445 

0x01BD 

Read-write

 

Time channel C period 2: ECO mode 

0b00000001=Comfort 

0b00010001=ECO

 

 

NC 

446 

0x01BE 

Read-write

 

Time channel C period 3: Start time hour 

0 – 23h

 

 

447 

0x01BF 

Read-write

 

Time channel C period 3: Start time minute 

0 – 59m

 

 

min  

448 

0x01C0 

Read-write

 

Time channel C period 3: Set point 

0..500 = 0..+50,0 °C

 

0.1 

°C/°F 

210 

449 

0x01C1 

Read-write

 

Time channel C period 3: ECO mode 

0b00000001=Comfort 

0b00010001=ECO

 

 

NC 

450 

0x01C2 

Read-write

 

Time channel C period 4: Start time hour 

0 – 23h

 

 

451 

0x01C3 

Read-write

 

Time channel C period 4: Start time minute 

0 – 59m

 

 

min  

452 

0x01C4 

Read-write

 

Time channel C period 4: Set point 

0..500 = 0..+50,0 °C

 

0.1 

°C/°F 

210 

453 

0x01C5 

Read-write

 

Time channel C period 4: ECO mode 

0b00000001=Comfort 

0b00010001=ECO

 

 

 

454 

0x01C6 

Read-write

 

Active Time Channel 

0bxABC1234 with binary value = 1 for active channel, 

i.e. 0x01000100 = A-2

 

 

 

464 

0x01D0 

Read-write

 

Make next day(s) holiday 

0bxxx00000= None 

0bxxx00001 …0bxxx11111 days of holidays (next n-

days (starting next 0:00) forces the coming 1...31 days 

to be treated as the day specified by the 3 MSB. Does 

overwrite the calender. 

0b000xxxxx = use ECO setting 

0b001xxxxx = set day = Mo 

0b010xxxxx =  set day = Tu 

0b011xxxxx =  set day = Wed 

0b100xxxxx =  set day = Thu 

0b101xxxxx = set day = Fr 

0b110xxxxx = set day = Sat 

0b111xxxxx = set day = Sun

 

 

 

 

Realtime Clock 

Address 

Access  Description 

Resolution / Unit 

Default 

496 

0x01F0 

Read-write 

system time—year 

2000-2099

default=2019

 

 

 

2019 

497 

0x01F1 

Read-write 

system time—month 

01-12

 

 

 

498 

0x01F2 

Read-write 

system time—day 

01-31

 

 

 

499 

0x01F3 

Read-write 

system time-hour 

00-23

 

 

 

500 

0x01F4 

Read-write 

system time-minutes 

00-59

 

 

 

501 

0x01F5 

Read-write 

system time—seconds 

00-59

 

 

 

 

Holding Register (operation to override FC from Modbus) 

Address 

Access  Description 

Resolution / Unit 

Default 

512 

0x0200 

Read-write 

Active fan speed setting 

0b00000000 = OFF 

0b00000001 = Stage Low 

0b00000010 = Stage Medium 

0b00000100 = Stage High 

0b00001000 = Auto OFF 

0b00001001 = Auto Low 

0b00001010 = Auto Medium 

0b00001100 = Auto High  

 

 

Содержание LCF02 Touch 3AO2DO

Страница 1: ...should only be used for the intended application Unauthorised modifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly...

Страница 2: ...ture acceptance of the wall or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are TECHNICAL DATA Measuring values temperature Output v...

Страница 3: ...voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected with each other and all negative operating voltage input terminals reference...

Страница 4: ...22 Heating valve 29 Off delay active 2 Schedular 9 Fan coil type 16 Set fan speed 23 Valve opening 30 Key locked 3 Room temperature 10 Auto mode 17 Power ON OFF 24 Dew point 31 Eco Mode active 4 Setp...

Страница 5: ...ID 247 1 2 Baud rate 1 4800bps 2 9600 3 19200 4 38400 2 3 Parity 0 none 1 odd 2 even 0 4 Stop Bits 1 1 Stopbit 2 2 Stopbits 2 5 Temperature Offset Internal Sensor 5 0 K 5 0 K 0 6 Temperature Offset E...

Страница 6: ...114 The display will show the average of both ECO Setpoint Temperatures 25 18 2 21 5 and the leaf symbol to indicate the ECO mode In ECO mode the setpoint is fixed and the device does not react to any...

Страница 7: ...switched OFF Switch thermostat to last state before power failure Record and Memorize Turn the thermostat ON Storage during power loss The status will be kept in EEPROM while the power failure so no...

Страница 8: ...ture sensor alarm 0x02 external temperature sensor high limit Alarm 0x04 external temperature sensor low limit Alarm 0x08 change over sensor missing alarm 10 0x000A Read only External input 1 0 Contac...

Страница 9: ...symbol shall be displayed and blink twice 0 270 0x010E Read write Display Settings 0b00000001 show Setpoint if no setpoint is shown the setpoint keys are locked 0x010D 0x10 lock temp setting 0b000000...

Страница 10: ...tion modes 0b00000000 none fan key is locked and the fan symbol will not be displayed 0bxxxx0001 single stage 0bxxxx0010 2 stages 0bxxxx0011 3 stages 0bxxxx1000 EC Fan 0b0001xxxx fan works not in heat...

Страница 11: ...Occupied 2 Occupancy sensor Closed Occupied 3 Window contact Open Window Open 4 Window contact Closed Window Open 5 Disable heating Open Heating disabled 6 Disable heating Closed Heating Disabled 7 D...

Страница 12: ...nnel A period 1 Start time minute 0 59m min 0 406 0x0196 Read write Time channel A period 1 Set point 0 500 0 50 0 C 0 1 C F 210 407 0x0197 Read write Time channel A period 1 ECO mode 0b00000001 Comfo...

Страница 13: ...ute 0 59m min 0 431 0x01AF Read write Time channel B period 3 Set point 0 500 0 50 0 C 0 1 C F 210 432 0x01B0 Read write Time channel B period 3 ECO mode NC 0 433 0x01B1 Read write Time channel B peri...

Страница 14: ...0bxABC1234 with binary value 1 for active channel i e 0x01000100 A 2 0 464 0x01D0 Read write Make next day s holiday 0bxxx00000 None 0bxxx00001 0bxxx11111 days of holidays next n days starting next 0...

Страница 15: ...0 ventilating PI loop controls fan stages only valves closed HMI mode 0b1xxx xxxx HMI Mode controller OFF 0b1xxx xx01 show symbol ventilating 0b1xxx xx10 show symbol heating 0b1xxx xx11 show symbol co...

Отзывы: