Parameter
Meaning
TOPH. TIME
Time in hours that the legionella demand is to be fulfilled for peak heating charging to be considered com-
plete.
Factory setting:
, range:
, 1H – 10H
TOPH. STOP
Stop temperature for peak heat charging. Operating mode that permits auxiliary heater must be selected.
Factory setting: 60°C, range: 50°C – 65°C
INFL. H.W SENSOR
Hot water sensor’s influence compared with the peak sensor’s at start of water heating.
Factory setting: 65%, range: 0% – 100%
INFL.ECO-MODE
Factory setting: 10, range: 0 – 30
TOP WATER SEN-
SOR
Shows the actual temperature at the top of the water heater provided that this sensor is engaged.
HOT WATER SEN-
SOR
Shows the actual temperature approx 1/3 from the bottom of the hot water sensor.
8.3
HEATING
Parameter
Meaning
START
The heat pump control system uses an advanced evaluation model for determining the heat demand, here ex-
pressed as a single value. The start threshold for heating is set default, but may be altered if local adjustments
are needed. Typically this is a setting you adjust in relation to the energy inertia of the building. Default value is
set for an average domestic building with normal insulation. Decreasing the START setting will allow the heat
pump to start sooner and vice versa.
Factory setting: 50, range: 1 – 100
STOP
The stop threshold for heating is set default, but may be altered if local adjustments are needed. Increasing the
STOP setting will allow the heat pump to stop sooner and vice versa.
Factory setting: -50, range: -100 – 0
START-UP H.T
The estimated time it takes for the water to be pumped around the system. During this time the control system
will not react on any demands.
Factory setting: 5M, range: 1s – 30M
HEATING TIME
When the heat pump must alternate between different demands for example heating, hot water, pool heating
and cooling, heating will be produced longest according to the set number of minutes.
Factory setting: 30M, range: 5M – 40M
8.4
COOLING
Parameter
Meaning
COOLING
Activates the cooling function.
Factory setting:
, range:
, ACTIVE COOLING, INTEGRATED IN HP
START
The heat pump control system uses an advanced evaluation model for determining the cooling demand, here
expressed as a single value. The start threshold for cooling is set default, but may be altered if local adjustments
are needed. Typically this is a setting you adjust in relation to the energy inertia of the building. Default value is
set for an average domestic building with normal insulation. Increasing the START setting will allow the heat
pump to start sooner and vice versa.
Factory setting: -50, range: -100 – -1
STOP
The stop threshold for cooling is set default, but may be altered if local adjustments are needed. Increasing the
STOP setting will allow the heat pump to stop sooner and vice versa.
Factory setting: 30, range: 0 – 100
COOLING TIME
When the heat pump must alternate between different demands for example heating, hot water, pool heating
and cooling, cooling will be produced longest according to the set number of minutes.
Factory setting: 20M, range: 5M – 40M
MAX START TEMP
Highest settable temperature for START parameter in INFORMATION -> COOLING.
Factory setting: 30°C, range: COOLING->MIN STOP TEMP – 55°C
MIN STOP TEMP
Lowest settable temperature for STOP parameter in INFORMATION -> COOLING.
Factory setting: 16°C, range: 5°C – COOLING->MAX START TEMP
Commissioning
iTec
VIJSR102
Thermia Värmepumpar
34