Ecopower Plus Remote Control Operation and DIP Switch Settings
On/Off (I/O)
Press On/Off switch (1) to turn the air curtain
On and operate as follows:-
Press Auto switch (2) to cycle between Manual
and Automatic modes. The Auto on indicator
LED is lit for "Auto Mode" and un-lit for "Manual
Mode".
Manual
:
Heat output can be selected as Zero, Half Heat
or Full Heat. Heating levels are selected by
stepping up or down with switches (3) and (4).
Heating level indicator LED's go 0%, 50% or
100% to show the level selected.
Automatic
:
If DIP switches 1, 2 and 4 on the Ecopower
motherboard are set to OFF, the air curtain
measures the incoming air temperature and
automatically selects the necessary amount of
heat to keep it at the level selected.
Fan Speed
Switches (5), (6) and (7) select fan speed low,
medium or high respectively. The appropriate
LED above each fan speed indicator is
illuminated to show which fan speed is selected.
Pressing the On/Off switch (1) again switches the
air curtain off with all the LED’s switched off. If a
heated air curtain is heating when switched off
the fan will run-on at low fan speed for an
extended time (approx. 2 minutes) to dissipate
excess heat.
DIP Switch Settings
At the back of the Ecopower Plus remote
control PCB there are four DIP switches (see
above) that provide the following optional
features.
DIP1
Restart on Power-Up –
If electrical
supply to the air curtain is
interrupted, upon restoring electrical
supply, the customer’s settings on
the remote control will be retained.
The default is with this feature ON.
DIP2
Stop Fan on Cold –
Fans switch off
when heating level is achieved
(Automatic mode only). The default
setting is with this feature OFF.
DIP3
Never Blow Cold –
Unit always
heats in Automatic mode (i.e. will
not go to ambient mode). The
default setting is with this feature
OFF.
DIP4
Air Sensor in Controller –
The air
sensor in the remote controller is
enabled (DIP4 ON) and the air
sensor on the Ecopower
motherboard in the air curtain is
disabled. Temperature control for
Automatic Mode is then done at the
remote control, which may be an
advantage to limit overheating of the
door entrance area. The default
setting is with this feature OFF.
Do not switch the air curtain On/Off from the isolator. If the mains supply is
isolated or cuts-out during operation the safety thermal cut-out(s) for electric
heated air curtains within the air curtain may operate. If this happens the
thermal cut-out(s) will need to be reset by a competent technician.