background image

©2015 Thermaco, Inc. All rights reserved  •  Patented/Patents Pending  •  Specifications subject to change without notice

Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651

MNL-ISPS50000 7

50000 Series

Big Dipper

®

 IS System

Troubleshooting

Big Dipper unit overflows

(1) Check to see that the outlet pipe is not reduced to a 

smaller size, the outlet piping is vented, has as few 90 

degree outlet turns as possible, and that no “P” trap is 

installed on the outlet.  Re-plumb the piping, if neces-

sary.  Check outlet piping for clogs.  Have a plumber 

clean the line, if necessary.

(2) Make sure that the solids strainer is in place and 

emptied daily.

 

(3) Check the bottom of the grease chamber for exces-

sive solids and silt buildup which may be blocking the 

outlet baffle.  Disconnect the power and use a long 

handled spatula or similar instrument to stir the bottom 

while water flows through the unit.  If necessary, drain 

and clean the sediment from the unit.  To prevent recur-

rence, schedule this cleaning to be done on a regular 

basis (properly used, a wet vac may be appropriate for 

cleaning sediment from the bottom of the unit).

(4) Make sure the flow rate to the unit does not exceed 

the maximum flow rate, which is shown on the nameplate.  

If necessary, have a plumber install an approved flow 

control to restrict the inlet flow to the specified level or 

install a properly sized Big Dipper for the application.

Excessive water observed in the grease collection 

container

(1) Check Digital Control for excessive “on” time.  Unit 

will pick up incidental water after all grease is removed.  

If  necessary,  reduce  the  digital  control  setting  (i.e. 

Moderate [II] to Light [I]) until no water is observed in 

the grease collection container.

(2) Make sure that the water flow to the unit does not 

exceed the rated flow and there are no drain line clogs 

downstream from the unit.

No grease is collected in the container

(1) Check to be sure the power is on and the correct 

setting is chosen.  One of the setting buttons should be 

illuminated.  If none of the setting buttons are illuminated, 

the unit is not powered.

(2) Lift the sump cover and clean away any buildup 

that may be present on the wiper blades or collection 

trough.  Make sure the wiper blade(s) are properly in 

place on the skimmer wheels.  Replace wiper blades 

when worn or warped.

(3) Press the Start Button on the bottom of the user inter-

face to ensure that the skimming wheel turns

.  

CAUTION: Keep your hands away from moving parts 

to avoid possible injury.  If the skimmer motor does not 

come on, the motor assembly may need to be replaced.

(4) Check for congealed grease in the unit.  If the Big 

Dipper’s heating element is not warming the unit, the 

heating element may need to be replaced.

(5) Some sites do not generate enough grease to be 

captured  by  the  skimming  process.    Set  Control  for 

minimum  operation  -  Setting  [I]  for  Light  Skimming 

Operation. 

Objectionable odor

(1) Make sure grease/oil is being skimmed properly 

from the unit.

(2) Check Digital Control for excessive “on” time.  Unit 

will pick up incidental water after all grease is removed.  

If  necessary,  reduce  the  digital  control  setting  (i.e. 

Moderate [II] to Light [I]) until no water is observed in 

the grease collection container.

(3) If excessive sediment has collected on the bottom 

of the unit, clean the unit as described in item 3 in “Big 

Dipper unit overflows.”

(4)  Clean  the  solids  strainer  and  grease  collection 

container more frequently.

(5) Grease interceptors, grease separators, automatic 

recovery  units,  grease  removal  devices  and  other 

similar plumbing devices receiving kitchen flows from 

sinks, floor drains, woks and other food bearing sources 

may generate odors.  There are many factors influenc-

ing odor evolution and dissemination.  These include 

room ventilation, kitchen menu, ambient temperatures, 

ware washing practices, grease/oil input, daily input 

fluid volume, sanitizers, installation plumbing design 

and product maintenance/upkeep.  Odors are usually 

prevented by good area ventilation, frequent fluid in-

puts, good product maintenance practices and proper 

product installation.  Additional steps, including aeration, 

chlorination, improved area ventilation and additional 

maintenance control, may be needed at some sites.

Содержание Big Dipper 50000 Series

Страница 1: ...E OR PART WITHOUT WRITTEN CONSENT FROM THERMACO INC POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMEN...

Страница 2: ...SPS50000 2 50000 Series Table of Contents Table of Contents IS System Overview 3 IS System Maintenance 4 IS Digital Control Operation 5 IS System Troubleshooting 7 How To Reverse IS System Operation 8...

Страница 3: ...on container A digital control maintains the self cleaning operation activating the skimming wheel periodically based on the setting chosen Only the cleaned water exits the unit and flows into the fac...

Страница 4: ...blades are clipped in place properly B Press the Start button on the bottom of the user interface momentarily to ensure that the motor and skimming wheel are still operating correctly C Check the thi...

Страница 5: ...ge immediately If the skimming cycle is changed between active skimming cycles the next skim cycle will be at the new level Motor Exercising Foralldefaultmodeskimminglevels the motor will be energized...

Страница 6: ...the Heavy Mode III Button 3 The button III will blink temporarily indicating which operation level has been selected 4 Select desired mode at skim times frequencies listed below Extreme Modes Button...

Страница 7: ...uld be illuminated Ifnoneofthesettingbuttonsareilluminated the unit is not powered 2 Lift the sump cover and clean away any buildup that may be present on the wiper blades or collection trough Make su...

Страница 8: ...GREEMENT BETWEEN THERMACO INC AND THE HOLDER OF THIS DRAWING DO NOT DESTROY THIS DRAWING IT IS THE SOLE PROPERTY OF THERMACO INC AND MUST BE RETURNED UPON REQUEST MATERIAL UNLESS NOTED FINISH UNLESS N...

Страница 9: ...With Water Before Applying Power BigDippersystems equippedwithanelectric heating element MUST be filled with water before energizing the power to the system Failuretodosomaydamagetheelectricheating e...

Страница 10: ...EEMENT BETWEEN THERMACO INC AND THE HOLDER OF THIS DRAWING DO NOT DESTROY THIS DRAWING IT IS THE SOLE PROPERTY OF THERMACO INC AND MUST BE RETURNED UPON REQUEST MATERIAL UNLESS NOTED FINISH UNLESS NOT...

Страница 11: ...Control for W 200 IS VFCA 25 Vented Flow Control for W 250 IS VFCA 35 Vented Flow Control for W 350 IS VFCA 50 Vented Flow Control for W 500 IS 2 3 Installations where head height is greater than 6 f...

Страница 12: ...eck local plumbing code to determine if they are permitted by state or local plumbing code VFCA Vented Flow Control Installation Instructions IMPORTANT The flow control should be installed after the l...

Страница 13: ...t Socket Outlet NOT SUPPLIED Digital Control Big Dipper Electrical Requirements 4 5 Amps 115 VAC 50 60Hz 520 Watts For 230 VAC Units 2 3 Amps 230 VAC 50 60Hz 520 Watts Note Digital Control Supplied wi...

Страница 14: ...LESS NOTED FINISH UNLESS NOTED 646 GREENSBORO STREET PO BOX 2548 ASHEBORO NC 27203 VOICE 336 629 4651 FAX 336 626 5739 Decimals XX 03 XXX 015 Unless otherwise specified Dimensions are in inches Tolera...

Страница 15: ...RMACO INC AND THE HOLDER OF THIS DRAWING DO NOT DESTROY THIS DRAWING IT IS THE SOLE PROPERTY OF THERMACO INC AND MUST BE RETURNED UPON REQUEST MATERIAL UNLESS NOTED FINISH UNLESS NOTED 646 GREENSBORO...

Страница 16: ...ING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO INC AND THE HOLDER OF THIS DRAWING DO NOT DESTROY THIS D...

Страница 17: ...V NO DWG NO PART NO C SCALE RELEASE DATE SHEET OF ENGINEERING DRAWN DATE THIRD ANGLE PROJECTION Big Dipper IS System Replacement Parts SOLIDS STRAINER BASKET FOR MODEL USE PART W 200 IS SS THROUGH W 2...

Страница 18: ...aterials Thermaco shall not be respon sible for damage to products resulting from vault flooding sewer line back up pumping or lift station failure ambient water flow or other sources of water damage...

Отзывы: