MEC 20 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM047 Rev 13 05/03/30
80
Thomson Technology
11. PROGRAMMING
SHEETS
11.1. SUMMARY CONFIGURATION DATA SHEET
MEC 20
MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
SUMMARY CONFIGURATION DATA SHEET
WORK ORDER #:
REV:
REV DATE:
INITIATED
BY:
CUSTOMER:
DEFAULT
PROGRAM:
DATE:
PROJECT
NAME: TPS
VER:
NOTES:
ENGINE/GEN SYSTEM INPUTS
SYSTEM AC VOLTS:
PHASES:
FREQUENCY:
DC VOLTAGE:
DIGITAL DISPLAY FEATURES
AC VOLTAGE
AC CURRENT
BATTERY VOLTAGE
ENGINE TEMPERATURE
KVA
TACHOMETER
OIL PRESSURE
FREQUENCY
HOURMETER
DIGITAL FAULT CIRCUITS (15)
ANALOG FAULT CIRCUITS
FAULT NAME
INPUT NAME
FAULT NAME
INPUT NAME
Overcrank Shutdown
Internal
Overspeed Shutdown
Mag-Pickup
Switch Not in Auto Alarm
Internal
Loss of Speed Sig. Shtdn
Mag-Pickup
Emergency Stop
Internal/ext
Undervoltage Shutdown
AC Voltage
Low Oil Press Shtdn (Std Default) or
Custom ________________________
Ext Dig Input #1
Overvoltage Shutdown
AC Voltage
High Eng Temp Shtdn (Std Default) or
Custom ________________________
Ext Dig Input #2
Under Frequency Alarm
AC Freq
Low Coolant Lvl Shtdn(CSA Std Default) or
Bat Chgr AC Fail (NFPA Std Default) or
Custom ________________________
Ext Dig Input #3
Over Frequency Alarm
AC Freq
Low Fuel Level Alarm (Std Default) or
Custom ________________________
Ext Dig Input #4
Overcurrent Alarm
AC Current
Ext Dig Input #5
Weak Battery Alarm
DC Volts
Ext Dig Input #6
Low Battery Voltage Alarm
DC Volts
Ext Dig Input #7
High Battery Voltage Alarm
DC Volts
Ext Dig Input #8
Low Engine Temp. Alarm
Temp. Sender
Ext Dig Input #9
High Engine Temp #1 Alm
Temp. Sender
Ext Dig Inpt #10
High Engine Temp #2 Shdn
Temp. Sender
Remote Emerg Stop (Std Default) or
Custom _______________________
Ext Dig Inpt #11
Low Oil Pressure #1 Alarm
Press. Sender
Idle Control or
Custom _______________________
Ext Dig Inpt #12
Low Oil Pressure #2 Shutdown
Press. Sender
STANDARD OUTPUT CONTACTS
OUTPUT NAME
OUTPUT TYPE
Run (Fuel)
Form A
Crank
Form
A
Common Fail
Form C
PROGRAMMABLE CONTACTS
OUTPUT NAME
OUTPUT TYPE
ATS Test (Std Default) or Custom _____________________________________
Programmable #1 – Form C
Common Alarm (Std Default) or Custom _________________________________
Programmable #2 – Form C
Common Shutdown (Std Default) or Custom _____________________________
Programmable #3 – Form C
Engine Running (Std Default) or Custom ________________________________
Programmable #4 – Form C
EPS Supplying Load/Engine Running (Std Default) or Custom _______________
Programmable #5 – Form A/B
(EAP 110/MEC 20 Exp –Group 1 Only)
Disabled (Std Default) or Custom _____________________________________
Programmable #6 – Form A/B]
(EAP 110/MEC 20 Exp –Group 2 Only)
OTHER OPTIONAL FEATURES
Remote Communication Port Enabled
VFD Display