MEC 20 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM047 Rev 13 05/03/30
55
Thomson Technology
9.4. CONTROL
PUSH-BUTTONS
The following control push-buttons are located on the front faceplate keypad.
9.4.1. RUN/OFF/AUTO/LOAD TEST
9.4.1.1.
RUN
In this position, the engine will start and operate continuously providing no
shutdown circuits are active. All protective circuits will be operative in this
mode. There will be no cooldown cycle at the end of a manual run
sequence.
9.4.1.2.
OFF
This position immediately stops the engine and locks it out from
operation. The OFF position also allows any shutdowns to be reset.
9.4.1.3.
AUTO
In this position, starting and stopping of the engine will be controlled by a
remote contact. When the remote start signal is removed the engine will
continue to run for the cooldown period (if selected) then stop. Re-
selecting the
Off
position will stop the engine immediately, even if the
cooldown period is not complete.
9.4.1.4.
LOADTEST
NOTE
:
The control feature is only operative if used in the
AMF application or if one of the programmable
output contacts is configured for “ATS Test” and a
remote transfer switch is interconnected with
remote testing circuitry.
In this position, a signal will be issued to a remote transfer switch to
permit an automatic engine start and load transfer. Once initiated, the
engine will receive a start signal from the transfer switch and upon the
generator reaching nominal voltage and frequency levels, a load transfer
will be initiated. The generator set will remain running on load until a