Refrigeration Service Operations (Rev. 1/99)
62
1.
Cap
7.
Clip
2.
Top Cap
8.
Seat
3.
Check Valve
9.
Gaskets
4.
Spring
10.
Stem Assembly
5.
Piston
11.
Screen
6.
Seal
12.
Bottom Cap
Three-way Valve
AEA714
THREE-WAY VALVE CONDENSER
PRESSURE BYPASS CHECK VALVE
REPAIR
Removal
1.
Remove the refrigerant charge.
2.
Unscrew the condenser pressure bypass check valve
cap from the three-way valve.
3.
Remove the snap ring.
4.
Unscrew the check valve stem by using a screwdriver
in the slot provided.
NOTE: The spring and the check valve are held in by
the stem. While removing the stem, use care to make
sure that the spring and the check valve are not lost.
5.
Remove the spring and the check valve.
6.
Inspect the check valve seat in the three-way valve.
7.
If replacement parts are needed, a kit P/N 60-163 must
be used which includes the check valve, spring, O-ring,
valve stem and snap ring.
1.
Check Valve
4
Valve Stem
2
Snap Ring
5
O-ring
3
Cap
6
Spring
Check Valve Assembly
AEA715
Содержание 914 724
Страница 4: ......
Страница 8: ......
Страница 14: ...4...
Страница 16: ...6...
Страница 25: ...Unit Description Rev 1 99 15 1 Fan 2 Thermometer Sensor 3 Thermostat Sensor Evaporator 1 2 3 AGA358...
Страница 32: ...22...
Страница 38: ...28...
Страница 98: ...88...
Страница 107: ...97 Model 10 and 20 Schematic Diagram...
Страница 108: ...98 Model 10 Wiring Diagram...
Страница 109: ...99 Model 20 Wiring Diagram...
Страница 110: ...100 Model 20 Single Phase with Heat Option Schematic Diagram...
Страница 111: ...101 Model 20 Single Phase Wiring Diagram...