MEC 20 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM047 Rev 13 05/03/30
5
Thomson Technology
•
Discharge body static charge before handling the equipment (contact a
grounded surface and maintain contact while handling the equipment, a
grounded wrist strap can/should also be utilized).
•
Do not touch any components on the printed circuit board with your hands
or any other conductive equipment.
•
Do not place the equipment on or near materials such as Styrofoam,
plastic and vinyl. Place the equipment on grounded surfaces and only
use an anti-static bag for transporting the equipment.
2. INSTALLATION
2.1. GENERAL
INFORMATION
NOTE:
Installations should be done according to all
applicable electrical regulation codes as
required.
The following installation guidelines are provided for general information only pertaining
to typical site installations. For specific site installation information, consult Thomson
Technology as required.
Note:
Factory installations of THOMSON TECHNOLOGY
supplied control panels that have been tested and proven may deviate from these
recommendations.
CAUTION!!!
All installation and/or service work performed must be done by qualified
personnel only. Failure to do so may cause personal injury or death.
2.2. BATTERY SUPPLY INPUT
The MEC 20 can operate on any battery supply from 10 to 30 volts DC. The battery DC
negative or common conductor must be grounded to the main generator-set frame
ground. The MEC 20 is internally protected by a solid state type fuse that protects it
from inadvertent shorts on the output terminals. The solid state fuse will automatically
reset when the overcurrent condition is removed. Wiring from the engine cranking