PELLING ECO
45
10
Troubleshooting
If faults occur in the heating system, it is possible to fix some of them by
following these instructions.
Displayanzeige
(deutsch)
Display
(english)
Error
description
Solution
F01 Pell
E01 Pell
No pellet or STB
1.
Fill pellet tank
2.
STB deactivate
F02 Zund
E02 Igni
Not fire on
1.
Check quality of pellet
2.
Check pellet in pellet tank
3.
Check pellet burner pot
sits corect
4.
Clean burning pot
5.
Check that igniter works
6.
Call service
F03 Tuer
E03 door
Door open
1.
Close door
F04 Temp
E04 Temp
High temperature
1.
Burning pot crowded
2.
Boiler is dirty- clean boiler
F05 Saug
E05 Fan
Exhaust fan error
HALL sensor error
STB is activated
1.
Exhaust fan error
2.
The bolier temperature
exceded over 90°C . Wait to
cool down and reset STB
F06 Flam
E06 Flam
Flame sensor error
1.
Check contacts
F07 Raum
E07 Room
Room Temperature
Sensor error (only
Minitherm air)
1.
1. Check contacts
Содержание PELLING 25 ECO
Страница 2: ...2...
Страница 15: ...PELLING ECO 15 4 2 Technical data...
Страница 18: ...PELLING ECO 18...
Страница 19: ...PELLING ECO 19...
Страница 20: ...PELLING ECO 20...
Страница 38: ...PELLING ECO 38 7 4 Hidraulic connection diagrams...
Страница 39: ...PELLING ECO 39...
Страница 40: ...PELLING ECO 40...
Страница 43: ...PELLING ECO 43...
Страница 56: ...PELLING ECO 56...
Страница 57: ...PELLING ECO 57...