11.2.9 Command ID
<id>ID<parameter><CR>
Identification number.
Access:
reading / writing
Description:
This command sets the identification number (THIES inter-
preter) or the slave address (MODBUS RTU interpreter). Only if
the id included in the command corresponds to the one set in
the wind transmitter, a response telegram is sent. One excep-
tion is the generic ‘id’ where all wind transmitters respond
(THIES interpreter). After changing the ‘id’, the device responds
immediately with the new ‘id’.
Parameter type:
unsigned integer
Parameter:
99 generic ‘id’ (THIES interpreter)
0 Broadcast slave address (MODBUS RTU interpreter)
Type return value:
unsigned integer
Return value:
see parameter
Value range:
0 to 99 (THIES interpreter)
1 to 247 (MODBUS RTU Interpreter)
Initial value:
0
(THIES interpreter) for sensor 4.3352x0.400
1
(MODBUS RTU Interpreter) for sensor 4.3352.x.0.401