Thermokon LCF02 Touch 3AO2DO Скачать руководство пользователя страница 8

Page 8 / 15 

 

Issue Date: 22.01.2020

 

 

 

 

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Deutschland · tel: 02778/6960-0 · fax: -400 · 

www.thermokon.de

 · 

[email protected]

 

LCF02-Touch_3AO2DO_Datasheet_en.docx   © 2020 

Input Register 

Address  Access 

Description 

Resolution / Unit 

 

0x0000 

Read-only 

Thermokon Model identification 

0xFF11 = FC182 LCF-3AO2DO

 

 

   

0x0001 

Read-only 

Firmware-Version 

e.g. 0x1A20 = 1.10.2.0

 

 

   

0x0002 

Read-only 

Back-Box type 

32 = 3AO2DO

 

 

   

0x0003 

Read-only 

Value of the integrated temperature sensor °C/°F 

0…500 = 0..+50,0 °C

 

0,1 

°C/°F   

0x0004 

 

Read-only 

fan status 

0b00000000 = OFF 

0b00000001 = Stage Low 

0b00000010 = Stage Medium 

0b00000100 = Stage High 

0b00001000 = Auto OFF 

0b00001001 = Auto Low 

0b00001010 = Auto Medium 

0b00001100 = Auto High

 

 

   

0x0005 

Read-only 

VA1 status 

0-100 0 = 0 (Off) …100% (On) 

 

   

0x0006 

Read-only 

VA2 status 

0-100 0 = 0 (Off) …100% (On) 

 

   

0x0007 

Read-only 

electrical heating status

 

0-1000 = 0 …100% 

0,1 

   

0x0008 

Read-only 

external temperature sensor °C/°F 

-200…+1000 = -20,0..+100,0 °C

 

0,1 

°C/°F   

0x0009 

Read-only 

failure status 

0x00=no failure 

0x01= control loop temperature sensor alarm 

0x02=external  temperature sensor high limit Alarm 

0x04=external  temperature sensor low limit Alarm 

0x08= change over sensor missing alarm

 

 

   

10 

0x000A 

Read-only 

External input 1 

0 = Contact Open, 1= contact closed (for window contact, 

dew point sensor)

 

 

   

11 

0x000B 

Read-only 

External input 2 

0 = Contact Open, 1= contact closed (for OCC-sensor, 

keycard Switch)

 

 

   

 

Holding Register 

General settings 

Address 

Access  Description 

Resolution / Unit 

Default 

256 

0x0100 

Read-write 

Customer set Device location identification

  

0…65535 

1.0 

 

257 

0x0101 

Read-write 

LCD Temperature Unit

 

0=°C 

1=°F 

 

 

258 

0x0102 

Read-write 

Beeper Intensity 

0=Off 

1..5 (Volume)

 

 

 

259 

0x0103 

Read-write 

Backlight intensity operated

 

0..100 

1.0 

80 

260 

0x0104 

Read-write 

Backlight intensity for screen saver (Parameter 7) 

0..25

 

 

 

20 

261 

0x0105 

Read-write 

Backlight operating delay setting 

1….255 = 1…255 seconds ON 

1.0 

15 

262 

0x0106 

Read-write 

Internal Sensor Temperature Offset

  

(added to meaured value) 

-50…50 = -5,0..+5,0 °C 

0.1 

°C/°F 

263 

0x0107 

Read-write 

external Sensor Temperature Offset

  

(added to meaured value)  

-50..+50 = -5,0..+5,0 °C 

0.1 

°C/°F 

264 

0x0108 

Read-write 

Display language 

0= German 

1= English 

2= no wording 

 

 

265 

0x0109 

Read-write 

Individual passwords setting 

001-999

default=987, 000 = no password 

 

 

987 

Содержание LCF02 Touch 3AO2DO

Страница 1: ...should only be used for the intended application Unauthorised modifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly...

Страница 2: ...ture acceptance of the wall or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are TECHNICAL DATA Measuring values temperature Output v...

Страница 3: ...voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected with each other and all negative operating voltage input terminals reference...

Страница 4: ...22 Heating valve 29 Off delay active 2 Schedular 9 Fan coil type 16 Set fan speed 23 Valve opening 30 Key locked 3 Room temperature 10 Auto mode 17 Power ON OFF 24 Dew point 31 Eco Mode active 4 Setp...

Страница 5: ...ID 247 1 2 Baud rate 1 4800bps 2 9600 3 19200 4 38400 2 3 Parity 0 none 1 odd 2 even 0 4 Stop Bits 1 1 Stopbit 2 2 Stopbits 2 5 Temperature Offset Internal Sensor 5 0 K 5 0 K 0 6 Temperature Offset E...

Страница 6: ...114 The display will show the average of both ECO Setpoint Temperatures 25 18 2 21 5 and the leaf symbol to indicate the ECO mode In ECO mode the setpoint is fixed and the device does not react to any...

Страница 7: ...switched OFF Switch thermostat to last state before power failure Record and Memorize Turn the thermostat ON Storage during power loss The status will be kept in EEPROM while the power failure so no...

Страница 8: ...ture sensor alarm 0x02 external temperature sensor high limit Alarm 0x04 external temperature sensor low limit Alarm 0x08 change over sensor missing alarm 10 0x000A Read only External input 1 0 Contac...

Страница 9: ...symbol shall be displayed and blink twice 0 270 0x010E Read write Display Settings 0b00000001 show Setpoint if no setpoint is shown the setpoint keys are locked 0x010D 0x10 lock temp setting 0b000000...

Страница 10: ...tion modes 0b00000000 none fan key is locked and the fan symbol will not be displayed 0bxxxx0001 single stage 0bxxxx0010 2 stages 0bxxxx0011 3 stages 0bxxxx1000 EC Fan 0b0001xxxx fan works not in heat...

Страница 11: ...Occupied 2 Occupancy sensor Closed Occupied 3 Window contact Open Window Open 4 Window contact Closed Window Open 5 Disable heating Open Heating disabled 6 Disable heating Closed Heating Disabled 7 D...

Страница 12: ...nnel A period 1 Start time minute 0 59m min 0 406 0x0196 Read write Time channel A period 1 Set point 0 500 0 50 0 C 0 1 C F 210 407 0x0197 Read write Time channel A period 1 ECO mode 0b00000001 Comfo...

Страница 13: ...ute 0 59m min 0 431 0x01AF Read write Time channel B period 3 Set point 0 500 0 50 0 C 0 1 C F 210 432 0x01B0 Read write Time channel B period 3 ECO mode NC 0 433 0x01B1 Read write Time channel B peri...

Страница 14: ...0bxABC1234 with binary value 1 for active channel i e 0x01000100 A 2 0 464 0x01D0 Read write Make next day s holiday 0bxxx00000 None 0bxxx00001 0bxxx11111 days of holidays next n days starting next 0...

Страница 15: ...0 ventilating PI loop controls fan stages only valves closed HMI mode 0b1xxx xxxx HMI Mode controller OFF 0b1xxx xx01 show symbol ventilating 0b1xxx xx10 show symbol heating 0b1xxx xx11 show symbol co...