Thermsaver unvented water heater Скачать руководство пользователя страница 4

4

STANDARD ENERGY LOSSES

The heat loss of each Unvented Unit while

maintaining the temperature of the stored water at 65 degrees

Celsius. (See performance table below).

1) Tests carried out by BBA. Slight variations may occur with

changes to water mains supply pressure

Performance

Nominal

Heat up

Heat up

Reheat

Reheat

Heat loss in

Capacity Model IDH Model DH Model IDH Model DH

24 hrs

Litres

Mins

Mins

Mins

Mins

kw/hr

80

33

64

23

53

1.12

130

28

115

21

90

1.50

150

33

138

24

104

1.82

175 27

167

24

124

2.10

215

35

212

30

153

2.64

255

42

263

35

184

2.73

305  

50

313

42

220

2.88

SITING THE UNIT

The unit can be placed anywhere convenient. Because it is

connected directly to the mains water supply it is equally efficient

on any floor – ground, first or second. Avoid areas that may be

subject to frost. Try to keep pipe runs as short as possible for

maximum economy, especially hot water discharge pipes running

down from the unit.

The unit can be fitted into a conventional airing cupboard and

does not require any additional insulation.

ALL UNVENTED VESSELS MUST BE STORED VERTICALLY

CHECK WATER PRESSURE & FLOW RATES

We suggest 1.5 bar pressure & 15 litres / minute flow rate to be the

minimum requirements for satisfactory operation. Less than this

the unit will still operate but you will not be able to run two, or

more, outlets at the same time. 85% of all U.K homes have more

than 2-bar pressure.

The mains supply must not exceed 16 bar. If it does a special

pressure-reducing valve will be required.

1 Element on IDH indirect models up to 305 litres and 80 litre

DH direct model

2 Elements on DH direct models from 130 up to 305 litres.

Additional elements from 215 to 305 litres are available on

request.

Cold-water control valve comprising line strainer, check valve,

pressure reducing valve set to 3 bar

Expansion relief valve with non return valve set at 6 bar

Tundish 15mm x 22mm F x F

Temperature / Pressure relief valve set at 90 degrees Celsius

and 7 bar pressure relief (factory fitted)

Motorised valve (indirect units only)

Cylinder thermostat-factory fitted to cylinder, maximum setting

85 degrees Celsius (indirect units only)

Thermal cut out set to operate at 87 degrees Celsius plus or

minus 3 degrees (indirect units only)

Expansion vessel capacity ranges as shown in the table below: -

Tank Size

80 to 130 Litres

150 to 215 Litres

255 to 305 Litres

Expansion Tank Required

12 Litres

18 Litres

25 Litres

2) These figures relate to a 45 degree differential between the

stored water and ambient temperature

WITH YOUR UNVENTED CYLINDER

THE FOLLOWING IS SUPPLIED AS STANDARD

Before commencing installation check that all the components of

your Unit are contained in the kit.

3KW Incoloy 825 heating element-incorporating thermostat to 

70 degrees Celsius and resetable safety cut out set at 80 

degrees Celsius

UNVENTED INSTALLATION INSTRUCTIONS

WARNING

: Under no circumstances must the factory fitted temperature pressure relief valve be removed. This will totally invalidate any

guarantee or claim. The cold-water inlet valve assembly must be fitted or the unit will not perform satisfactorily.

DO NOT ATTEMPT TO VENT THE PRIMARY CIRCUIT THROUGH THE UNIT.

All boilers should be installed to manufacturers instructions and the primary circuit through the unit must be pumped.

Содержание unvented water heater

Страница 1: ...unvented water heater installation manual 3bar kit version...

Страница 2: ...LAND BUILDING REGULATION P5 AFTER INSTALLATION THE BENCHMARK LOG BOOK MUST BE COMPLETED AND LEFT ALONG WITH THESE INSTRUCTIONS WITH THE HOUSEHOLDER FOR FUTURE REFERENCE INSTALLATION INSTRUCTION MANUAL...

Страница 3: ...jam or leak no noise from tank filling All your water hot and cold is direct from the mains Site the unvented water heater wherever convenient Your vessel fills your bath in minutes and will run two a...

Страница 4: ...05 litres and 80 litre DH direct model 2 Elements on DH direct models from 130 up to 305 litres Additional elements from 215 to 305 litres are available on request Cold water control valve comprising...

Страница 5: ...roperty with short lengths max 1 metre runs of 15mm going to baths showers and basin taps Smaller bore pipe can be used to suit taps SECONDARY CIRCULATION This is particularly easy to fit on unvented...

Страница 6: ...6 SECONDARY CIRCULATION CONNECTION DIAGRAM Fig 3 2 2 PORT S PLAN VALVE SYSTEM GUIDANCE LAYOUT ONLY Fig 4...

Страница 7: ...er thermostat fails WARNING Ensure that the immersion heater thermostat is set at 60 degrees Celsius FITTING THE THERMAL CUT OUT PRIMARY CONNECTIONS The motorised valve supplied and the thermal cut ou...

Страница 8: ...equivalent EXTERNAL EXPANSION TANK This smaller tank is connected to the cold water inlet side of the vessel Mount the tank according to separate manufacturers instructions provided with the External...

Страница 9: ...ully ii downward discharges at low level i e up to 100mm above the external surfaces such as car parks hard standings grassed areas etc are acceptable providing that where children may play or otherwi...

Страница 10: ...perate change the complete heating element assembly Important In the event of an over heat situation reset all thermal cutouts If hot water discharges from Tundish WARNING Do not turn the mains water...

Страница 11: ...egular service stamp by a qualified unvented installer Exclusions The guarantee does not cover The effects of large scale build up Any labour charges associated with replacing the unit or outs parts A...

Страница 12: ......

Отзывы: