background image

All installations and services must be performed by qualified service personnel. 

 
 
The Field vent kit is set up with 4 inch diameter vent pipe with concentric through-the-wall vent termination/inlet air 
vent hood. The combustion air inlet pipe diameter is also 4 inch diameter. For Beckett, the combustion air inlet pipe 
will be reduced to 3” diameter with the Beckett side wall vent kit. 
 
The side wall vent may be installed either through the upper knock-out on the left side casing of the unit or vertically 
out the top opening of the vestibule. The 4” flexible vent pipe included w/ Field vent kit is able to be installed at 2” 
clearance to combustibles. 
 
The combustion air inlet can be installed through the either the lower left side casing knock-out or the lower right 
side casing knock-out. 
 
 
B. DRAFT REGULATORS: 
 
A  draft  regulator  is  supplied  with  the  furnace  and    should  be  installed  according  to  the  regulator  manufacturers 
recommendations. With the burner operating, use a draft gauge to adjust the regulator to the proper setting. (refer to 
the instructions enclosed with draft regulator to adjust to the proper setting). When the burner air supply and draft are 
properly adjusted, the overfire draft should be a negative (-).01" to (-).02" WC

  1

, as measured at the 5/16" overfire 

air tap (See Fig. 4). This tap is provided in the upper burner mounting plate. To measure the flue draft, punch a small 
hole in the vent connector pipe as close to the furnace as possible and always before the draft regulator. 
 

 

 

 

 

 

 

 

 

Note: 

1. Draft overfire may be positive for high fire applications but not to exceed (+).02" WC. 

 
 
C.  DUCT WORK/AIR CONDITIONING/SUPPLY/RETURN AIRFLOW AND AIR TEMPERATURE: 
 
If the furnace is used in connection with summer air conditioning (cooling), the furnace should be installed parallel 
with  or  on  the  upstream  side  of  the  evaporator  coil  to  avoid  condensation  in  the  furnace  heat  exchanger.  If  the 
cooling unit is installed with a parallel flow arrangement, dampers or other means used to control flow of air should 
be  provided  to  prevent  chilled  air  from  entering  the  furnace.  If  such  a  damper  is  manually  operated,  it  must  be 
equipped with a means to prevent operation of either unit, unless the damper is in the full heat or cool position. 
 
The  supply/return  airflow  shall  be  set  to  obtain  an  air  temperature  rise,  across  the  furnace,  in  the  range  of  55º  to 
85ºF.  Since  the  flow  resistance  of  each  duct  system  is  slightly  different,  the  airflow  (fan  speed)  may  have  to  be 
changed in the field to achieve a satisfactory temperature rise.  
 
One  way  to  measure  the  temperature  rise  across  the  furnace  is  to  insert  temperature  measuring  devices  (e.g. 
thermometers) into the return air duct and into the supply air duct about 12 inches from the furnace. After the furnace 
has been firing continually for over 20 minutes, read the temperature difference between the two (2) thermometers. 
The temperature difference should not exceed 85ºF, nor be less than 55ºF. A temperature rise of 70ºF is considered 
to be optimum for comfort. 
 
The  blower  (fan)  speed  fan  is  adjusted  by  changing  the  fan  motor  winding  energized  by  the  control  system.  The 
furnace is set on fan speed, “ML”, at the factory, refer to page 13 of this manual. To adjust the fan speed, change 
corresponding wire from the appropriate fan speed to the “HEAT” tap on the control. 
 

FIELD VENT TERMINATION 

KIT

SIDE WALL VENT  

ACCESSORIES KIT

COMBUSTION AIR INTAKE 

HOOD KIT

(15’ application MAX)

(BURNER SPECIFIC)

(FOR COMBUSTION AIR 

APPLICATIONS ONLY)

PART NUMBER

PART NUMBER

PART NUMBER

Beckett AFG

AOPS8393 

AOPS8394

AOPS8397

Beckett NX 

AOPS8393

AOPS8412

AOPS8413

BURNER

SIDE WALL VENTING APPLICATION ORDER INFORMATION

Содержание Spirit VHF-ABE

Страница 1: ...nce Improper installation adjustment alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional informati...

Страница 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Страница 3: ...RETURN AIRFLOW AND AIR TEMPERATURE 3 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANI...

Страница 4: ...located or protected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MA...

Страница 5: ...power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the VHF A it is possible to rotate the flue elbow which is factory installed for vertical discharge...

Страница 6: ...tioning cooling the furnace should be installed parallel with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger If the cooling unit is installed with a...

Страница 7: ...essary to cut the return air opening in the side or rear casing depending upon the needs of the specific installation The filter rack provided with the furnace refer to Fig 2 will serve as a template...

Страница 8: ...ange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions for adapting the return air plenum to the filter rack are provided See Fig 2 E LIMIT...

Страница 9: ...ig 4 This retainer secures the chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and compo...

Страница 10: ...CONE FOR EXAMPLE A NOZZLE RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information c...

Страница 11: ...With access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum clean...

Страница 12: ...discoloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage...

Страница 13: ...ystem and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The fil...

Страница 14: ...MASONRY CHIMNEY W METAL LINER FUEL LINE FILTER DRAFT CONTROL COMBUSTION TESTS Operate burner at least 10 minutes before CO2 in stack pipe INITIAL SERVICE SERVICE SERVICE INSTALLATION Draft Over fire D...

Страница 15: ...All installations and services must be performed by qualified service personnel 12 APPENDIX A Replacement Parts List...

Страница 16: ...All installations and services must be performed by qualified service personnel 13...

Страница 17: ...All installations and services must be performed by qualified service personnel 14...

Страница 18: ...All installations and services must be performed by qualified service personnel 15...

Страница 19: ...All installations and services must be performed by qualified service personnel 16 APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier...

Страница 20: ...All installations and services must be performed by qualified service personnel 17...

Отзывы: