The control command teach-in can be adopted with the 

„SendoPro 868-A“ management remote control or with the 

„theSenda P“ installation remote control via the 

 button.

Factory settings

The theRonda P360-100 M presence detector is supplied with 

the following parameter values:

Parameter

Value

Brightness switching value A

300 lux

Time delay A

10 min

Short presence A

On

Configuration type

auto

Control input S

auto

Detection sensitivity (PIR)

Stage 3

Group address

T

LED display movement

Off

9.  Start-up

Switching behaviour

Every time the power supply is switched on, the presence 

detector runs through two phases that are shown on an LED:

1. Start-up phase (30 s)

 

The red LED flashes every second, the switch contact is 

closed (light on).

 

The detector does not react to push button commands 
and remote control commands.

 

When no one is present the switch contact opens after 
30 seconds.

2. Mode

The detector is ready for operation (LED off).

Test presence

Presence test mode is used to test presence detection and 

wiring. Presence test mode can be activated with the „Sendo-

Pro 868-A“ management remote control and with the „the-

Senda P“ installation remote control.

Setting the presence test mode via remote control

 

The detector goes directly into test mode when the test 
mode is set via the remote control:

y

y

Every movement is indicated by the LED.

y

y

When movement occurs the light switch contact closes.

y

y

When no one is present the light switch contact opens after 

10 seconds.

y

y

Brightness measurement deactivates, detector does not react 

to brightness.

y

y

The detector reacts as in fully automatic function mode even 

if semi-automatic is set.

y

y

Teach-in cannot be activated in test mode.

 

Test mode ends automatically after 10 mins. The detector 
performs a new start (see switch-on behaviour).

10. Technical data

Operating voltage

110-230 V AC + 10 % / - 15%

Frequency

50-60 Hz

Upstream protection device:

13 A

Power consumption

approx. 0.1 W

Type of installation

Ceiling installation; Flush/

surface mounted or ceiling 

installation

Installation height

2,0 – 3,5 m / max. 10 m

Minimum height

> 1.7 m

Detection area 

horizontal

 vertical

360°

120°

Maximum range

Ø 8 m (Mh. 3 m) / 50 m

2

 radially 

moving

Ø 24 m (Mh. 3 m) / 452 m

2

 

tangentially moving

Setting range brightness switching value 30 – 3000 Lux
Lighting time delay

10 s – 60 min / Pulse

Channel A light

Relay 230 V / 10 A, µ-contact

Max. switching capacity  

cos 

j

 1 

resistive

2300 W 

Max. switching capacity cos 

j

 0.5

1150 VA 

Max. switching capacity LED

LED lamps < 2 W

LED lamps > 2 W

see manufacturer concerning 

cos 

j

60 W

180 W

Guidance value max. switch-on peak

800 A / 200 µs

Maximum number EBs T5/T8

16 x 54/58 W, 24 x 35/36 W

8 x 2 x 54/58 W

12x 2x 35/36 W 

Connection type

Terminals screws

Max. cable cross-section

max. 2 x 2.5 mm²

Flush-mounted socket size

Siz. 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 54 (installed)

Ambient temperature

-15 °C – 50 °C

CE Declaration of Conformity

This device conforms to the 

safety regulations of the EMC 

directive 2014/30/EU and of 

2014/35/EU.

  

Product overview

Type of 

installation

Channel Ope-

rating 

voltage

Colour

Type

Item No.

Ceiling 

installation

Light

110-

230 V 

AC

White

theRonda 

P360 -100 M

2080020

Ceiling 

installation

Light 

110-

230 V 

AC

Grey

theRonda 

P360 -100 M

2080021

Ceiling 

installation

Light

110-

230 V 

AC

Special colour 

in accordance 

with customer 

information

theRonda 

P360 -100 M

2080023

Troubleshooting

Fault

Cause

Light does not switch 

on and/or off if pre-

sence is detected and 

in darkness

Lux value is set too low; detector set on semi-

automatic; light was switched off manually via 

push button or „theSenda S“; person not within 

detection range; obstruction(s) interrupting detec-

tion; time delay set too short

Light stays on with 

detection of presence 

despite sufficient 

brightness 

Lux value is set too high; light was briefly switched 

on manually via push button or with „theSenda S“ 

(wait 30 min.); detector is in test mode

Содержание theRonda P360-100 M UP WH

Страница 1: ...lectrician in accordance with the technical regulations applying to electricity Comply with the country specific safety regulations for work on electrical systems Ensure absence of voltage in the cabl...

Страница 2: ...reduced as temperatures increase Seated persons The details relate to smallest movements at table height approx 0 80 m Moving persons At installation heights of between 5 and 10 m the extent and dist...

Страница 3: ...ave parallel switching If the detection area covered by one presence detector is insufficient larger rooms then up to 10 detectors can be operated in parallel by connecting P terminals In the process...

Страница 4: ...min Classroom approx 10 min Work areas office meeting room approx 10 min Pulse Control staircase light time switch 0 5 s on 10 s off Parameters and control commands via remote control The following pa...

Страница 5: ...theSenda P man Button Control input S Control input S for manual switch on off of channel A light automatically detects push buttons or switches Several push buttons can be connected to control input...

Страница 6: ...AC 10 15 Frequency 50 60 Hz Upstream protection device 13 A Power consumption approx 0 1 W Type of installation Ceiling installation Flush surface mounted or ceiling installation Installation height...

Страница 7: ...test mode or LED display movement is activated The LED displays detection of movement Guarantee Theben HTS presence detectors are manufactured with the utmost care and using state of the art technolog...

Страница 8: ...act Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzer...

Отзывы: