
with a three-phase voltage of 380V ~ (allowable voltage fluctuations from 342V~ to 418V~) and 
an earth loop. 
2.  Before  connecting  the  curtain  to  the  electrical  network,  it  is  necessary  to  install  an  external 
control panel connected at the factory. To do this, it is necessary to: 
- unscrew the screw on the control panel; 
- remove the top cover and remote control panel; 
- mount the remote control on the wall; 

Содержание Power Door Series

Страница 1: ...INSTRUCTION MANUAL RU 2 ENG AIR CURTAIN 18 Models THC WT1 3M THC WT1 5M THC WT1 6M THC WT1 9M THC WT1 12M THC WT1 18M THC WT1 24M...

Страница 2: ...IM2020 2 1 2 1 2 3 4 5 6...

Страница 3: ...IM2020 3 7 8 9 10 11 12 13 0 C 2 14 15 16 17 18 19 20 21 22 23 24 25 26 3 27 28 29 30 31 32 93...

Страница 4: ...WT1 12M THC WT1 18M THC WT1 24M 220 50 220 50 380 50 380 50 380 50 380 50 380 50 13 7 20 5 9 1 13 7 18 5 27 5 36 4 3000 4500 6000 9000 12000 18000 24000 0 1500 3000 0 2250 4500 0 3000 6000 0 4500 9000...

Страница 5: ...910 1610 1910 6 5 10 16 21 32 32 32 145 180 820 215 230 800 215 230 1060 215 230 1420 215 230 1910 215 230 1910 215 230 1910 1 2 1 2 A B C D H G L THC WT1 3M 35 760 20 150 215 840 THC WT1 5M 52 680 46...

Страница 6: ...IM2020 6 5 2 1 2 3 4 THC WT1 3M THC WT1 5M 5 THC WT1 6M THC WT1 9M THC WT1 12M THC WT1 18M THC WT1 24M 1 O 2 3 6 1 1 2 1 3 1 4 1...

Страница 7: ...IM2020 7 7 1 2 2 2 1 5 3 WT1 3M 4 50 5 6 7 9 12 2 1 2 1000 3 THC WT1 3M THC WT1 5M 1 220 198 242 2 3 1 16 1 5 2 2 5 2...

Страница 8: ...THC WT1 6M THC WT1 9M 1 380 342 418 2 3 1 1 5 2 2 16 THC WT1 12M THC WT1 18M THC WT1 24M 1 380 342 418 2 3 40 4 THC WT1 12M 2 5 2 THC WT1 18M 4 0 2 THC WT1 24M 6 0 2 5 25 THC WT1 12M 32 THC WT1 18M 40...

Страница 9: ...IM2020 9 8 THC W 1 3M THC WT1 5M 3 1 2 THC WT1 3M THC WT1 5M 1 1 1 0 1 2 1 3 2 2 2 2 1...

Страница 10: ...IM2020 10 2 2 10 20 3 4 3...

Страница 11: ...IM2020 11 THC WT1 6M THC WT1 9M THC WT1 12M THC WT1 18M THC WT1 24M 4 1 2 I II 3 THC WT1 6M THC WT1 9M THC WT1 12M THC WT1 18M THC WT1 24M 1 1 1 OFF 1 2 1 3 ON 2 II...

Страница 12: ...IM2020 12 2 2 1 I 2 2 II 10 20 3 3 1 5 30 3 2 3 3 4 5 3 OFF 9...

Страница 13: ...IM2020 13 10 3 3...

Страница 14: ...IM2020 14...

Страница 15: ...IM2020 15 11 THC W 1 3M 5 1 EK2 1 M2 SA1 SA2 SK1 SK2 1 XT1 THC W 1 5M 6...

Страница 16: ...IM2020 16 1 2 1 1 SA1 SA2 SK1 SK2 THC W 1 6M THC W 1 9 7 A1 C1 EK1 EK6 KM1 KM2 1 SK1 SK2 SK3 XT1 XT2...

Страница 17: ...IM2020 17 THC WT1 12M THC WT1 18M THC WT1 24M 8 A1 C1 EK1 EK6 KM1 KM2 1 SK1 SK2 SK3 XT1 XT2 12...

Страница 18: ...some misprints in text and digital notations in the present manual IMPORTANT Important safeguards and descriptions contained in this manual do not include all possible situations that you may experien...

Страница 19: ...not pull on the power cord grasp the plug Do not twist and do not wind it on anything 17 The curtain should always be monitored its long term operation without qualified personnel is prohibited 18 Nev...

Страница 20: ...room to maintain a comfortable temperature in installation zone of the curtain Also with the heating elements turned off it can be used in summer to protect the air conditioned room from penetrating...

Страница 21: ...10 Net weight kg 6 5 10 16 21 32 32 32 Device dimensions mm 145 180 820 215 230 800 215 230 1060 215 230 1420 215 230 1910 215 230 1910 215 230 1910 Dimensional characteristics Dimensional characteris...

Страница 22: ...of sheet steel coated with a high quality polymer coating finned tubular heating element and fan unit Fans take air through the perforated grille 2 after which the air flow passing through the heating...

Страница 23: ...cialists in accordance with Rules for the installation of electrical devices and Safety Rules for the operation of electrical devices operating at voltages up to 1000V 3 Before connecting the curtain...

Страница 24: ...ctory To do this it is necessary to unscrew the screw on the control panel remove the top cover and remote control panel mount the remote control on the wall Install the panel and the top cover instru...

Страница 25: ...on and the indicator of the second button will light up ATTENTION The first time the curtain is turned on a specific odor and smoke may appear oil is burned from the surface of the heating elements It...

Страница 26: ...t the heating power mode switch to II ATTENTION The first time the curtain is turned on a specific odor and smoke may appear oil is burned from the surface of the heating elements It is recommended to...

Страница 27: ...r Malfunction Possible cause Solution The device is connected to the network but doesn t work No power Check whether the power supply is disconnected from the device and if necessary connect device to...

Страница 28: ...ontact an authorized service center The air flow speed has decreased the outside air easily gets into the room Malfunction in circuit breaker Change the circuit breaker Perforated air intake grille is...

Страница 29: ...IM2020 29 THC W 1 5M Fig 6 1 2 heating elements 1 magnetic switch 1 fan motor SA1 network switch SA2 heating power mode switch SK1 SK2 thermal limiters THC W 1 6M THC W 1 9 Fig 7...

Страница 30: ...ulfillment by the Buyer of the requirements of legislation on utilization and methods of utilization of the device selected by the Buyer The lifetime of the device is indicated in the warranty card Wa...

Страница 31: ...marks Temperature Requirements Transportation and storage From 30 C up to 50 C Humidity Requirements From 15 up to 85 without condensate We are exploring new technologies and we constantly improving...

Страница 32: ...www timberk ru...

Отзывы: