Thermocet Hi-Fire Ligero Скачать руководство пользователя страница 20

Page 20 

10.  

Maintenance activities.

 

 

Please note: turn off the gas supply and power supply as much as possible during maintenance activities. Maintenance 
activities should be performed by a qualified fitter. Close the gas valve while maintenance activities are being performed

  

 

Inspect

  

 

 Work activities

 

 

OK 

1   General inspection

 

 

a   The main burner should ignite smoothly (within several seconds) and not give a bang sound due to 

delayed ignition. Go to number 7 if there appears to be delayed ignition.

 

 

 

   

b   Check the flame image. No flames against the glass. The flame image should be stable (See page 22 

item 12.7). The flame should be yellow after approximately 15 minutes; go to number 7 if the flame 
image is blue.

 

 

 

   

c   Check for excessive formation of soot on the inside of the glass/combustion chamber and on decorative 

parts. Go to number 7 if there is excessive formation of soot.

 

 

 

   

   

 

2   Door/front

 

 

a   check for obstructions in the convection air openings

 

 

 

   

   

 

3   Glass window, seal.

 

  a  check the glass window for cracks etc. Replace if damaged, cracked, or broken.

 

 

 

   

b   check the seal of the glass window; this needs to join the unit and glass window. Replace if required.

 

    

   

c   check any hinges, seals, quadrants etc.

 

 

 

   

d   clean the glass. Check there is an even (not too large) load on the glass window. Prevent point load. 

 

   

   

 

4   Gas control compart-

ment and convection 
part of the unit

 

 

a   clean these areas with a vacuum cleaner. Do so carefully. Remove parts that do not belong here.

 

 

 

   

b   check if the convection airflow is free.

 

 

   

   

 

5   Decorative parts (logs/

pebbles etc.)

 

and 

(pilot)burner

 

 

a   remove decorative parts and clean the burner (be careful with ceramic burners!) with a vacuum cleaner.

 

 

 

    

b   inspect decorative parts for damage/cracks/discolouration and clean with a soft brush if required

 

 

 

   

c   check if the burner cover is intact and free of corrosion. Replace the burner if required.

 

 

 

   

d   after completing the inspection: replace decorative parts, exactly as stipulated by the manufacturer. 

Ensure the pilot burner is kept free!

 

 

 

   

e   check if the pilot flame protection is intact (if applicable).

 

 

 

   

f   check the piezo for sufficient spark power, and ensure the ignition cable is free from metal parts/

electrical parts.

 

 

 

   

   

 

6   Combustion chamber

 

  a   check the condition of the finishing, such as varnish and enamel. Check for corrosion. Repair if 

required.

 

 

 

   

b   replace the unit if there are holes. Close the unit for further use

.

 

 

   

c   check overpressure hatches or overpressure construction for sealing and sufficient movement/deposits.

 

  

   

   

 

7   Ignition and operation 

of the main burner

 

 

a   remove the burner from the unit and check whether the main injector is dirt-free. 

 

   

b   check if the primary ventilation opening in the main burner is dirt-free.

 

 

 

   

c   mount the burner and check if the burner is in a good position in relation to the pilot burner.

 

  

 

   

d  check if the burner is fixed and cannot move.

 

 

 

   

e  check if the pilot burner burns well, with a blue flame (blue only)

 

 

 

   

f   check if the burner ignites uniformly across the entire surface and without significant delay.

 

 

 

   

g  check if the flame image is uniform and stable (manufacturer’s description).

 

 

 

   

h   check the initial and burner pressure. Do not forget to close the pressure measuring points.

 

 

 

   

i   check if gas control parts are intact, and that plastic parts have not melted, for example. 

 

   

j   check electrical wiring for damage and ensure they are away from hot parts of the unit. 

 

   

   

 

8   Installation 

a   check if convection grates are dust-free and dirt-free 

 

   

b   check if there is sufficient distance between the unit and flammable furniture 

 

   

   

 

9   Flue tube/air supply

 

  a   where possible, inspect the general state of the exhaust/supply system and check for blockages / leaks / 

corrosion. 

 

   

b   check the outlet, which should be free from dirt and blockages. 

 

   

c   specifically check for leaking of cement borders etc. 

 

   

   

 

10  Remote control

 

 

a  check for correct functioning of the remote control.

 

 

 

   

   

 

11  Ventilators (if present)

 

 a   clean the convection ventilators and check for correct functioning.

 

 

 

Содержание Hi-Fire Ligero

Страница 1: ...Page 1 OPERATING AND INSTALLATION INSTRUCTIONS HI FIRE COLLECTION BASE UNIT GREAT BRITTAN GB IRELAND IE...

