5
below the switching value, the light switches on when a pre-
sence is detected (in configuration type fully automatic).
Value range
Lux values with "SendoPro 868-A" management remote
control
In the installation remote control "theSenda P", the
following values are available
(The currently measured brightness value (Lux) can
be adopted with the "SendoPro 868-A" management
remote control, with the teach-in control command or
with the “theSenda P” installation remote control via the
teach-in button.)
Values outside the permitted range will automatically be
set to the appropriate limit value.
30 - 3000 Lux
30, 300, 500,
800 lux
- Deactivating the brightness measurement (the bright-
ness has no influence)
- The light channels only switch after presence/absence.
Possible with "SendoPro 868-A" management remote
control or "theSenda P" installation remote control.
Measurement
off
Button
Time delay A
Value range
Adjustable values with "SendoPro 868-A" manage-
ment remote control
In the "theSenda P" installation remote control, the
following values are available
10 s - 60 min
10 s, 30 s, 60 s, 2
min, 10 min, 20 min,
60 min
Control for staircase light timer switch (0.5 s "on"
/ 10 s "off")
"SendoPro 868-A"
"theSenda P"
Pulse
Button
1
Short-term presence
The time delay of channel A light can be switched off sooner
if a room is occupied only for a short time. (In fully automatic
device and semi-automatic device configuration type)
The switch-off delay time is used according to set parameters.
Off
If someone enters an unoccupied room and it is only occupied for
up to 30 seconds, the light goes off 2 minutes early.
On
Configuration type
Fully automatic device: The lighting switches on and off automa-
tically. (due to presence/no presence and brightness)
„SendoPro 868-A“
„theSenda P“
auto
Button A
Semi-automatic: Switch on must always occur manually. Switch
off occurs automatically by the presence detector. (due to pre-
sence or brightness)
„SendoPro 868-A“
„theSenda P“
man
Button
Control input S
Control input S for manual switch on/off of channel A light
automatically detects push buttons or switches.
Several push buttons can be connected to control input S
Use light push button only with neutral conductor connector
Value range
Automatic detection of push button or switch. A signal that
is present for than 0.7 s is detected as a push button. Longer
signals are evaluated as a switch.
auto
To adapt to user behaviour, the type of
signal transmitter used can be set to
fixed. Automatic detection is deactivated.
When selecting the push button, ope-
ning contact or NO contact can also be
specified.
Switch
Push button (NO
contact)
Push button (ope-
ning contact)
Switch
Push button
S
Push button
O
Configuration possible only with „SendoPro 868-A“.
Detection sensitivity
The detector has 5 sensitivity increments. The basic setting
is the middle level (3). By selecting the operation mode test
presence, the set sensitivity increment is not changed.
With the „SendoPro 868-A“ management remote control,
levels 1 to 5 can be selected and sent to the detector.
With the „theSenda P“ installation remote control, the sen-
sitivity can be reduced or increased by one level with every
button press.
Level
Sensitivity
1
very insensitive
2
insensitive
3
Standard
4
sensitive
5
very sensitive
Group address channel A
This parameter is applied when using the „theSenda P“ user
remote control. A group address can be assigned to the chan-
nel A light.
The „SendoPro 868-A“ or „theSenda S“ can be used to pro-
gram the group addresses in the detector.
Group address value range
Adjustable values "SendoPro 868-A"
I, II , III , All
Adjustable values "theSenda S"
I, II
LED display motion
The motion detection can be displayed via the LED.
Value range
No display of motion detection.
Off
The LED switches on when motion is detected, otherwise swit-
ches off.
On
Adjustment possible only with „SendoPro 868-A“.
Teach-in channel A
With teach-in, the currently measured brightness value is
accepted as brightness switching value A. Values outside the
permitted range will automatically be set to the appropriate
limit value.