![Thytronic Pro-N NVA100X-D Скачать руководство пользователя страница 314](http://html1.mh-extra.com/html/thytronic/pro-n-nva100x-d/pro-n-nva100x-d_manual_1113999314.webp)
314
NVA100X-D - Manual - 02 - 2016
SETTING AND COMMISSIONING
NVA100X-D_menuset3.ai
PREVIOUS SET MENU’
PREVIOUS PROFILE A MENU’
PROCEED SET MENU’
SET
PROFILE A
PROCEED PROFILE A MENU’
49MG
>>
Common
>>
DthIN 0.0 DThetaB
KST 2.0
K2
0
T+
10 min
T-
1.0 T+
DthCLP Mode
OFF
tDthCLP 0.10 s
DthAL1 Element
>>
DthAL1 Enable OFF
DthAL1 0.5 DThetaB
DthAL1BLK1 OFF
DthAL1BLK2IN OFF
DthAL1BLK2OUT OFF
DthAL1BLK4 OFF
Relays DthAL1
DthAL1-K
-
LEDs DthAL1
DthAL1-L
-
DthAL2 Enable OFF
DthAL2 1.0 DThetaB
DthAL2BLK1 OFF
DthAL2BLK2IN OFF
DthAL2BLK2OUT OFF
DthAL2BLK4 OFF
Relays DthAL2
DthAL2-K
-
LEDs DthAL2
DthAL2-L
-
DthAL2 Element
>>
Dth> Enable
OFF
Dth> 1.200 DThetaB
Dth>BLK1 OFF
Dth>BLK2IN OFF
Dth>BLK2OUT OFF
Dth>BLK4 OFF
Dth>BF OFF
Dth>disby50-51 OFF
Relays Dth>
Dth>-K
-
LEDs Dth>
Dth>-L
-
Dth> Element
>>
50/51
>>
I> Element
>>
I>> Enable
OFF
Type
Characteristic:
I>>Curve DEFINITE
ICLP>> Mode
OFF
tCLP>> 0.10
s
t>>RES 0.00
s
I>>def OFF
1.00 In
ICLP>>def 2.00
In
t>>def 1.00
s
I>>inv OFF
1.00 In
ICLP>inv 2.00
In
t>>inv 5
s
I>>BLK1 OFF
I>>BLK2IN OFF
I>>BLK2OUT OFF
I>>BLK4 OFF
I>>2ndh-REST OFF
I>>BF
OFF
I>disbyI>> OFF
Relays I>>
I>>ST-K
-
I>>TR-K
-
LEDs I>>
I>>ST-L
-
I>>TR-L
-
I> Enable
OFF
Type
Characteristic:
I>Curve DEFINITE
ICLP> Mode
OFF
tCLP> 0.10
s
t>RES 0.00
s
I>def
OFF
1.00 In
ICLP>def 2.00
In
t>def 1.00
s
I>inv
OFF
1.00 In
ICLP>inv 2.00
In
t>inv 10.0
s
I>BLK1 OFF
I>BLK2IN OFF
I>BLK2OUT OFF
I>BLK4 OFF
I>2ndh-REST OFF
I>BF
OFF
Relays I>
I>ST-K
-
I>TR-K
-
LEDs I>
I>ST-L
-
I>TR-L
-
I>>> Enable
OFF
ST-I>>>&ST-U<< OFF
ICLP>>> Mode
OFF
tCLP>>> 0.10
s
t>>>RES 0.00
s
I>>>def OFF
1.00 In
ICLP>>>def 2.00 In
t>>>def 1.00
s
I>>>BLK1 OFF
I>>>BLK2IN OFF
I>>>BLK2OUT OFF
I>>>BLK4 OFF
I>>>2ndh-REST OFF
I>>>BF OFF
I>disbyI>>> OFF
I>>disbyI>>> OFF
Relays I>>>
I>>>ST-K -
I>>>TR-K -
LEDs I>>>
I>>>ST-L -
I>>>TR-L -
I>> Element
>>
I>>> Element
>>
ILR> Enable
OFF
Mode51LR>
No speed crt1
ILR>inv 0.80
IB
I-MOT-ST 1.00
IB
tLR>inv 10.0
s
ILR>BLK1 OFF
ILR>BLK2IN OFF
ILR>BLK2OUT OFF
ILR>BF OFF
Relays ILR>
ILR>ST-K -
ILR>TR-K -
LEDs ILR>
ILR>ST-L -
ILR>TR-L -
ILR>> Enable
OFF
Mode51LR>>
No
speed
crt1
tLRCLP>> 0.10
s
ILR>>def 1.00
IB
tLR>>def 1.00
s
ILR>BLK1 OFF
ILR>>BLK2IN OFF
ILR>>BLK2OUT OFF
ILR>>BF OFF
Relays ILR>>
ILR>>ST-K -
ILR>>TR-K -
LEDs ILR>>
ILR>>ST-L -
ILR>>TR-L -
51LR(48)/14 >>
ILR> Element
>>
ILR>> Element
>>
t-I/U>RES 0
s
I-I/U>def enable
OFF
I-I/U>def 1.00
In
t-I/U>def 1.00
s
I-I/U>BLK1 OFF
I-I/U>BLK2IN OFF
I-I/U>BLK2OUT OFF
I-I/U>BF OFF
Relays I-I/U>
I-I/U>ST-K -
I-I/U>TR-K -
LEDs I-I/U>
I-I/U>ST-L -
I-I/U>TR-L -
t-I/U>>RES 0.00
s
I-I/U>>def enable
OFF
I-I/U>>def 1.00 In
t-I/U>>def 1.00
s
I-I/U>>BLK1 OFF
I-I/U>>BLK2IN OFF
I-I/U>>BLK2OUT OFF
I-I/U>BF OFF
I-I/U>disbyI-I/U>>
OFF
Relays I-I/U>>
I-I/U>>ST-K -
I-I/U>>TR-K -
LEDs I-I/U>>
I-I/U>>ST-L -
I-I/U>>TR-L -
Mode51V
Voltage controlled
U-I/U< 0.50
Un
U-I/U-1< 0.80
Un
U-I/U-2< 0.50
Un
K
1.00
51V
>>
Common
>>
I-I/U> Element
>>
I-I/U>> Element >>