RENEWABLE HEATING & COOLING TECHNOLOGY
PARAMETER CHECKING AND ADJUSTMENT
Unit Status Query Table
Code
Parameter
Name
A1
Coil
temp
A2
Return
gas
temp
A3
Exhaust
gas
temp
A4
Ambient
temp
A5
Outlet
water
temp
A6
Return
water
temp
A7
Reserved
A8
Compressor
current
A9
Opening
of
the
EEV
A10
Reserved
E1
~
E6
Error
code
display
Parameter settings
User parameters(can be adjusted by users.)
Code
Parameter
Name
Range
Default
L2
Outlet
water
temp
variation
for
compressor
start
2
℃~
25
℃
5
℃
L3
Outlet
water
temp
set
when
heating
5
℃~
60
℃
55
℃
L4
Outlet
water
temp
set
when
cooling
5-32
℃
12
℃
L5
Ambient
temp
for
electric
heater
start
0
℃~
35
℃
5
℃
L6
Return
water
temp
20
℃~
65
℃
40
℃
L7
Allowable
water-refill
temp
20
℃~
60
℃
20
℃
L8
Compressor
current
0
~
40A
0
L9
Thermostatic
valve
temp
set
30
℃~
55
℃
55
℃