Issue Date: 22.01.2020

  

 

Page 7 / 15 

 

 

 

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Deutschland · tel: 02778/6960-0 · fax: -400 · 

www.thermokon.de

 · 

[email protected]

 

LCF02-Touch_3AO2DO_Datasheet_en.docx   © 2020 

The analog 0..10 V output for the EC fan in automatic mode outputs the voltage value according to the control value of the controller. For manual 

switching, the following voltage values apply to the EC output: 

Fan stage 

Voltage 

Parameter 

OFF 

0V 

 

(Speed level 1) LOW  

3,5 V 

Reg. 0x128,  default = 35 

(Speed level 2) Medium  

7 V 

Reg. 0x129,  default = 70 

(Speed level 3) High  

10 V 

 

°F/°C selective 

Temp display range is 32 °F..99 °F, respectively 0 °C..50 °C (factory default is °C). 

Temperature offset correction 

(Register address 0x0106)

 

The internal sensor will be affected by the Thermostat’s self-heating. As a consequence it would display a higher room temperature than the 

average of indoor temperature (real value). Item 5 & 6 of the parameter table does contain the correction of temperature offset (resolution 0,1 °C). 

Set the Temperature set point range 

(Register address 0x0110 – 0x0112)

 

Press 

“▲”or “▼” key

 to adjust the temperature set point range. Factory default (°C) is 16 °C..30 °C

When °F has been selected Temp range is 

60 °F..86 °F. 

Key lock selection 

(Register address 0x010D)

 

If a key is pressed that is locked, the lock symbol 

 will appear for 2s and blink 2x but no further action is taken. 

Power failure – Restart selection 

(Register address 0x010C)

 

On the LCD, there are three symbols 

   

   

 that define how the thermostat will restart after a power failure:  

 Keep thermostat switched OFF  

 Switch thermostat to last state before power failure (Record and Memorize) 

 Turn the thermostat ON  

Storage during power loss 

The status will be kept in EEPROM, while the power failure, so no data will be lost.  

The setpoint is not saved. The standard setpoint after power-on reset applies, register address 271 (0x010F). 

 

Occupancy (OCC) 

If the input is configured for an Occupancy sensor. If the sensor indicates “UnOccupied” the current setpoint will be replaced by the Eco Mode 

Setpoint Temp. The display will show the leaf symbol and the lettering ECO to indicate the ECO mode. Once the room occupancy is detected 

again the previously used Setpoint will be restored and the leaf symbol will not be showing any more.  

Window contact (ESI)  

If the input is configured as window contact, the “Window open” Symbol will be displayed the thermostat will check every 3 seconds the input 

whether active. The cooling valve will be closed as long as the input will be active. The rest of the thermostat will work as usual, the user may 

change the setpoint or the fan stage, but the valve outputs will remain in valve closed position. If configured the “Window open” 

or the Dew 

Point symbol 

  will be flashing. When the input will not be active, the thermostat’s outputs return to normal operation and operates the outputs 

normally. 

Sensor failure alarm 

In case the room NTC temp sensor is open or short, thermostat switches fan to medium and the valve to 50% (5V output, 50%). The display will 

show (blinking) error code: “E1” Thermostat will allow to control fan manually as well as the valve output using the “▲”or “▼

” keys. Every operation 

of the “▲”or “▼” key

s will decrement / increment the output voltage by 1V = 10%  AND the PWM by 10%. The percentage is shown in the display.  

 

 

Содержание LCF02 Touch 3AO2DO

Страница 1: ...should only be used for the intended application Unauthorised modifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly...

Страница 2: ...ture acceptance of the wall or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are TECHNICAL DATA Measuring values temperature Output v...

Страница 3: ...voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected with each other and all negative operating voltage input terminals reference...

Страница 4: ...22 Heating valve 29 Off delay active 2 Schedular 9 Fan coil type 16 Set fan speed 23 Valve opening 30 Key locked 3 Room temperature 10 Auto mode 17 Power ON OFF 24 Dew point 31 Eco Mode active 4 Setp...

Страница 5: ...ID 247 1 2 Baud rate 1 4800bps 2 9600 3 19200 4 38400 2 3 Parity 0 none 1 odd 2 even 0 4 Stop Bits 1 1 Stopbit 2 2 Stopbits 2 5 Temperature Offset Internal Sensor 5 0 K 5 0 K 0 6 Temperature Offset E...

Страница 6: ...114 The display will show the average of both ECO Setpoint Temperatures 25 18 2 21 5 and the leaf symbol to indicate the ECO mode In ECO mode the setpoint is fixed and the device does not react to any...

Страница 7: ...switched OFF Switch thermostat to last state before power failure Record and Memorize Turn the thermostat ON Storage during power loss The status will be kept in EEPROM while the power failure so no...

Страница 8: ...ture sensor alarm 0x02 external temperature sensor high limit Alarm 0x04 external temperature sensor low limit Alarm 0x08 change over sensor missing alarm 10 0x000A Read only External input 1 0 Contac...

Страница 9: ...symbol shall be displayed and blink twice 0 270 0x010E Read write Display Settings 0b00000001 show Setpoint if no setpoint is shown the setpoint keys are locked 0x010D 0x10 lock temp setting 0b000000...

Страница 10: ...tion modes 0b00000000 none fan key is locked and the fan symbol will not be displayed 0bxxxx0001 single stage 0bxxxx0010 2 stages 0bxxxx0011 3 stages 0bxxxx1000 EC Fan 0b0001xxxx fan works not in heat...

Страница 11: ...Occupied 2 Occupancy sensor Closed Occupied 3 Window contact Open Window Open 4 Window contact Closed Window Open 5 Disable heating Open Heating disabled 6 Disable heating Closed Heating Disabled 7 D...

Страница 12: ...nnel A period 1 Start time minute 0 59m min 0 406 0x0196 Read write Time channel A period 1 Set point 0 500 0 50 0 C 0 1 C F 210 407 0x0197 Read write Time channel A period 1 ECO mode 0b00000001 Comfo...

Страница 13: ...ute 0 59m min 0 431 0x01AF Read write Time channel B period 3 Set point 0 500 0 50 0 C 0 1 C F 210 432 0x01B0 Read write Time channel B period 3 ECO mode NC 0 433 0x01B1 Read write Time channel B peri...

Страница 14: ...0bxABC1234 with binary value 1 for active channel i e 0x01000100 A 2 0 464 0x01D0 Read write Make next day s holiday 0bxxx00000 None 0bxxx00001 0bxxx11111 days of holidays next n days starting next 0...

Страница 15: ...0 ventilating PI loop controls fan stages only valves closed HMI mode 0b1xxx xxxx HMI Mode controller OFF 0b1xxx xx01 show symbol ventilating 0b1xxx xx10 show symbol heating 0b1xxx xx11 show symbol co...