PREPARING FOR INITIAL START-UP
EMPTYING
Switch the electricity supply OFF at the system’s main
switch and at the control panel before starting to empty
the boiler or storage cylinder.
EMPTYING THE CENTRAL HEATING SYSTEM
- Open any non-return valves in the CH circuit to facilitate
emptying.
- Close the shut-off cocks for the water circuit.
- Connect a plastic hose to the hose union on the boiler’s
drain cock (1) and open the cock.
- Close the CH circuit's non-return valves.
ON
OFF
- The water and fuel shut-off cocks must be open.
- With the system cold, the water pressure gauge (3)
must show a pressure
over 1 bar
, with the water circuit
properly de-aerated
- The expansion vessel (fitted on installation) must be
properly pre-charged.
- The cap on the vent valve (2) must be open.
- All electrical connections to the mains supply and to
the system’s control and safety devices must have been
made correctly.
- The flue gas exhaust and flue pipes must have been
correctly installed and connected.
- The pump/s (fitted on installation) must turn freely.
Unscrew the inspection cap and use a flat blade
screwdriver to check that the pump shaft turns smoothly.
- The room unit (if fitted) must be correctly connected
(see the "Electrical connections" section).
b
Protect all electrical devices under the pump before
you unscrew the inspection cap just in case water
comes out.