Procedure for additionally filling the heating system with water:

1.  Disconnect the boiler from electrical voltage
2.  Slowly open the valve for additional filling and monitor manometer on the control panel of the boiler.
3.  Set the system pressure to the necessary value (according to the heating system, recommended 1.0 – 1.5 bar)
4.  Close the valve for additional filling
5.  Connect the boiler to the electricity network and connect the boiler again

!

 

2.5  Maintenance and service

Regular maintenance is very important for reliable operation, to achieve a long service life, and efficient combustion. We 

consistently recommend the user to contact a service organisation in the place of residence and to ensure regular inspections 

of the boiler after one year of operation (see chapter: Warranty and Warranty Terms). The service technician will for example, 

inspect the control and security elements of the boiler, inspect the tightness of the gas and water distribution or the cleaning 

of the burner and the exchanger of burnt dust particles, etc.

For error-free operation of the heating system, it is also necessary to regularly inspect the initial water pressure in a cold 

condition. In the case of a decrease of pressure below 0.8 bar, it is necessary to additionally fill the heating system.

 

2.5.1  Additionally filling the heating system

Adding of water to the heating system (system pressurizing) must be performed via the top-up valve, which forms part of 

the heating system. Water for filling must fulfil certain parameters, see chapter 3.8.

During additional filling it is necessary to take the following conditions into consideration:

 

2.6  Warranty and warranty terms

The producer is not liable for any mechanical damage to individual components by rough handling, for damage caused by 

unprofessional intervention into the electronic system during the adjustment and connection of the add-in regulation, for 

damages caused by the use of other parts and components than the original components used by the producer.

The warranty is also not applicable to defects caused by non compliance with the binding notifications and terms stated in 

individual parts of this manual.

The warranty is not applicable to non-standardized relations in distribution networks (variation of electrical voltage – in 

particular voltage peaks, pressure and cleanliness of gas, etc.), defects to equipment outside the boiler that influence activity, 

improper collection of burnt gases, dirt in the combustion air, damage from outside influences, mechanical damage, storage, 

transport and defects originated by natural disasters.

In such cases the service organisation may require that the client pays for the repair.

THERMONA Ltd provides a warranty according to the stated in the Warranty Certificate delivered with the product.

Terms for application of the warranty:

1.  Regular, 1x per year, inspection of the gas boiler. Inspections must only be performed by an authorized organisation, 

i.e. contractual service. The list of service centres is attached to each boiler. The actual list of service centres is available  

from www.thermona.cz

2.  Documentation for all records of warranty repairs and annual inspections of boilers is in the appendix to this manual.
3.  Submitting completed and confirmed warranty certificate and protocol on commissioning into the operation of THERM 

products

a)  the pressure of utility water supplied into the boiler must be higher than the water pressure in the heating 

system (otherwise the heating water can flow back to the water mains!)

b)  the additional filling of water is necessary to be done exclusively under a cold status (the temperature of 

the heating water in the boiler is a maximum of up to 35 °C) 

Содержание THERM 90 KD.A

Страница 1: ...Manual for installation operation and maintenance of boiler Hanging gas condensing boiler THERM 90 KD A...

Страница 2: ...THERM 90 KD A Manual for installation service and maintenance of boiler...

Страница 3: ...Complete character of the delivery 19 3 3 Location of the boiler 20 3 4 Suspending the boiler 20 3 5 Connecting the boiler to the hot water system 21 3 5 1 Dimensions and connection 21 3 5 2 Graphs of...

Страница 4: ...res to maintain the minimum pressure of the water in the heating system of 0 8 bar measured in cold state With regard to their power and use variability the THERM 90 KD A boilers are not fitted with e...

Страница 5: ...al to the volume of air through the mixer delivered with the ventilator Therefore it can be stated that the output on the boiler depends on the volume of the air flow for combustion As a result the re...

Страница 6: ...gases disconnect the boiler ensure ventilation of the room windows door call service the boiler must not be used until after the service inspection In the case of a consumer appliance fire close the g...

Страница 7: ...Temperature of glue gases in overheated condition C 82 Lower flue gas temperature at minimum thermal power C 25 Weight flow of burnt gases g s 1 10 2 42 8 Weight flow of flue gases at minimum thermal...

Страница 8: ...et of boiler THERM 90 KD A 1 Condensing chamber 2 Ventilator 3 Heating temperature probe 4 Mixer 5 Emergency thermostat 6 Circulation pump 7 Gas valve 8 Safety valve 9 Control panel 10 Pressure switch...

