Operation - UT150 Controller
Programming Operation: Entering a Program
6-10
Thermo Scientific
setpoint value with arrow button then press and release the "SET/ENT" button
twice to enter this value and to advance to the "tM1" display. If the value for
"SP1" is correct and will not be changed, press and release the “SET/ENT”
button once to advance to the "tM1” display.
4. The next parameter, "tM1", represents the first time period for the unit to reach
the target temperature setpoint selected in "SP1".This selection can be a value
ranging from 0.00 to 99.59, which represents hours and minutes. Select this
time value with the arrow buttons and enter it by pressing and releasing the
"SET/ENT" button twice.
5. Press and release the "SET/ENT" button to advance to the next display of
"SP2", this is considered the dwell segment. Select the same target setpoint
temperature value as "SP1" with the arrow buttons. Press and release the
"SET/ENT" button twice to enter this value and to advance to next display.
6. The next parameter, "tM2", represents the second time period used to maintain
or dwell at the target setpoint selected in "SP2". This selection can be a value
ranging from 0.00 to 99.59, which represents hours and enter it by pressing
and releasing the "SET/ENT" button twice.
7. Next, "SP3" is the third setpoint value desires in the chamber. Select this target
temperature setpoint with the arrow buttons and press and release the
"SET/ENT" button twice to enter this value and release the "SET/ENT" button
twice to enter this value and advance to the "tM3" display. If this value is
correct and not changed, press and release the "SET/ENT" button once to
advance to the "tM3" display.
8. "tM3" represents the third time period for the unit to reach the target setpoint
selected in "SP3". This selection can be a value ranging from 0.00 to 99.59,
which represents hours and minutes. Select this value with the arrow buttons
and enter it by pressing and releasing the "SET/ENT" button.
9. The next parameter, "SP4" is considered the dwell segment. Select the same
target temperature as "SP3" with the arrow buttons, then press and release the
"SET/ENT" buttons twice to enter this new value and to advance to next
display.
Additional Program Parameters"
10. The next parameter, "SP4" is normally the dwell segment. Select the same
target temperature as "SP3" with the arrow buttons, then press and release the
"SET/ENT" button twice to enter this new value and to advance to next display.
This operation ends the offer use of setpoint and time parameters.
11. The next display shows "EV1" in the upper display. The lower value should
always be "0" (zero). Press and release the "SET/ENT" button once to go to
next display.
12. “AL1” should always have a lower value "9". Press and release the "SET/ENT"
button once to advance to the next display.
Содержание CC58114PBC
Страница 1: ......
Страница 6: ...List of Figures ii Thermo Scientific ...
Страница 12: ...Introduction 2 2 Thermo Scientific ...
Страница 14: ...Unpacking 3 2 Thermo Scientific ...
Страница 20: ...Installation Thermocouple Wiring Installation 4 6 Thermo Scientific ...
Страница 22: ...Initial Start up 5 2 Heratherm Thermo Scientific ...
Страница 46: ...Communication Option Addresses for Multiple Controllers 7 6 Thermo Scientific ...
Страница 50: ...Excess Temperature Option Excess Temperature Controller Operation 8 4 Thermo Scientific ...
Страница 57: ...Replacement Parts Thermo Scientific Heratherm 11 3 Figure 5 Wiring Diagram ...
Страница 58: ...Replacement Parts 11 4 Heratherm Thermo Scientific ...
Страница 59: ...Thermo Scientific 12 1 12 Error Codes This chapter is not applicable ...
Страница 60: ...Error Codes 12 2 Thermo Scientific ...
Страница 62: ...WEEE Compliance 13 2 Thermo Scientific ...
Страница 63: ...Thermo Scientific 14 1 14 14 Spare Parts and Accessories This chapter is not applicable ...
Страница 64: ...Spare Parts and Accessories 14 2 Thermo Scientific ...
Страница 66: ...Device Log 15 2 Thermo Scientific ...