background image

All installations and services must be performed by qualified service personnel. 

F.  BURNER INSTALLATION: 
 
NOTE: The burner is factory installed on this furnace. 
NOTICE:
  Remove all cardboard packing from around chamber before installing burner. 
The oil burner will mount on three stud mounting bolts on the lower mounting plate covering the opening in the front 
of the heat exchanger. The end of the burner tube should be inserted no further than 1/4 inch back from the inside 
surface of the combustion chamber. A distance further than 1/4 inch back from the inside chamber wall may cause 
impingement  and  sooting.  This  unit  is  equipped  with  a  chamber  retainer  (refer  to  Fig.4).  This  retainer  secures  the 
chamber  during  shipping  and  helps  to  maintain  insertion  depth.  DO  NOT  remove  this  retainer  when  installing 
burner. 

 

Fig. 4: Typical location of the overfire air tap and components in burner mounting plate area 

 

 

Fig. 5: Burner insertion illustration (Top view) 

 
 

When mounting the burner, the mounting plate (Fig. 4) must be removed to provide access to the area in front of the 
combustion chamber. A fiber insulating sleeve or amulet is provided on the burner tube of specific burners.(see Fig. 
5). See burner application chart for type of insulator.  Do not allow the burner tube or end cone to physically touch 
or protrude into the chamber, as excess heat transfer could result in destruction of the tube, end cone or both. The 
burner tube/end cone is properly positioned, when the end is ¼ inch back from the inside surface of the combustion 
chamber wall. 

 

 
 
 

Содержание Spirit VHF-ABE

Страница 1: ...nce Improper installation adjustment alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional informati...

Страница 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Страница 3: ...RETURN AIRFLOW AND AIR TEMPERATURE 3 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANI...

Страница 4: ...located or protected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MA...

Страница 5: ...power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the VHF A it is possible to rotate the flue elbow which is factory installed for vertical discharge...

Страница 6: ...tioning cooling the furnace should be installed parallel with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger If the cooling unit is installed with a...

Страница 7: ...essary to cut the return air opening in the side or rear casing depending upon the needs of the specific installation The filter rack provided with the furnace refer to Fig 2 will serve as a template...

Страница 8: ...ange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions for adapting the return air plenum to the filter rack are provided See Fig 2 E LIMIT...

Страница 9: ...ig 4 This retainer secures the chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and compo...

Страница 10: ...CONE FOR EXAMPLE A NOZZLE RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information c...

Страница 11: ...With access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum clean...

Страница 12: ...discoloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage...

Страница 13: ...ystem and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The fil...

Страница 14: ...MASONRY CHIMNEY W METAL LINER FUEL LINE FILTER DRAFT CONTROL COMBUSTION TESTS Operate burner at least 10 minutes before CO2 in stack pipe INITIAL SERVICE SERVICE SERVICE INSTALLATION Draft Over fire D...

Страница 15: ...All installations and services must be performed by qualified service personnel 12 APPENDIX A Replacement Parts List...

Страница 16: ...All installations and services must be performed by qualified service personnel 13...

Страница 17: ...All installations and services must be performed by qualified service personnel 14...

Страница 18: ...All installations and services must be performed by qualified service personnel 15...

Страница 19: ...All installations and services must be performed by qualified service personnel 16 APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier...

Страница 20: ...All installations and services must be performed by qualified service personnel 17...

Отзывы: