SETPOINTS MENU
EVCA Modulating Fire Test Procedures and Specifications
APPENDIX D (Cont…) - TSBC
TM
SETPOINTS Menu
Display
Factory
Settings
Range/Choices
Description
Operational
SP
180
60 to 230 F
Setpoint used in Local Setpoint Mode when not servicing a Domestic Hot Water
Priority (DHWP) request.
On Point
-5
0 to 99 F
The boiler starts when the water temperature drops ‘On Point’ degrees below the
setpoint.
Off Point
15
0 to 99 F
The boiler stops when the water temperature rises ‘Off Point’ degrees above the
setpoint.
High Temp
Stop
Boilers
230
60 to 230 F
The boiler stops when water temperature is above the High Temperature Stop
setpoint. This setpoint is active in every control mode.
DHWP
Setpoint
180
140 to 230 F
The Domestic Hot Water Priority (DHWP) Setpoint is active when DHW Input
(DP) closes and “DHWP” parameter is set to “yes” and Local SP Mode is
selected. When the contact is closed, the boiler outlet is maintained at, or above,
the DHW Setpoint.
Only visible when
DHWP
equals
Yes
.
WWSD
Setpoint
70
40 to 90 F
The Warm Weather Shutdown (WWSD) Setpoint used to disable boiler and or
system pump operation when enabled by setting the “WWSD” parameter to
“WWSD of Boiler”, “WWSD of Sys Pump” or “Both”.
Only visible when
WWSD
does not equal
Off
.
Max SP
Boilers
230
140 to 230 F
The Maximum Operational Setpoint for all possible Local and Remote modes.
Min SP
70
60 to 230 F
The Minimum Operational Setpoint is the lower limit for all Local and Remote
modes.
Min BIT
120
60 to 235 F
Low Boiler Inlet Temperature alarm and event setpoint.
Min In H2O
Temp
130
110 to 180 F
Minimum Inlet Water Temperature setpoint used as the Mixing Valve inlet
temperature setpoint.
Only visible when
Mixing Valve
equals
Yes
.
Max H2O
Delta T
50
20 to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature
setpoint used as the Mixing Valve differential temperature setpoint.
Only visible when
Mixing Valve
equals
Yes
.
Max
Delta T
Hold
50
20 to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature used
to hold modulation rate at low fire.
Page 17 of 22
Boilers
230
Water
Heaters
200
Boilers
230
Water
Heaters
200
140
Содержание EVS SERIES
Страница 13: ...13 Figure 3 Sidewall Positive Pressure Venting Optional Figure 2 Sidewall Positive Pressure Venting ...
Страница 14: ...14 Figure 4 Vertical Pressurized Venting ...
Страница 16: ...16 Figure 5 Typical Negative Pressure Conventional Venting ...
Страница 18: ...18 Figure 7 Vertical Air Intake Piping ...
Страница 27: ...27 Figure 9a 208 230 460V 1 3 ph 60 Hz Supply Power Wiring Schematic ...
Страница 28: ...28 Figure 9b 120V 1ph 60Hz Supply Power Wiring Schematic ...
Страница 29: ...29 Figure 9c Standard UL FM CSD 1 Wiring Diagram EVS 500 2000 ...
Страница 31: ...31 Figure 9e Standard UL FM CSD 1 EVS 2000S 3000 ...
Страница 35: ...35 Figure 11 Modular System Horizontal Air Intake Piping ...
Страница 36: ...36 Figure 12 Modular System Vertical Air Intake Piping ...
Страница 37: ...37 Figure 13 Modular System Typical One Pipe Water Piping ...
Страница 38: ...38 Figure 14 Modular System Typical Primary Secondary Water Piping ...
Страница 39: ...39 Figure 15 Modular System Typical Primary Secondary without System Pump ...
Страница 40: ...40 Figure 16 Modular System Typical Reverse Return Water Piping ...
Страница 41: ...41 Figure 17 Modular System Reverse Return with System Pump Only ...
Страница 42: ...42 Figure 18 Modular System Typical Primary Secondary with Reverse Return ...
Страница 58: ...58 Figure 19 Combustion Chamber Assembly ...
Страница 60: ...60 Figure 20 Burner Assembly FRONT VIEW TOP VIEW ...
Страница 62: ...62 Figure 21 UL FM CSD 1 Main Gas Train Assembly ...
Страница 65: ...65 Figure 22b DB B Gas Train 500 750 Figure 22c DB B Gas Train 1000 2000 ...
Страница 70: ...70 Figure 23 Jacket Panels ...
Страница 74: ...74 Figure 25 Pilot Assembly Bishop Design ...
Страница 88: ...88 NOTES ...
Страница 89: ...89 NOTES ...
Страница 90: ...90 NOTES ...
Страница 91: ...91 NOTES ...