6
The control command teach-in can be adopted with the
„SendoPro 868-A“ management remote control or with the
„theSenda P“ installation remote control via the
button.
Factory settings
The theRonda P360-100 M presence detector is supplied with
the following parameter values:
Parameter
Value
Brightness switching value A
300 lux
Time delay A
10 min
Short presence A
On
Configuration type
auto
Control input S
auto
Detection sensitivity (PIR)
Stage 3
Group address
T
LED display movement
Off
9. Start-up
Switching behaviour
Every time the power supply is switched on, the presence
detector runs through two phases that are shown on an LED:
1. Start-up phase (30 s)
•
The red LED flashes every second, the switch contact is
closed (light on).
•
The detector does not react to push button commands
and remote control commands.
•
When no one is present the switch contact opens after
30 seconds.
2. Mode
The detector is ready for operation (LED off).
Test presence
Presence test mode is used to test presence detection and
wiring. Presence test mode can be activated with the „Sendo-
Pro 868-A“ management remote control and with the „the-
Senda P“ installation remote control.
Setting the presence test mode via remote control
•
The detector goes directly into test mode when the test
mode is set via the remote control:
y
y
Every movement is indicated by the LED.
y
y
When movement occurs the light switch contact closes.
y
y
When no one is present the light switch contact opens after
10 seconds.
y
y
Brightness measurement deactivates, detector does not react
to brightness.
y
y
The detector reacts as in fully automatic function mode even
if semi-automatic is set.
y
y
Teach-in cannot be activated in test mode.
•
Test mode ends automatically after 10 mins. The detector
performs a new start (see switch-on behaviour).
10. Technical data
Operating voltage
110-230 V AC + 10 % / - 15%
Frequency
50-60 Hz
Upstream protection device:
13 A
Power consumption
approx. 0.1 W
Type of installation
Ceiling installation; Flush/
surface mounted or ceiling
installation
Installation height
2,0 – 3,5 m / max. 10 m
Minimum height
> 1.7 m
Detection area
horizontal
vertical
360°
120°
Maximum range
Ø 8 m (Mh. 3 m) / 50 m
2
radially
moving
Ø 24 m (Mh. 3 m) / 452 m
2
tangentially moving
Setting range brightness switching value 30 – 3000 Lux
Lighting time delay
10 s – 60 min / Pulse
Channel A light
Relay 230 V / 10 A, µ-contact
Max. switching capacity
cos
j
1
resistive
2300 W
Max. switching capacity cos
j
0.5
1150 VA
Max. switching capacity LED
LED lamps < 2 W
LED lamps > 2 W
see manufacturer concerning
cos
j
60 W
180 W
Guidance value max. switch-on peak
800 A / 200 µs
Maximum number EBs T5/T8
16 x 54/58 W, 24 x 35/36 W
8 x 2 x 54/58 W
12x 2x 35/36 W
Connection type
Terminals screws
Max. cable cross-section
max. 2 x 2.5 mm²
Flush-mounted socket size
Siz. 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 54 (installed)
Ambient temperature
-15 °C – 50 °C
CE Declaration of Conformity
This device conforms to the
safety regulations of the EMC
directive 2014/30/EU and of
2014/35/EU.
Product overview
Type of
installation
Channel Ope-
rating
voltage
Colour
Type
Item No.
Ceiling
installation
Light
110-
230 V
AC
White
theRonda
P360 -100 M
2080020
Ceiling
installation
Light
110-
230 V
AC
Grey
theRonda
P360 -100 M
2080021
Ceiling
installation
Light
110-
230 V
AC
Special colour
in accordance
with customer
information
theRonda
P360 -100 M
2080023
Troubleshooting
Fault
Cause
Light does not switch
on and/or off if pre-
sence is detected and
in darkness
Lux value is set too low; detector set on semi-
automatic; light was switched off manually via
push button or „theSenda S“; person not within
detection range; obstruction(s) interrupting detec-
tion; time delay set too short
Light stays on with
detection of presence
despite sufficient
brightness
Lux value is set too high; light was briefly switched
on manually via push button or with „theSenda S“
(wait 30 min.); detector is in test mode