Страница 2: ...nstallation instructions regarding existing flues 7 4 Parts 7 5 Installation 7 6 Cleaning and maintenance 8 Instructions for the Mertik Maxitrol GV60 and the Remote Control Page 16 9 Maintenance check...

Страница 3: ...ll and or some smoke to be emitted Any deposit on the heat resistant glass should be removed immediately using a fireplace cleaner suitable for heat resistant glass Attention The unit must be installe...

Страница 4: ...the unit continues to operate safely For additional instructions see Chapter 3 Maintenance If for whatever reason the pilot light extinguishes you must wait 5 minutes before igniting the pilot light...

Страница 5: ...ait a moment or press OFF to return to MAN mode 3 5 Setting the desired temperature Press the SET key briefly to select the required mode or Keep the SET key pressed in until the screen starts flashin...

Страница 6: ...n Simultaneously push the keys OFF and on the manual transmitter A short sound signal will confirm commencement Short sound signals will then follow until the pilot flame and main burner are ignited A...

Страница 7: ...d by Flat batteries replace the batteries An electronic problem can be solved by pressing the RESET key on the receiver Contact your fitter if the unit regularly turns off 3 12 Replacing the batteries...

Страница 8: ...wn for another 10 seconds and then let go Important If the pilot light extinguishes one should wait at least 5 minutes before repeating the aforementioned steps Turn the operating button to the ON pos...

Страница 9: ...d fireplaces Prevent discolouration of walls and ceilings There are always particles in the air in each living area even if the area is vacuum cleaned regularly These particles are easily visible when...

Страница 10: ...cal information for the relevant country needs to be consulted and modifications discussed with the manufacturer There will be air in the gas pipes when the unit is first used The gas pipes therefore...

Страница 11: ...ength The outlet can be installed at any point on the roof face or exterior wall supply and discharge in an identical pressure area but must meet applicable regulations Duct pathways may not be insula...

Страница 12: ...king any hindrance to the surrounding area into consideration according to national regional local standards and regulations Ensure wind pressure on the flue terminal is not too extreme such as a balc...

Страница 13: ...between rooms See national regional local standards and regulations A casing made of fireproof material e g 12 mm Promatect fire resistant plate must be used at 25mm from the outside duct Determine th...

Страница 14: ...90 to 165 8 Existing brickwork duct 9 Mounting plate on the roof square 300 10 Clamping strip supplied with 11 11 Roof pass through Note The renovation sanitation set consists of parts 3 4 5 7 and 9...

Страница 15: ...Page 15 A B...

Страница 16: ...erformed at a later date This may be more difficult if the control is installed using a method that is different from the instructions provided here Please note Only place the batteries after wiring t...

Страница 17: ...ton using a blunt object See photograph 3 Continue to press this button until you hear a short beeping sound followed immediately by a long beeping signal Release the button Direct the manual transmit...

Страница 18: ...Page 18...

Страница 19: ...Name Address Unit serial number Date of purchase Installation date Comments 9 0 MAINTENANCE CHECK UP LIJST Fitter details Service date Performed by Work activities performed Service and maintenance l...

Страница 20: ...he inspection replace decorative parts exactly as stipulated by the manufacturer Ensure the pilot burner is kept free e check if the pilot flame protection is intact if applicable f check the piezo fo...

Страница 21: ...quipment 11 3 Placing ceramic wood blocks See page 28 Please note You need to check if a restriction plate needs to be mounted before the wood blocks are placed See page 22 Remove the gas clamps hold...

Страница 22: ...e vertically on the unit Next continue building up the flue pipe using two 45 bends the calculation length for each bend is 1 metre until you have reached the maximum pipe length of 12 metres includin...

Страница 23: ...H I2E I2E I2L I3B P I3B P I3B P I3P I3P I3P PRIMAIRE AIR INLET 2 x 6 5 2 x 4 4 3 x 13 3 x 13 3 x 13 2 x 13 1 x 5 2 x 13 1 x 5 2 x 13 1 x 5 PRE PRESSURE mBAR 20 Mbar 25 Mbar 28 30 Mbar 30 Mbar 50 Mbar...

Страница 24: ...cannot be adjusted there may be an obstruction in the pilot 2 Check whether the thermocouple interrupter is connected to the gas valve prop erly 3 Check that the gas valve is not faulty 4 Check whethe...

Страница 25: ...Page 25 1...

Страница 26: ...Page 26 1 2 1 7 1 6 1 5 1 4 1 3...

Страница 27: ...Page 27 A E B C D F I H G K L J M N O...

Страница 28: ...Page 28 E D C B A...

Страница 29: ...Page 29...

Страница 30: ...Page 30 3 1 G 2 G 1 H I P O P O 2...

Страница 31: ...Page 31...

Страница 32: ...Pag 32 TTI d o o Thermo Technology International...

Отзывы: