background image

8

LED display motion

The motion detection can be displayed via the LED.

Value range

No display of motion detection.

Off

The LED is switched on when motion is detected, otherwise it 

remains off.

On

Settings are possible with "SendoPro 868-A" management 

remote control or with "theSenda B" app remote control (with 

"theSenda Plug" app).

Factory settings

The thePassa P360-101 UP presence detector is delivered 

with the following parameter values:

Parameter

Value

Detection zone

Z1 and Z2

Brightness setpoint value A

300 lux

Room correction factor A

0.3

Detection sensitivity (PIR)

Increment 3

Time delay A

10 min

Short presence A

On

Time delay H

10 min

Switch-on delay H

0 s

Configuration type

auto

Control input S

auto

Staircase light function

Off

Group address

I

LED display motion

Off

9.  Start-up

Switch-on behaviour

Every time the power supply is switched on, the presence 

detector runs through two phases that are shown by an LED:

9.1.  Start-up phase (30 s)

 

The red LED flashes at one second intervals, both switch 
contacts are closed (light and presence on).

 

The detector does not respond to push button com-

mands and remote control commands.

 

When no one is present, both contacts open after 30 s.

9.2.  Operation

The detector is ready for operation (LED off).

Presence test 

Presence test mode is used to test presence detection and 

wiring. Presence test mode can be activated with "SendoPro 

868-A" management remote control, with "theSenda B" app 

remote control (with "theSenda Plug" app) and with "the-

Senda P" installation remote control.

Setting the presence test mode via remote control

The detector goes directly into test mode when the test mode 

is set via the remote control:

Every movement is indicated by the LED.

 

When movement occurs, the light and presence switch 

contacts close.

¾

y

When no one is present, the light switch contact opens 

after 10 s.

¾

y

Brightness measurement deactivated, detector does 

not react to brightness.

¾

y

The detector reacts as in configuration type fully auto

-

matic device, even if semi-automatic is set.

¾

y

Teach-in cannot be activated in test mode.

¾

y

Test mode ends automatically after 10 min. The detec

-

tor restarts itself (see switch-on behaviour).

10. Technical data

Operating voltage

110-230 V AC + 10% / - 15%

Frequency

50-60 Hz

Upstream protection device:

13 A

Power consumption

approx. 0.1 W

Type of installation

Ceiling installation; flush/

surface mounted or ceiling 

installation

Recommended installation height

2.0 – 6.0 m

Minimum height

> 1.7 m

Detection area 

horizontal

360°

Maximum range

20 x 5 m (Mh. 3.5 m) / 100 m

2

 

radially moving

30 x 5 m (Mh. 3.5 m) / 150 m

2

 

tangentially moving

Setting range brightness setpoint value

30–3000 lux

Light time delay

10 s – 60 min/pulse

Presence time delay

10 s–120 min

Switch-on delay "Presence"

0 s – 10 min

Channel A light

Relay 230 V/10 A, µ-contact

Max. switching capacity  

cos 

j

 1 

resistive

2300 W 

 (max. 10 A)

Max. switching capacity 

cos 

j

 

0.5

1150 VA   

Max. switching capacity LED

LED lamp < 2 W

LED lamp > 2 W

see manufacturer concerning cos 

60 W

180 W

Guidance values max. switch-on current

800 A/200 µs

Maximum number EBs T5/T8

16 x 54/58 W, 24 x 35/36 W

8 x 2x 54/58 W

12 x 2x 35/36 W 

Channel H, presence

Relay, floating, base insulation

Maximum voltage

220 V DC / 250 V AC

Maximum switching capacity

50 W / 50 VA  (max. 2 A)

Recommended minimum load

10 mV / 10 mA

Connection type

Screw terminals

Max. cable cross-section

Max. 2 x 2.5 mm²

Size of flush-mounted box

Size 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 20 (IP 54 installed)

Ambient temperature

-15 °C – 50 °C

CE Declaration of Conformity

This device conforms to the 

safety regulations of the EMC 

directive 2014/30/EU and of 

directive 2014/35/EU. 

Содержание thePassa P360-101 UP WH

Страница 1: ... control theSenda B option and corres ponding app theSenda Plug iOS Android 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the techni...

Страница 2: ...ple are present or it is dark Channel H presence Channel H presence is used for HVAC control The switching response of the floating contact is influenced only by pre sence and not by brightness If the contact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The ...

Страница 3: ...ighting directly below the detector If the brightness measurement is deactivated chan nel A light only switches depending on presence brightness setpoint value set to on via potentiometer or set to mea surement off via remote control 1 8 m Suitable lamps The presence detector is designed for the operation of fluore scent compact fluorescent halogen and incandescent lamps as well as LEDs The maximu...

Страница 4: ... L Light measurement only with the Master Parameters are only set on the Master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePassa P360 101 UP Slave thePassa P360 Slave UP Master Master parallel switching for several lighting groups Several Masters can be used in a parallel switching Each Master controls its lighting group according to its own...

Страница 5: ... only closes when someone is present after expiry of the switch on delay 0 contact closes immediately if people are present Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing Parameter Description Can be que ried by SendoPro 868 A theSenda B app Can be chan ged by SendoPro 868...

Страница 6: ... the furniture With the room correction factor the brightness measurement value of lighting channel A is adjusted to the conditions in the room and in this way can be matched to the lux meter value measured at the surface beneath the presence detector Room correction factor Brightness value at the ceiling brightness value at the working surface Using management SendoPro 868 A remote control and lu...

Страница 7: ...stable values 0 s no switch on delay 30 s 1 10 min Configuration type Fully automatic device The lighting is switched on and off automatically Due to presence absence and brightness SendoPro 868 A theSenda B app auto theSenda P Button A Semi automatic Lights must always be switched on manually Switching off occurs automatically by the presence detector due to absence or brightness SendoPro 868 A t...

Страница 8: ...ment occurs the light and presence switch contacts close y y When no one is present the light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode y y Test mode ends automatically after 10 min Th...

Страница 9: ...e Flickering for 2 s The command sent from the remote control via infrared was accepted by the presence detector Lighting up briefly The command sent from the remote control via infrared was rejected by the presence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Fli...

Страница 10: ...Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda S Item no 9070911 Details www theben de en 12 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzerland Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 4...

Отзывы: