EVS Fire Test Procedures and Specifications
Page 15 of 22
APPENDIX D (Cont…) - TSBC
TM
SETUP Menu
Display
Factory
Settings
Range/Choices
Description
Outdoor
Sensor
No
No
Display Only
Outdoor Reset
Enables the Outside Air Temperature sensor display and control logic.
No:
Outside Air Input (O+O-) is ignored.
Display Only: Do Not Calculate setpoint based on outdoor temperature,
Display Outside Air Temperature
Outdoor Reset: Calculate the temperature setpoint based on outdoor
temperature using a reset curve defined by Outdoor Set Up,
Boiler Set Up, Outdoor Design and boiler Design parameters
Outdoor
Set Up
55
40 F to 100 F
The Outdoor Set Up temperature is the outdoor temperature at which the
Boiler Set Up temperature is supplied.
Only visible when Outdoor Sensor is set to Outdoor Reset
Boiler
Set Up
140
80F to 180 F
The Boiler Set Up Temperature is the starting boiler water temperature of the
reset ratio. If the building feels cool during mild outdoor conditions, the
Boiler Set Up setting should be increased.
Only visible when Outdoor Sensor is set to Outdoor Reset
Outdoor
Design
30
-20 F to 50 F
The Outdoor Design Temperature is the outdoor temperature at which the
Boiler Design temperature is supplied.
Only visible when Outdoor Sensor is set to Outdoor Reset
Boiler
Design
180
80F to 220 F
The Boiler Design setting is the water temperature required to satisfy the
building heat loss during the Outdoor Design temperature. If the building feels
cool during cold outside conditions, the Boiler Design setting should be
increased.
Only visible when Outdoor Sensor is set to Outdoor Reset
Blower
SPD
High
100
0 to 100 %
Percent of (0 - 10 vdc output (V+, V-) output that represents a 100%
modulation rate. This scaling factor allows the controller to display 100%
when the blower is at rated boiler output.
Blower
SPD
Low
0
0 to 100 %
Percent of (0 - 10 vdc output (V+, V-) output that represents a 0% modulation
rate. This scaling factor allows the controller to display 0% when the blower is
at minimum boiler output.
Low Fire
Spd
50
0 to 100 %
Modulation % used for Low Fire Hold and Low Fire Start conditions
Fan
Purge
Spd
See
Description
0 to 100 %
Percent of blower operating range that the blower should be run during Fan
Purge (at ignition)
Build
Boiler model
500 750 1000
1500
2000
2000S
2500
3000
Standard 100 100 100
100
100
47
84
55
Low fire
proving
25
25
24
19
26
47
84
55
Venturi
NA 100 100
23
26
NA
NA
NA
Содержание EVS SERIES
Страница 13: ...13 Figure 3 Sidewall Positive Pressure Venting Optional Figure 2 Sidewall Positive Pressure Venting ...
Страница 14: ...14 Figure 4 Vertical Pressurized Venting ...
Страница 16: ...16 Figure 5 Typical Negative Pressure Conventional Venting ...
Страница 18: ...18 Figure 7 Vertical Air Intake Piping ...
Страница 27: ...27 Figure 9a 208 230 460V 1 3 ph 60 Hz Supply Power Wiring Schematic ...
Страница 28: ...28 Figure 9b 120V 1ph 60Hz Supply Power Wiring Schematic ...
Страница 29: ...29 Figure 9c Standard UL FM CSD 1 Wiring Diagram EVS 500 2000 ...
Страница 31: ...31 Figure 9e Standard UL FM CSD 1 EVS 2000S 3000 ...
Страница 35: ...35 Figure 11 Modular System Horizontal Air Intake Piping ...
Страница 36: ...36 Figure 12 Modular System Vertical Air Intake Piping ...
Страница 37: ...37 Figure 13 Modular System Typical One Pipe Water Piping ...
Страница 38: ...38 Figure 14 Modular System Typical Primary Secondary Water Piping ...
Страница 39: ...39 Figure 15 Modular System Typical Primary Secondary without System Pump ...
Страница 40: ...40 Figure 16 Modular System Typical Reverse Return Water Piping ...
Страница 41: ...41 Figure 17 Modular System Reverse Return with System Pump Only ...
Страница 42: ...42 Figure 18 Modular System Typical Primary Secondary with Reverse Return ...
Страница 58: ...58 Figure 19 Combustion Chamber Assembly ...
Страница 60: ...60 Figure 20 Burner Assembly FRONT VIEW TOP VIEW ...
Страница 62: ...62 Figure 21 UL FM CSD 1 Main Gas Train Assembly ...
Страница 65: ...65 Figure 22b DB B Gas Train 500 750 Figure 22c DB B Gas Train 1000 2000 ...
Страница 70: ...70 Figure 23 Jacket Panels ...
Страница 74: ...74 Figure 25 Pilot Assembly Bishop Design ...
Страница 88: ...88 NOTES ...
Страница 89: ...89 NOTES ...
Страница 90: ...90 NOTES ...
Страница 91: ...91 NOTES ...