Operating mode 

Press the “Mode Key” 

, to adjust the mode cyclically (Cooling > Ventilating > Auto mode > Heating …). 

In 2-pipe configuration not available modes (depending on the change-over sensor’s signal) will be skipped. In this case the user can select the 

available modes only. 

Standby / ECO / ON 

The Power-Button switches the device from Stand-by to ON. In Standby the display is off, but the control loop is actively monitoring the 

temperature and will activate the heating output if the room temperature drops below the frost protection threshold.  
In case the external sensor is configured as a temperature limiter, the heating valve will be closed in case the threshold value will be exceeded. 

Besides the frost protection the device shall monitor a high limit as well in case the external sensor input is configured as a temperature limiter. 

This is the case for floor heating systems, where the external sensor is embedded in the floor. In case the floor temperature will exceed a certain 

threshold the heating valve shall be closed to avoid damaging the floor or the pipes embedded in the floor. 
Pressing the button once switches the display on and the device to ECO mode. In ECO mode it controls the room temperature to the setpoint 

predefined by register 275 and 276 (0x0113, 0x0114). The display will show the average of both ECO Setpoint Temperatures (25+18 /2=

21,5

) and 

the leaf symbol to indicate the ECO mode. In ECO mode the setpoint is fixed and the device does not react to any button pressed by the user 

besides pressing the Stand-by /ECO/ON  button a 2nd time. Then it will switch from ECO to comfort mode. To indicate that the Fancoil thermostat 

is in ECO mode it will show the leaf and the word ECO in the display.  
In case an occupancy sensor is connected to one of the inputs the mode will change from ECO to Comfort as soon as the input becomes active 

and the previously used Setpoint will be restored and the leaf symbol will not be showing any more. 

Temperature sensor input – temperature limiter and external sensor 

The temperature sensor input (address 0x0152) can be used as change over sensor (addresses 0x012B and 0x012C) or as external temperature 

sensor.  
Furthermore, it can also be used to limit the heating temperature (address 0x010A) and cooling temperature (address 0x010B). This is the case 

for floor heating systems, where the external sensor is embedded in the floor. In case the floor temperature will exceed a certain threshold the 

heating valve shall be closed to avoid damaging the floor or the pipes embedded in the floor. 

Fan control 

If the fan is configured to be 1-stage or 2-stage the selection will be adapted accordingly. In „ventilating mode“, the valves will be closed. If the fan 

speed 

 is set to Auto the steps are switched depending on the temperature difference between the setpoint value and the current temperature 

value. 

In auto mode heating or cooling, the fan level is calculated from the output of the PI loop (control variable). 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание LCF02 Touch 3AO2DO

Страница 1: ...should only be used for the intended application Unauthorised modifications are prohibited The product must not be used in relation with any equipment that in case of a failure may threaten directly...

Страница 2: ...ture acceptance of the wall or the longer the selected inquiry interval of the temperature sensor is the smaller the deviations limited in time are TECHNICAL DATA Measuring values temperature Output v...

Страница 3: ...voltage supply it is to be ensured that all positive operating voltage input terminals of the field devices are connected with each other and all negative operating voltage input terminals reference...

Страница 4: ...22 Heating valve 29 Off delay active 2 Schedular 9 Fan coil type 16 Set fan speed 23 Valve opening 30 Key locked 3 Room temperature 10 Auto mode 17 Power ON OFF 24 Dew point 31 Eco Mode active 4 Setp...

Страница 5: ...ID 247 1 2 Baud rate 1 4800bps 2 9600 3 19200 4 38400 2 3 Parity 0 none 1 odd 2 even 0 4 Stop Bits 1 1 Stopbit 2 2 Stopbits 2 5 Temperature Offset Internal Sensor 5 0 K 5 0 K 0 6 Temperature Offset E...

Страница 6: ...114 The display will show the average of both ECO Setpoint Temperatures 25 18 2 21 5 and the leaf symbol to indicate the ECO mode In ECO mode the setpoint is fixed and the device does not react to any...

Страница 7: ...switched OFF Switch thermostat to last state before power failure Record and Memorize Turn the thermostat ON Storage during power loss The status will be kept in EEPROM while the power failure so no...

Страница 8: ...ture sensor alarm 0x02 external temperature sensor high limit Alarm 0x04 external temperature sensor low limit Alarm 0x08 change over sensor missing alarm 10 0x000A Read only External input 1 0 Contac...

Страница 9: ...symbol shall be displayed and blink twice 0 270 0x010E Read write Display Settings 0b00000001 show Setpoint if no setpoint is shown the setpoint keys are locked 0x010D 0x10 lock temp setting 0b000000...

Страница 10: ...tion modes 0b00000000 none fan key is locked and the fan symbol will not be displayed 0bxxxx0001 single stage 0bxxxx0010 2 stages 0bxxxx0011 3 stages 0bxxxx1000 EC Fan 0b0001xxxx fan works not in heat...

Страница 11: ...Occupied 2 Occupancy sensor Closed Occupied 3 Window contact Open Window Open 4 Window contact Closed Window Open 5 Disable heating Open Heating disabled 6 Disable heating Closed Heating Disabled 7 D...

Страница 12: ...nnel A period 1 Start time minute 0 59m min 0 406 0x0196 Read write Time channel A period 1 Set point 0 500 0 50 0 C 0 1 C F 210 407 0x0197 Read write Time channel A period 1 ECO mode 0b00000001 Comfo...

Страница 13: ...ute 0 59m min 0 431 0x01AF Read write Time channel B period 3 Set point 0 500 0 50 0 C 0 1 C F 210 432 0x01B0 Read write Time channel B period 3 ECO mode NC 0 433 0x01B1 Read write Time channel B peri...

Страница 14: ...0bxABC1234 with binary value 1 for active channel i e 0x01000100 A 2 0 464 0x01D0 Read write Make next day s holiday 0bxxx00000 None 0bxxx00001 0bxxx11111 days of holidays next n days starting next 0...

Страница 15: ...0 ventilating PI loop controls fan stages only valves closed HMI mode 0b1xxx xxxx HMI Mode controller OFF 0b1xxx xx01 show symbol ventilating 0b1xxx xx10 show symbol heating 0b1xxx xx11 show symbol co...

Отзывы: