35
Electric Control Installation
Wiring cautions
Cautions for power wiring
●
Use copper wire as power wire and do not make it too tight.
●
The IDU and ODU use different circuits: the ODU uses a three-phase power supply,
while the IDU uses a single-phase power supply
●
All the IDUs and ODUs of the same system must be supplied with power
simultaneously.
●
The distribution box shall be provided with a set of electric leakage protection device
and air switch for each module.
●
Make sure all the earth lines of the unit are connected to ground securely. Do not
connect earth lines to lightning devices, telephone line, gas pipe or tap water pipe.
Improper grounding may cause electrical shock or fire.
Cautions communication line wiring
●
TIMS independent/strong heat independent inverter VRF air conditioning unit has
both high voltage (power) line and control (communications) line. Do not connect
power line to the connecting terminal of communication cables!
●
The total length of communication line is less than 1000 m.
The shielding layer of communication line must be connected to earth lines of each
module and IDUs securely.
Sleeve
Shielding layer
Insulator
Conductor
Legends of shielded
twisted pair
●
Communication cable is well connected before being powered on. Do not remove the
power plug with power on, lest the communication chips would be damaged.
●
To prevent high voltage signal from disturbing control signal, shielded twisted pair
must be used.
Try to select shielded twisted pair with dense shielding layers and smaller lay.
●
Control signal has two polarities A and B, and different polarities cannot be
connected, otherwise communication failures may be caused;
As shown in the following figure:
Control main
board
Control main
board
Communication
interface
Communication
interface
● When power line is parallel with communication line, they shall be covered by respective
conduits and kept at some distance away.
Содержание TIMS-X Series
Страница 1: ...INVERTER MULTI SYSTEM UNIT Applicable to TIMS X XA XT C series https tica pro...
Страница 27: ...27 Installation of Refrigerant Piping TBP4033TA TBP4072TA...
Страница 28: ...28 Installation of Refrigerant piping TBP4073TA Qty 2 Qty 2...
Страница 29: ...29 TBP4090TA...
Страница 30: ...30 TBP4135TA Qty 2 Qty 2...
Страница 57: ...141014 12 805 7 495 127 79 00 7 969 190 85 85 Email info tica pro...