3.5.3 CHANNEL SET SCREENS – HUMIDITY
THERMOMAX
3
4
1-4
Channel 1 to 4 function selector
By pressing any of the Channels 1 to 4 function selector keys a
second time, the
Channel Set Screen
for that channel will be displayed.
5
By pressing the keys you can select the window you wish to
change the information in.
6
Bargraph Display Scale
By pressing the
or
key, the bargraph scale may be adjusted to show
either the temperature or the humidity range best suited to the particular
installation. The form of measurement displayed on this bargraph depends
on each channel input.
7
High Alarm Stage 1 Humidity (0% to 99.5%)
The stage 1 alarm is a time / humidity related alarm. If the maximum
threshold is exceeded, a timer is initiated, and no further action is taken at
this time.
8
High Alarm Stage 1 Delay (1 – 99 min.)
After the maximum threshold has been exceeded, the alarm will not be
triggered until the time exceeds the time delay set here. If the humidity
drops below the threshold before the expiry of this delay, the timer is reset. If
following this, the humidity rises above the threshold again, the timer
restarts from zero.
9
High Alarm Limit Stage 2 Humidity (0% to 99.5%)
If at any time, this limit is exceeded, the time delays will be overridden and
the alarm will trigger immediately.
10
Low Alarm
All the functions described in 7 – 9 above also apply to the Low Alarm.