background image

 

  3 

 

The entire text of these instructions must be read and understood, before 
installing the appliance. It is the installer's responsibility to do the following: 

 
1.  Inform and demonstrate to the user, the correct operation and maintenance of the appliance, as 

explained in the 

Homeowner/User Information and Routine Maintenance

 section of this manual.  

 
2.  Inform the user of the hazards of flammable liquids and vapors and to remove such liquids and 

vapors from the vicinity of the appliance. 

 
3.  Inform the user of all pertinent warnings and precautions concerning this appliance. 
 

 

 

WARNING: This unit is not to be used for temporary heating of buildings, or structures, under 
construction. 

Construction dust may enter the appliance or the duct system and cause a fire hazard.

 

Certain chemicals used during construction when burned, form corrosive condensate that can 
substantially reduce the life of the heating system heat exchanger.

 

 
This appliance is shipped completely assembled and internally wired. All electrical wiring has been factory 
installed and inspected. At the time of installation, the unit will require connection to electric power, fuel oil 
supply, and supply and return air ductwork.   
 
This  unit  uses  a  fan-assisted  combustion  system,  consisting  of  a  pressure  atomizing,  oil  burner  and 
combustion  air  blower,  used  to  push  the  products  of  combustion  through  the  heat  exchanger  system.  
After installation, the furnace and duct system must be adjusted to obtain a temperature rise of 56°- 81°F 
through  the  unit.  (Refer  to  the  rating  label  located  on  side  panel  inside  the  burner  compartment).  The 
installation  must  conform  with  local  codes  or,  in  the  absence  of  local  codes,  with  the  Standard  for  the 
Installation of Oil-Burning Equipment, NFPA 31-1997, or the latest edition, and to these instructions.  The 
installation must also comply with CSA B139 for recommended installation practices where applicable. 

 

A. CODES AND CLEARANCES: 

 

The following items must be considered when choosing the size and location of the unit. 

 
1. 

All local codes and/or regulations take precedence over the instructions in this manual and 
should be followed accordingly.

 In the absence of local codes, installation must conform to these 

instructions and the guidelines of the National Fire Protection Association (NFPA). Two applicable 
NFPA installation codes are the National Electrical Code, ANSI/NFPA 70-1999, and Standard for the 
Installation of Oil-Burning Equipment, NFPA 31-1997. The latest editions of these codes should be 
consulted. 

 
2. The selection of a heating unit should be based on a rate of heat loss calculation for the residence 

according to the manuals provided by the Air Conditioning Contractors of America (ACCA) or the 
American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE). The heating 
capacity of the unit proposed for installation should meet or slightly exceed the rate of heat loss for the 
residence.  Over sizing should not exceed 25% of the heat loss calculation. 

 
3.  When installed, this unit should be level. If possible, it should be installed in a central location, with 

respect to outlet registers of the supply air ductwork. 

 
4.  Definitions of "combustible" and "non-combustible" materials as presented in the 1996 version of the 

National Fuel Gas Code, ANSI Z223.1-1996/NFPA 70-1996, are as follows: 

 
 

a. 

Combustible material:

 

“...materials made of or surfaced with wood, compressed paper, plant fibers, or 
other materials that are capable of being ignited and burned. Such materials 
shall be considered combustible even though flame proofed, fire-retardant 
treated, or plastered.” 

 
 

Содержание THV1M119A960SA

Страница 1: ...AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE c WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASS...

Страница 2: ......

Страница 3: ...ANK AND PIPING 16 FILTER 16 J ELECTRICAL WIRIING 16 K BLOWER SETUP 18 L BLOWER CONTROLLER INFORMATION FOR PSC AND CTM MOTOR 21 M STARTUP PROCEDURES 26 III USERS INFORMATION SECTION 28 A OIL SUPPLY 28...

Страница 4: ......

Страница 5: ...Y A QUALIFIED SERVICE PERSON See Page 30 CAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 28 WARNING The area around the furnace should be kept free and clear of combustible liquids and materi...

Страница 6: ...2...

Страница 7: ...r the Installation of Oil Burning Equipment NFPA 31 1997 or the latest edition and to these instructions The installation must also comply with CSA B139 for recommended installation practices where ap...

Страница 8: ...ow Requirements and Sizing of Ductwork section of this manual 5 Make sure supply and return air ducts are completely sealed to the appliance casing Refer to the Airflow Requirements and Sizing of Duct...

Страница 9: ...A furnace installed in a residential garage must be installed so the burner and ignition source are located higher than 18 inches above the floor The furnace must also be located or protected to avoid...

Страница 10: ...imney in a worse case situation Condensation most likely will not occur at the bottom of the chimney because the stack gas heats the chimney walls as it rises and the bottom will be heated first This...

Страница 11: ...feet above roof or exit point must be maintained See Figure 2b If the roof is flat rather than the normal residential pitched roof refer to Figure 3 for proper clearances Fig 3 Proper chimney terminat...

Страница 12: ...so they will seal to avoid air leaks 7 NO INTERCONNECTED CHIMNEY FLUES If chimney flues are divided or there are multiple flues within one chimney make sure there are no openings in the partition sepa...

Страница 13: ...ber or mineral wool batts sandwiched between two sheets 0 024 24 gauge sheet metal with ventilated air space 9 6 5 3 3 3 A Equal the required clearance with no protection B Equals the reduced clearanc...

