PROBLEM SOLVING

No water in tap from the Unit

Check that mains supply is on.

Check that the line strainer is not blocked

Check that the combination valve has been fitted so that the arrow

on it faces in the direction of the water flow.

If the water at the hot tap is cold

Boiler (indirect): Ensure that the boiler has been switched on and

working correctly.

Check that no air blocks have occurred in the primary system

Check the following are all connected correctly

Cylinder Stat

Thermal cut out (Reset by pushing red button)

Motorised valve

Boiler thermostat (max setting 82 degrees Celsius)

Boiler thermal cut out (if fitted)(Reset by pushing red button)

Direct (Electric) Models

WARNING

: Isolate unit at main electric supply before opening

heating element cover.

Ensure that power is available to the element from the electric

mains and that the isolator is on. If there is power to the element

and the element fails to operate check as follows:

Check that the thermal cut out on the elements have not operated.

If they have, reset by pressing the red button. If they cut out again

as the water heats up the cylinder thermostat has failed and needs

replacing. Fit a new thermostat and reset the thermal cut out.

With power on and the thermal cut out reset check the output

terminal on the thermostat. If the circuit cannot be completed, the

thermostat and/or cut out needs replacing.

Check current amps drawn by the heater, should be approx. 15

amps. If heating element fails to operate, change the complete

heating element assembly.

Important. In the event of an over heat situation reset all

thermal cutouts.

If hot water discharges from Tundish

WARNING

: Do not turn the mains water supply off - switch off (1)

power to immersion heaters (Direct) or (2) shut down heating
boiler (Indirect)

If hot water discharges from the tundish on indirect models there

could be a fault with the thermal cut out, cylinder thermostat or

temperature pressure relief valve. On a direct model the fault could

lie with the heating element thermostat. We recommend you call

your installer or Fabdec ltd.

SPARES

When ordering replacement parts the serial number on the unit

should be quoted.

PART/COMPONENT REFERENCES

Expansion Vessel Kit (12 Litre) - 

951923

Expansion Vessel Kit (18 Litre) - 

951924

Expansion Vessel Kit (25 Litre) - 

951925

Motorised Valve - 

951878

Immersion Heater - 

951860

Temp/pressure Relief  Valve - 

951858

Twin Thermostat - 

951879

WARNING:

Should the factory fitted temperature and pressure

relief valve be tampered with your guarantee will be invalidated.
Neither the distributor nor manufacturer shall be responsible for
any consequential damage howsoever caused.

TABLE 1   SIZING OF COPPER DISCHARGE PIPE (D2) FOR COMMON T&P RELIEF VALVE SIZES

Valve outlet Size 

 

Minimum size of 

 

Minimum size of

Maximum resistance

 

Resistance created by

           discharge pipe D1

discharge pipe D2

allowed, expressed as a

 

each elbow or bend 

from tundish

length of straight pipe 

(i.e. no elbows or bends) 

G1/2

15mm

22mm

up to 9m

0.8m

28mm

up to 18m

1.0m

35mm

up to 27m

1.4m

G3/4 22mm

28mm

up 

to 

9m

1.0m

35mm

up to 18m

1.4m

42mm

up to 27m

1.7m

G1 

28mm

35mm

up to 9m

1.4m

42mm

up to 18m

1.7m

54mm

up to 27m

2.3m

Содержание unvented water heater

Страница 1: ...unvented water heater installation manual 3bar kit version...

Страница 2: ...LAND BUILDING REGULATION P5 AFTER INSTALLATION THE BENCHMARK LOG BOOK MUST BE COMPLETED AND LEFT ALONG WITH THESE INSTRUCTIONS WITH THE HOUSEHOLDER FOR FUTURE REFERENCE INSTALLATION INSTRUCTION MANUAL...

Страница 3: ...jam or leak no noise from tank filling All your water hot and cold is direct from the mains Site the unvented water heater wherever convenient Your vessel fills your bath in minutes and will run two a...

Страница 4: ...05 litres and 80 litre DH direct model 2 Elements on DH direct models from 130 up to 305 litres Additional elements from 215 to 305 litres are available on request Cold water control valve comprising...

Страница 5: ...roperty with short lengths max 1 metre runs of 15mm going to baths showers and basin taps Smaller bore pipe can be used to suit taps SECONDARY CIRCULATION This is particularly easy to fit on unvented...

Страница 6: ...6 SECONDARY CIRCULATION CONNECTION DIAGRAM Fig 3 2 2 PORT S PLAN VALVE SYSTEM GUIDANCE LAYOUT ONLY Fig 4...

Страница 7: ...er thermostat fails WARNING Ensure that the immersion heater thermostat is set at 60 degrees Celsius FITTING THE THERMAL CUT OUT PRIMARY CONNECTIONS The motorised valve supplied and the thermal cut ou...

Страница 8: ...equivalent EXTERNAL EXPANSION TANK This smaller tank is connected to the cold water inlet side of the vessel Mount the tank according to separate manufacturers instructions provided with the External...

Страница 9: ...ully ii downward discharges at low level i e up to 100mm above the external surfaces such as car parks hard standings grassed areas etc are acceptable providing that where children may play or otherwi...

Страница 10: ...perate change the complete heating element assembly Important In the event of an over heat situation reset all thermal cutouts If hot water discharges from Tundish WARNING Do not turn the mains water...

Страница 11: ...egular service stamp by a qualified unvented installer Exclusions The guarantee does not cover The effects of large scale build up Any labour charges associated with replacing the unit or outs parts A...

Страница 12: ......

Отзывы: