  Ecopower Controller Motherboard  

 

 

Function 

 

 

Control 

 

Comments 

 

Standard 

Fan Heat Interlock – 

The heat output is governed by the 
fan speed. If low or medium fan 
speed is selected the heat output 
will operate on only first heat stage. 
Second stage heating will only 
operate on high fan speed. 

 

DIP1 Option 

Suitable on vertical electrically 
heated Designer air curtain. 
Maximum heat output achieved if 
maximum fan speed selected.  
Independently set-up DIP switch 
on each mother board. This 
feature operates in manual or 
auto mode. 

As supplied, the 
default setting would 
be for heat and fan 
settings to be 
independent (DIP1 
OFF). 

Disable Fan Run-on – 

 

Disable fan run-on. 

DIP2 Option  

(LPHW & 

Ambient only) 

 
 
 

Must only be used for LPHW and 
Ambient air curtains.  
Independently set-up DIP switch 
on each mother board. 

As supplied, the 
default setting would 
enable fan run-on 
(DIP2 OFF). 

Thermostat Master –

  

Only the air sensor thermistor in 
the master air curtain will be used 
for measuring the reference air 
temperature for the whole 
master/slave installation.  

 

DIP3 Option  

 

The air sensor thermistors in all 
the slave air curtains will be 
ignored. This will then avoid 
situations on larger doorways with 
master/slave air curtains where 
some units can blow cold air 
whilst others can blow warm air, 
because they currently all refer to 
their own air sensor for control of 
the heat output of each air 
curtain.  
The master air curtain need not 
be the one that the wall control is 
plugged into. This dip switch 
setting must also be used for 
Global Switching (Master/Slave) 
via the INHIBIT terminal – see 
next page.

As supplied, the 
default setting would 
be for the air sensor 
thermistor on all 
units to be 
measuring  
(DIP3 OFF). 

 

Overheat Fan Disable –

  

If DIP4 is on and thermal cut-out(s) 
operate both heat and fan circuits 
are isolated and LED’s on wall 
switch flash.  If DIP4 is off and 
thermal cut-out(s) operate, only the 
heating circuit is isolated and the 
LED’s on the wall switch flash. 

DIP4 Option 
(Electric only)  

 

Independently set-up DIP switch 
on each mother board. 

 

To remove fault, isolate electrical 
supply to air curtain, reset TOC 
and reconnect supply.

  

As supplied, the 
default setting would 
enable fan if TOC 
trips (DIP4 OFF). 

 

Fan run-on time set two minutes. 

Built-in 

If “FAN ONLY” has been 
selected, at switch off, no fan run-
on. 

 

 

              

white rectangle indicates the moveable head of each 4 way DIP switch 

 
 

 
 
 
 

 

 

DIP switches fitted on the Ecopower board provide a selection of optional features as 
described above.  Isolate and switch electrical power off before configuring and/or 
changing any DIP switch settings. 

ON 

OFF 

 1    2     3    4

ON 

OFF 

 1    2     3    4

ON 

OFF 

 1    2     3    4

ON 

OFF 

 1    2     3    4

Содержание C series

Страница 1: ...ION MAINTENANCE INSTRUCTIONS PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING INSTALLATION Thermoscreens Ltd St Mary s Road Nuneaton Warwickshire England CV11 5AU Email sales thermoscreens com Tel 44 0 24 7638 4646 Fax 44 0 24 7638 8578 www thermoscreens com ...

Страница 2: ...l Brackets Fixing Bolts additional bracket and bolts supplied for C1500 C2000 models Note Optional filters are available on Water and Ambient models only and are packed separately If anything is missing or damaged please contact your place of purchase immediately For your records Date of Purchase Place of Purchase Serial Number For warranty purposes proof of purchase is necessary so please keep a ...

Страница 3: ...t see table 1 Step 1 Refer to Figure 1 for mounting details and drill the wall accordingly Step 2 Screw in the top bolts leaving a small gap between the head and the wall lower the unit onto the bolts via key hole slots in the top of the wall brackets and then screw in the bottom bolts Step 3 Ensure all fixing bolts are tightened to stop the unit being lifted off the wall Ceiling Suspension 6mm th...