Страница 9: ...ummer regime only heating of DHW is ON the heating is OFF Winter regime heating and heating of DHW is ON Unblocking the failure status of the boiler Service mode the function sweeper the output of the...

Страница 10: ...er the termination of the setting the indication of the set temperature remains for about 5 seconds The following permanent display of the numeric value and the symbol the real temperature of the resp...

Страница 11: ...rface of the cascade is active Description of symbols shown on the display 2 1 3 Information menu Buttons and are used for entrance and bi directional browsing in the information menu in the following...

Страница 12: ...is attached to the product The procedure for the first ignition of the boiler is as follows set the rotary button of the input temperature of the heating water of the boiler to the maximum insert the...

Страница 13: ...least a simple room thermostat The room temperature is time stable and keeps the boiler in the operating regimes It is recommended to use the built in equitherm regulation either in dependently or com...

Страница 14: ...we recommend not to mount thermostatic heads on radiators in the reference room at all 2 3 3 Operation of the boiler using built in equithermal regulation This regime is accessible in the boiler in t...

Страница 15: ...nds to the shift of the curve 0 C After inspection of the temperature of the heated space after approximately 24 hours it is possible to perform additional setting according to all requirements for th...

Страница 16: ...ked In the case of any increase above 86 C the burning is stopped and circulating pump remains active The reignition is in the case of a decrease of the temperature under 80 C The working phase of the...

Страница 17: ...stat within the range 0 10 minutes may only be performed by an authorized service technician Notification All the above mentioned security and registered functions are in activity only if the boiler i...

Страница 18: ...s by rough handling for damage caused by unprofessional intervention into the electronic system during the adjustment and connection of the add in regulation for damages caused by the use of other par...

Страница 19: ...ol on the commissioning of THERM products into operation 6 Application for registration into the prolonged warranty programme 7 Confirmation of completing 1 and 2 service inspection 8 Hanging bar incl...

Страница 20: ...hane polystyrene polyethylene PVC etc The safe distance between flammable items and the boiler is 50mm from the chimney flue and the control hole 200mm Flammable items must not be located at lower dis...

Страница 21: ...m Due to the optimal use of the condensing regime of the boiler it is recommended to design heating systems for low temperatures t 50 30 C The minimum overpressure of the system is 0 8 bar We recommen...

Страница 22: ...0 Heating systems in buildings Design and assembly The producer requires mount into the slides of the pump filter and de sludge equipment e g Spirovent Kal mount a bypass valve in heating systems with...

Страница 23: ...ss of all joints 3 7 Filling and discharging of the heating system When filling the heating system the boiler must be disconnected from the electricity network by disconnecting the fork from the socke...

Страница 24: ...ases of these types of boilers must be designed by means of the certificate smoke collection system delivered by the producer From the viewpoint of checking the route for burnt gases it is necessary t...

Страница 25: ...t has voltage free contact can be used i e no other voltage is supplied into the boiler It is necessary to connect the room thermostat to the boiler by a two core conductor The recommended cross secti...

Страница 26: ...must not be grounded to the body in several places For example a SYKFY cable is recommended Construction C 13 axial horizontal variant with termination to the peripheral wall The piping can be double...

Страница 27: ...tart and mixture ration are adjusted by the service technician during start up of the boiler by means of the flue gas analyser The gas fitting is set exclusively by an employee of the authorized servi...

Страница 28: ...28 THERM 90 KD A 4 2 Electrical connection diagram...

Страница 29: ...er alloys are collected into the sorted metal collection units The thermal insulation of the combustion chamber is harmless to health and is disposed of in common communal wastes For storage it is nec...

Страница 30: ...n burner power consumption Pign kW In standby mode PSB kW Emissions of nitrogen oxides NOx mg kWh Sound power level indoors LWA dB For combination heaters Water heating energy efficiency class Water h...

Страница 31: ...Slovak Republic EC notified body identification number 202 THERM 90 KD A Certificate of testing of the model according to the EC Directive for consumer appliances for gas fuel 2009 142 EEC No E 30 01...

Страница 32: ...THERMONA spol s r o Star osada 258 664 84 Zast vka u Brna 420 544 500 511 FAX 420 544 500 506 thermona thermona cz www thermona cz THERMONA 2016 09 2016...

Отзывы: