58
TECHNICAL ASSISTANCE SERVICE
ENGLISH
RESETTING THE BURNER
Proceed as follows to reset the burner:
- Press and hold the reset button for between 2 and 4 seconds. If the burner does not restart, Check that the boiler
controller is actually requesting ignition.
-
The burner can only be reset consecutively 5 times . After that, the power supply must be disconnected in order
to obtain a further 5 resets .
Colour codes for burner reset button LED
BURNER FAULT LOCKOUT TYPES AND TIMES
Functioning status
LED colour code
Speed of
flashing
Seconds
ON OFF
Standby
Led off
-
-
-
Pre-heating time
Green flashing
Slow
0,5
2,5
Pre-ventilation
Orange flashing
Slow
0,5
0,5
Safety time
Green flashing
Slow
0,5
0,5
Functioning
Green
-
-
-
Extraneous light (false flame signal)
Green + Red flashing
Slow
0,5
0,5
Power supply frequency error
Orange
-
-
-
Voltage monitor error
Green flashing
Fast
0,2
0,2
Reset / remote reset button fault
Green + Red flashing
Fast
0,2
0,2
Lockout for flame failure after Ts
Red
-
-
-
Lockout for false flame signal
Red flashing
Slow
0,5
0,5
Lockout for maximum number of startup cycle
repetitions (flame failure during functioning)
Red flashing
Fast
0,2
0,2
Lockout for failure to complete preheating
Red flashing
Slow
0,5
2,5
Lockout for fan motor error
Red + Orange flashing
Reversed 2,5
0,5
Lockout for fuel oil valve fault
Green + Red flashing
Reversed
2,5
0,5
Lockout for EEPROM error
Green flashing
Slow
0,5
0,5
Description of fault
Lockout
Presence of extraneous light on burner startup or shutdown.
Within 1 second
Pre-heating not finished
After 600 seconds
Presence of extraneous light during fuel oil pre-heating.
After max 25 seconds
Flame not detected by end of safety time.
5 seconds after the
activation of the fuel oil
valve
Flame failure during functioning.
After 3 ignition cycles
Fan motor error
Immediate
FLockout for fuel oil valve fault
Immediate
EEPROM error
Immediate