Страница 14: ...may also be horizontally vented through a sidewall A field model FDVS 67 FOVP 615 side wall vent kits for such applications is available When installing the sidewall vent kits outside combustion air...

Страница 15: ...lel with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger If the cooling unit is installed with a parallel flow arrangement dampers or other means use...

Страница 16: ...ilter rack can be held in position by tape or similar temporary means Position the open end of the filter rack so as to provide access for filter replacement Once the filter rack is positioned correct...

Страница 17: ...aximum Air Velocity ft min Model Number THV1M119A Supplied Permanent 600 480 in Standard Permanent 500 576 in Disposable 300 960 in Table 3 Minimum Required Filter Area in square inches The supplied f...

Страница 18: ...ber before installing burner The oil burner will mount on three stud mounting bolts on the lower mounting plate covering the opening in the front of the heat exchanger The end of the burner tube shoul...

Страница 19: ...EAD STATIC PLATE MAXIMUM NOZZLE SIZE SHIPPED NOZZLE SIZE OIL PUMP PRESSURE PSIG BECKETT AFG TP2701 N AFG 4 5 F6 2 3 4U 1 10X80 A 1 00X80 A 120 Table 5 Burner specifications INSULATOR S SLEEVE OR N NON...

Страница 20: ...y should be thoroughly cleaned before installing a new cartridge K ELECTRICAL WIRIING This appliance must be grounded in accordance with local codes or in the absence of local codes with the National...

Страница 21: ...tween EAC and N6 provides a switched 115 vac to power an electronic fan cleaner The same switched 115 vac is available between FAN and N7 and may be used in conjunction with a humidistat to control a...

Страница 22: ...his setting can be found in the thermostat installation instructions If this information is not available or if the correct setting is questioned the following procedures should be followed L Blower M...

Страница 23: ...87 971 9 38 923 9 01 895 8 68 864 8 23 829 High 13 5 1320 13 2 1290 12 8 1270 12 4 1240 11 3 1130 10 7 1090 10 2 1020 Speed Tap Static Pressure High Fire Temperature Rise vs External Static pressure i...

Страница 24: ...3 72 310 3 84 325 4 02 339 4 13 350 4 31 364 Med 3 74 314 3 91 327 4 11 345 4 25 360 4 39 374 4 60 390 4 74 406 MH 4 21 356 4 40 373 4 57 390 4 73 407 4 90 422 501 432 5 12 450 High 7 2 638 7 2 650 7...

Страница 25: ...arness Wires Beckett Connections Riello Connections Thermostat Humidistat connections C Common ground W Thermostat call for heat R 24 VAC to thermostat G Thermostat call for fan Y Thermostat call for...

Страница 26: ...will light when the control receives a call for dehumidification Refer to the Cool Mode section for the control operation Thermostat call for fan G 24 VAC thermostat input A call for fan is recognized...

Страница 27: ...ed from the thermostat If no other mode is calling for blower operation the control will operate the fan relay K4 and power the Low blower speed terminal The fan mode will be operated as long as the G...

Страница 28: ...tap only In the case of thermostat calls for Y and W together blower speed selection will be determined by the input that was first initiated In the case where the control is in a cooling mode with b...

Страница 29: ...nputs and are located directly below those inputs They will light to indicate the presence of these signals The red Board Status LED has two functions It will light when the board recognizes a valid i...

Страница 30: ...ed service technician or oil supplier To Turn Off Oil to Appliance i Set the thermostat to the lowest setting and set the operating mode switch to OFF ii If service is to be performed turn off the ele...

Страница 31: ...appliance heating section the following test instruments are required A smoke density measuring and rating device A carbon dioxide CO2 or oxygen O2 analyzer A flue gas temperature measuring device e g...

Страница 32: ...materials damage from rust or corrosion soot or carbon build up EXTERIOR OF FURNACE The furnace exterior should be inspected for signs of excessive heat such as discoloration of materials and damage...

Страница 33: ...removing any furnace access doors to service the air filters The air filters should be inspected each month and cleaned when dirty Cleaning the air filters frequently may reduce airborne contaminants...

Страница 34: ...eat exchanger will act as an insulator and reduce heat transfer resulting in less efficiency 1 To clean the heat exchanger first turn off all power to the unit Remove clean out plugs the vent connecto...

Страница 35: ...31 Figure 17 Heat Exchanger Clean Outs Vacuum Hose Length THV1M119A 8FT Fig 18 Recommended method and device for cleaning inside of heat exchanger...

Страница 36: ...32 V Sequence of Operations Flow Chart...

Страница 37: ...33...

Страница 38: ...34 VI Trouble Shooting Flow Chart...

Страница 39: ...35...

Страница 40: ...36...

Страница 41: ...37...

Страница 42: ...38...

Страница 43: ...FILTER DRAFT CONTROL COMBUSTION TESTS Operate burner at least 10 minutes before CO2 in stack pipe INITIAL SERVICE SERVICE SERVICE INSTALLATION Draft Over fire Draft in stack pipe Smoke number Furnace...

Страница 44: ...40 Appendix A Replacement Parts for THV1M119A...

Страница 45: ...41...

Страница 46: ...42 Appendix B THV1M119A960SA PSC Wiring Diagram...

Страница 47: ...43 THV1M119A9T5SA CTM Wiring Diagram...

Отзывы: