AutoMITTER SIB Option
CSA Certified Systems
Thermo Fisher Scientific
AutoPILOT PRO Flow Computer User Guide 6-3
Read the following warnings before making any connections.
Warning
Do not install the system in any hazardous area, except in those
for which the system has been approved.
Warning
Do not make any connections unless the area is known to be
non-hazardous. Once connections are made, do not disconnect unless
power has been removed and the area is known to be non-hazardous.
Warning
Do not connect power to TB4 until all other connections are
made.
Warning
Substitution of components may impair suitability for Class I,
Div. 2.
Warning
Use wires suitable for at least 90°C.
Warning
Service connections can only be used in safe atmospheres.
1.
Open the enclosure door. Loosen the thumbscrews on the mounting
bracket, and lift the main board and mounting bracket to expose the
chassis bracket.
2.
Mount the SIB onto the flow computer chassis bracket using the
standoffs provided. See the figure below for assembly orientation and
mounting location.
Installation