MEC 20 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM047 Rev 13 05/03/30
85
Thomson Technology
11.4. DIGITAL FAULT PROGRAMMING MENU
TYPICAL PROGRAM FACTORY DEFAULT SETTINGS
DIGITAL FAULT PROGRAMMING MENU
FAULT
NAME
INPUT #
ACTION
S=SHUTDOWN
A=ALARM
ALARM
LATCH
Y=YES
N=NO
POLARITY
O=OPEN
C=CLOSE
BYPASS ON
START
Y=YES
N=NO
TRANSIENT
DELAY
(SEC)
LOW OIL
PRESSURE
1 S __ O Y 0.5
HIGH ENG
TEMP
2 S __ O Y 1.0
BATT CHGR
INPUT FAIL
3 A Y C N
30.0
LOW FUEL
LEVEL
4 A N C N 0.1
“blank”
5 A N C N 0.0
“blank”
6 A N C N 0.0
“blank”
7 A N C N 0.0
“blank”
8 A N C N 0.0
“blank”
9 A N C N 0.0
“blank”
10 A N C N 0.0
REMOTE
EMERG
STOP
11 S N C N 0.1
IDLE
12 A N C N 0.1