13
3.3.3 SET SCREEN 3 : SYSTEM PRESETS 2
THERMOMAX
3
4
1
SET SCREEN function selector
Pressing this key a third time reveals Set Screen 3.
2
Alarm Mute
Alarm mute period for Channel 1 (from 0 to 95 Minutes). If any key is
pressed during an Alarm situation for this channel, the buzzer will be muted
(silenced) for this period.
3-5
Alarm Mute period for Channel 2 to Channel 4(from 0 to 95 Minutes).
Same as above.
6
Channel select for Channel 1. Each sensor input can be “switched” on or off
by pressing the
or
keys for 5 seconds respectively. When the sensor
input is switched “ON”, the unit will operate in normal mode and the actual
sensor temperature will be monitored and logged to the databank every 15
minutes. If the sensor input is switched “OFF”, the unit will display 0°C
continuously. This value will also be logged to the databank. Hence it is
therefore only necessary to connect sensors to the required number of
inputs.
Note:
If a channel is switched off, the Alarm parameters will automatically
revert back to the default factory settings to prevent an alarm occurrence.
These parameters cannot be changed until the sensor input is switched on
again.
7-9
Channel Select for channel 2 to channel 4.
6
7
8
9
2
3
4
5
1