ERROR CODES

When an error occurs or the protection mode is set automatically,the wired controller will 
display an error code as below.

Failure

Code

Possible reasons

Remedy

Er 15

Inlet water temp sensor 
failure

1)sensor open circuit
2)sensor short circuit
3)Main PCB damaged

1)Check the sensor connection
2)Replace the sensor
3)Replace the main PCB

Er 27

Outlet water temp 
sensor failure

As above

As above

Er 42 Coil temp sensor failure

As above

As above

Er 21

Ambient temp sensor 
failure

As above

As above

Er 18

Compressor exhaust 
gas temp. sensor failure

As above

As above

Er 23

Inadequate outlet water 
temp protection under 
cooling mode

1)Inadequate water flow rate
2)Inadequate inlet water temp
3)Main PCB damaged

1)Check the water filter and 
water circuit (no block)
2)Adjust the setting temp to 
normal working range
3)Replace the main PCB

Er 44

Anti-freeze 
protection in Winter

This function occurs when 
ambient temp is too low and unit 
is in standby

No action needed

Er 05 High pressure protection

1)Inadequate flow rate
2)Uncompressed gas in refrigerant     
system
3)Overcharge with refrigerant
4)Water temp setting too high
5)Poor connection of pressure switch
6)Pressure switch failure
7)Main PCB damaged

1)Check pump and water control 
valve
2)Discharge and them recharge 
the refrigerant
3)Discharge some refrigerant
4)Set lower water temp
5)Reconnect the switch
6)Replace the pressure switch
7)Replace the PCB

Er 06

Low pressure protection

1) Undercharged refrigerant
2) Capillary block
3) Poor connection of pressure switch
4) Pressure switch failure
5) Main PCB damaged

1) Add some refrigerant
2) Replace the capillary
3) Reconnect the switch
4) Replace the pressure switch
5) Replace the PCB

Er 03

Water flow switch failure

1) Inadequate water flow 
2) Water flow switch damaged
3) Main PCB damaged

1) Check the pump
2) Replace the water flow switch
3) Replace the PCB

Er 37

1) Too low water flow 
2) Main PCB damaged

1)Check the water filter and water 
circuit (no blockages)
2)Replace the PCB

Failure for too big inlet/outlet

 

water temp difference for 
cooling mode

Er 12

1) Refrigerant Undercharged

1) Add some refrigerant

High compressor 
exhaust gas temp 
protection

Содержание LCSPI-120

Страница 1: ...RENEWABLE HEATING COOLING TECHNOLOGY Swimming Pool Heat Pump Enjoy longer swimming seasons with less cost Operation Installation Manual...

Страница 2: ...ONTENTS OVERVIEW OF THE UNIT INSTALLATION Installation guidelines Locating your Unit Water connection Electrical connection Trial running OPERATING THE UNIT Features and functions User interface Butto...

Страница 3: ...be used with all types of water treatment including chlorine iodine bromine and salt water Multiple functions Cooling and heating functions available Auto operation Auto restart Auto defrost Auto time...

Страница 4: ...pply If there is no suitable earthed supply available have one installed by a qualified electrician Do not move repair the unit yourself Before carrying out any maintenance service or repair work the...

Страница 5: ...OGY CONTENTS Before starting the installation please make sure that all items are found inside the box The Unit Box Item Image Qty Swimming pool heat pump 1 Operation and Installation Manual 1 Accesso...

Страница 6: ...RENEWABLE HEATING COOLING TECHNOLOGY OVERVIEW OF THE UNIT Page 5 LCSPI 120 150 170...

Страница 7: ...Page 6 RENEWABLE HEATING COOLING TECHNOLOGY EXPLODED VIEW...

Страница 8: ...ed to a solid wall Try to avoid placing the unit under a tree or exposed to extreme conditions Water connection The heat pump is connected to a filtration circuit with a by pass It is imperative that...

Страница 9: ...e supply cables Trial Running After connecting the unit to the pool system ensureyour installation is complete with a suitable by pass and electrical connections by a qualified engineer Be sure that 1...

Страница 10: ...THE BUTTONS OF THE DIGITAL CONTROLLER WITH A HARD POINTED OBJECT THIS MAY DAMAGE THE DIGITAL CONTROLLER NEVER INSPECT OR SERVICE THE DIGITAL CONTROLLER YOURSELF REFER TO A QUALIFIED SERVICE ENGINEER B...

Страница 11: ...tory parameter query interface factory parameter query password 0814 manufacturer setting password 8563 On factory parameter query interface screen press to enter into parameter setting interface pres...

Страница 12: ...wer off On Timer setting interface screen press to confirm current Timer settings and back to main operation interface Settings way for other groups of Timers is same as Timer 1 Timer 1 2 are for unit...

Страница 13: ...A10 Reserved E1 E6 Error code display Parameter settings User parameters can be adjusted by users Code Parameter Name Range Default L2 Outlet water temp variation for compressor start 2 25 5 L3 Outle...

Страница 14: ...No action needed Er 05 High pressure protection 1 Inadequate flow rate 2 Uncompressed gas in refrigerant system 3 Overcharge with refrigerant 4 Water temp setting too high 5 Poor connection of pressur...

Страница 15: ...ed using compressed air or by flushing with clean water It may be necessary to remove the unit cover and air inlet grid first Attention Before opening the unit ensure that all electrical supplies are...

Страница 16: ...sales service technician Work on the heat pump may only be carried out by authorized and qualified after sales service technicians ENVIRONMENTAL INFORMATION This equipment contains fluorinated greenh...

Страница 17: ...be treated at a specialized treatment facility for re use recycling and recovery By ensuring that this product is disposed of correctly you will help to prevent potential negative consequences for th...

Страница 18: ...Page 17 RENEWABLE HEATING COOLING TECHNOLOGY WIRING DIAGRAM Please refer to the wiring diagram on the electric box Model LSCPI 120 150 170...

Страница 19: ...Page 18 RENEWABLE HEATING COOLING TECHNOLOGY Model LCSPI 210 250 300...

Страница 20: ...Page 19 RENEWABLE HEATING COOLING TECHNOLOGY TECHNICAL SPECIFICATIONS...

Отзывы: