![Thytronic Pro-N NVA100X-D Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/thytronic/pro-n-nva100x-d/pro-n-nva100x-d_manual_1113999038.webp)
38
NVA100X-D - Manual - 02 - 2016
TECHNICAL DATA
3.8
CONTROL AND MONITORING
Second harmonic restraint - 2ndh-REST
Second harmonic restraint threshold (
I
2ndh
>)
10...50 % (step 1 %)
I
2ndh
> reset time delay (
t
2 ndh> R E S)
0...100.0
s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot
time
0.04
s
Pickup accuracy
I
2ndh
> ±
1% with 0.1
I
n
, ±
0.5% with 1
I
n
Operate time accuracy
5% ±
10 ms
Trip Circuit Supervision - 74TCS
Operate time:
One binary input supervision
40 s
Two binary inputs supervision
2 s
Reset time delay:
One binary input supervision
6 s
Two binary inputs supervision
0.6 s
Selective block - BLOCK2
Selective block IN
BLIN1 Selective block operating mode (
ModeBLIN1
)
OFF-ON IPh/IE-ON IPh-ON IE
BLIN maximum activation time for phase protections (
t
B-IPh)
0.10...10.00 s (step 0.01 s)
BLIN maximum activation time for ground protections (
t
B-IE )
0.10...10.00 s (step 0.01 s)
Selective block OUT
BLOUT1 Selective block operating mode (
ModeBLOUT1
)
OFF-ON IPh/IE-ON IPh-ON IE
BLOUT Dropout time for phase protections (
t
F -IPh
)
0.00...1.00 s (step 0.01 s)
BLOUT Dropout time for ground protections (
t
F -IE
)
0.00...1.00 s (step 0.01 s)
BLOUT Dropout time for ground and phase protections (
t
F-IPh/IE
) 0.00...1.00 s (step 0.01 s)
Internal selective block - BLOCK4
Output internal selective block dropout time for phase protections (
t
F I-IPh
)
0.00...10.00 s (step 0.01 s)
Output internal selective block dropout time for ground protections (
t
F I-IE
)
0.00...10.00 s (step 0.01 s)
Circuit Breaker supervision
Circuit breaker diagnostic
Number of CB trips threshold (
N.Open
)
0...10000
(step 1)
Cumulative CB tripping currents threshold (
SumI
) 0....5000
I
n
(step 1
I
n
)
Cumulative CB tripping I
2
t threshold (
SumI^2t
)
0....5000
(
I
n
)
2
∙s
(step 1
I
n
2
∙s)
Circuit Breaker opening time for I^2t calculation (
t
break
)
0.05...1.00 s (step 0.01 s)
Circuit Breaker maximum allowed opening time (
t
break
>)
0.05...1.00 s (step 0.01 s)
VT supervision - 74VT
74VT Negative sequence overvoltage threshold (
U
2 V T>
) 0.05...0.50
E
n
(step 0.01
E
n
)
74VT Negative sequence overcurrent threshold (
I
2 V T>
)
0.05...0.50
I
n
(step 0.01
I
n
)
74VT Phase undervoltage threshold (
U
V T<
)
0.05...0.50
E
n
(step 0.01
E
n
)
74VT Minimum change of current threshold (
D
I V T<
)
0.05...0.50
I
n
(step 0.01
I
n
)
74VT Alarm time delay (
t
V T-A L
)
0.0...10.0 s (step 0.1 s)
Undercurrent inhibition threshold (I
V T<
) 0.100...40.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...40.0
I
n
(step 0.1
I
n
)
Pickup accuracy for negative sequence voltage thresholds
±
5% con 0.01
U
n
±
0.5% with 0.15
U
n
Pickup accuracy for negative sequence current thresholds
±
1% with
I
2
= 0.5
I
n
±
1% with
I
2
= 1
I
n
Operate time accuracy
5% or ±
10 ms
CT supervision - 74CT side H
74CT Threshold (
S
(H)
<)
0.10...0.95
(step 0.01)
74CT(H) Overcurrent threshold (
I
(H) *
)
0.10...1.00
I
nH
(step 0.01
I
nH
)
Operating time delay (
t
S(H)
<)
0.03...200
s
0.03...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
Dropout ratio for the
I
(H) *
pickup 0.95...0.98
Dropout time
≤
0.05 s
Pickup accuracy
I
(H) *
±
0.5% with 0.1
I
nH
, ±
0.2% with 1
I
nH
Pickup accuracy
I
*
± 0.5% with 0.1
I
nH
, ± 0.2% with 1
I
nH
Operate time accuracy
5% ±
10 ms
—
—
•
•
•
•
—
—
—
—
—