Страница 4: ...r 25mm gland Electrical supply inlets C1500 C mm N A E mm F mm D mm N A 161 710 B mm A mm C1000 1137 908 275 Rp 1 2 1 2in BSP female LPHW connections 964 704 161 874 1748 604 170 1208 21 120 1928 2200 C2000 1408 1669 M6 inserts C B A C 198 100 min 220 E D E 33 F 75 Figure 1 ...

Страница 5: ...lectrical supply the unit requires a neutral connection 3N Cable glands used for the Electrical Input must be rated IP21 or higher Table 1 Air Curtain Electrical Supply V ph Hz Rated Power Input kW Current per phase A Heat Output kW Weight kg C1000A 230 1 50 0 15 0 7 N A 15 C1500A 230 1 50 0 20 0 9 N A 21 C2000A 230 1 50 0 25 1 1 N A 31 C1000W 230 1 50 0 15 0 7 6 0 18 C1500W 230 1 50 0 20 0 9 9 0 ...

Страница 6: ...s isolation valves are fitted in the flow and return pipework When fitting the 3 port valve ensure that the pipe connections are fitted as detailed below and are in accordance with the manufacturers leaflet supplied with the valve Air Curtain Water Flow Rate l s 82 72 C Coil Water Pressure Drop kPa C1000W 0 14 2 77 C1500W 0 21 6 74 C2000W 0 29 13 40 Ambient Models Ambient units are supplied with a...

Страница 7: ...x M3 5 mounting screws not provided With the cable RJ plug locking clip lying nearest to controller PCB connect the RJ plug to the RJ socket on the board Note For controller DIP switch options refer to Ecopower Plus Remote Control Operation and DIP Switch Settings Refit the controller front case to the back case The air curtain end of the control cable should be connected to one RJ socket fitted e...

Страница 8: ...ins where some units can blow cold air whilst others can blow warm air because they currently all refer to their own air sensor for control of the heat output of each air curtain The master air curtain need not be the one that the wall control is plugged into This dip switch setting must also be used for Global Switching Master Slave via the INHIBIT terminal see next page As supplied the default s...

Страница 9: ...need connect the remote contact to only one of them to turn all units on and off in the master slave system For global switching to work on the slave units need to set DIP3 Option see previous page on the unit that the remote contact is wired to and have previously turned the unit on with the wall switch As supplied a wire link will be fitted to the terminal block on every unit For summer settings...

Страница 10: ...4001160 6 UK Page 10 of 16 ...

Страница 11: ...4001160 6 UK Page 11 of 16 ...

Страница 12: ...4001160 6 UK Page 12 of 16 ...

Страница 13: ...o dissipate excess heat DIP Switch Settings At the back of the Ecopower Plus remote control PCB there are four DIP switches see above that provide the following optional features DIP1 Restart on Power Up If electrical supply to the air curtain is interrupted upon restoring electrical supply the customer s settings on the remote control will be retained The default is with this feature ON DIP2 Stop...

Страница 14: ...or replacement Fault Conditions In the event of a fault the thermal cut out s Note If the mains supply is isolated during operation then the thermal cut outs may operate or internal fuses may operate The thermal cut out s are located on the top face of the unit directly above the element banks one on the 1 1 5m and two on the 2m model For Ecopower units two internal electrical fuses are located on...

Страница 15: ...act Installer Service Agent to investigate why thermal cut out s have operated Service Agent to reset thermal cut out s Contact Installer Yes No Yes Yes No No No Yes Yes No No Is Electrical Power switched on Are the fans operating correctly Is the unit discharging warm air Check if thermal cut out s have tripped Electric Heated only Do the LED s light up on the remote control Is the remote control...

Страница 16: ...in please note that the motor s are permanently lubricated and require no additional lubrication If filters are fitted ensure these are regularly inspected and cleaned or replaced All dirty or blocked filters should be immediately replaced Once the air curtain has been cleaned check all electrical connections within the unit ensuring terminals are tight and that crimped connections have not become...

Отзывы: