background image

6

www.UsePhoenix.com  •  [email protected]

Toll-Free 1-800-533-7533

3.   Remove aluminum tape
4.   Remove control panel
5.   Remove right panel screws, viewed from front, attaching 

front filter bracket, and evaporator

6.   Remove control board
7.  Detach thermistor from control board jumper, (EVAP)
8.   Reassemble thermistor and dehumidifier using the above 

procedure in reverse

4.5 Condensate Pump Replacement

The internal condensate pump removes water that collects in 

the reservoir.
To replace the condensate pump:
1.   Unplug the unit
2.   Remove the rear skidplate
3.   Unplug the pump wires from the wire harness
4.   Remove the condensate hose and the screw attaching 

the pump bracket to the base

5.   Replace the pump, hose, wiring, bolts, and cover in the 

reverse order

4.6 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a 

new charge must be accurately weighed in. If any of the 

old charge is left in the system, it must be removed before 

weighing in the new charge. Refer to the unit nameplate for 

the correct charge weight and refrigerant type.

4.7 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external 

overload, run capacitor, but no start capacitor.

4.8 Gravity Drain Option

If the condensate pump fails and cannot be replaced 

immediately, the Phoenix 200HT can be used by draining by 

gravity.
1.  Unplug the unit and remove the front cover.
2.  Push the plastic plug on the right side (see Fig. 4) out 

from inside the unit.

3.  Locate the heavy vinyl hose that connects the drain pan 

to the condensate pump. Pull the end out of the pump.

4.  Remove tie wrap holding drain tube to suction line.
5.  Push that end of the vinyl hose through the hole in the 

right side.

6.  Connect a garden hose and run it to a drain. Keep the 

hose as flat to the floor as possible to avoid air pockets 

that would hinder draining. Placing the unit on something 

above the floor will also improve draining.

Содержание Phoenix 200 HT

Страница 1: ...Faster drying and superior static pressure for ducting Multiple Ducting Options 12 intake 10 exhaust Solid State Controls Easy to read and operate Recessed 12 Wheels Allows greater maneuverability on...

Страница 2: ...t from walls and other obstructions to air flow Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transporting the Phoenix 200HT 2 2 2 Location 2 2 3 Electrical Requirements 3 2 4...

Страница 3: ...e plugged in dehu midifier to rest 15 minutes before the final purge 2 8 Hour Meter The digital hour meter displays the amount of time the dehumidifier has been turned on to the tenth of an hour The h...

Страница 4: ...an alternative to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polyethylene To flush 1 Run the hose to a drain 2 Plug in the un...

Страница 5: ...but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle 4 Air filter dirty 5 Defecti...

Страница 6: ...ately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type 4 7...

Страница 7: ...www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 5 Wiring Diagram LL Therma Stor...

Страница 8: ...e 1 4023080 11 Control Board 1 4030083 12 Capacitor Compressor 45mfd 370V 1 4033032 05 13 Capacitor Impeller 15mfd 370V 1 4033031 07 14 Thermistor 1 4031279 15 Cord 1 4032297 16 TOS 8 2 KBTU R410A 1 4...

Страница 9: ...www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 This page intentionally left blank...

Страница 10: ...anty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts o...

Отзывы: